Page 116

5. Diagnosis and error treatment

Faults of fault class 2 No.

Handheld display

Operating status

Fault treatment

40

[CO−Life Guard]

Fault resulting from Life Guard monitoring

Check cabling, check CAN bus load, check Guard Time and Life Factor and adjust if necessary

41

[CO−Heart Beat]

Fault resulting from Heart Beat monitoring

Check cabling, check CAN bus load, check Heart Beat Time, adjust if necessary

42

Reserved

43

[CO−CAN Overrun (Objects lost)]

Telegrams have been lost

Check CAN bus load

44

[CO−Invalid PDO received]

PDO received with two few data Possibly correct PDO mapping or bytes increase number of PDO bytes

45

[CO−CAN WarnLimit reached]

Some defective CAN telegrams have been discovered

Check cabling

46

[CO−CAN recovered from BusOff ]

Defective CAN telegrams have been increasingly discovered

Check cabling; a CAN participant may be defective

47

[CO−Bus Power lost]

No power supply at the CAN interface

Check power supply at Bus and Bus

48...63

Reserved

64

[Number of Modules incorrect]

The number of modules in the current CPX equipment status does not equal the saved equipment status

Correct module equipment status or save new one

65...69

Reserved

70

[CC−L Station equip. status incorrect]

CPX equipment status is greater than the number of stations set

Check DIL switch setting of stations)

5−10

Festo P.BE−CPX−SYS−EN en 0503b

Page 117

5. Diagnosis and error treatment

Faults of fault class 2 No.

Handheld display

Operating status

Fault treatment

71

[CC−L Bus connection lost]

Bus connection interrupted

Check cabling

72...127

Reserved

Possible faults (fault class 2)

Faults of fault class 3 No.

Handheld texts

Operating status

Fault treatment

128

[Switch unit defective]

Hardware defective

Replace module

129

[CBUS asic not ready]

Fault in the CBUS communication

Check module installation

130

[CPU Hardware Trap]

System error has occurred

Replace module if new message after power off/on

131

[CBUS C−manager not ready]

Fault in the CBUS communication

Replace module if new message after power off/on

132 reserved

133

[Remanent memory defective]

Hardware defective

Replace module

134

[Flash system memory defective]

Hardware defective

Replace module

135

[Number of mod. params.more than 64]

Fault in the CBUS configuration

Replace module

136

Reserved

137

[CBUS diagnostic telegram]

An invalid diagnostic telegram was received from a module

Replace module

138

[CBUS init fault (gap)]

Fault in the CBUS configuration

Check module array

139

[Order queue full]

System error has occurred

Replace module if new message after power off/on

140

[CBUS−EEPROM error]

Hardware defective

Replace module

Festo P.BE−CPX−SYS−EN en 0503b

5−11

Page 118

5. Diagnosis and error treatment

Faults of fault class 3 No.

Handheld texts

Operating status

Fault treatment

141

[CBUS C−timeout error]

Fault in the CBUS communication

Replace module if new message after power off/on

142

[CBUS telegram fault]

Fault in the CBUS communication

Replace module if new message after power off/on

143... 199

Reserved

Possible faults (fault class 3)

Faults of fault class 1 No.

Handheld texts

Operating status

Fault treatment

200

[Fault param. transfer module n]

Fault in parameterisation (parameter transfer failed)

Replace module if new message after power off/on

201

[Invalid field bus address]

Address incorrect

Check the DIL switch setting.

202

[Protokoll Asic not ready]

Initialisation of the Asics protocol defective

Replace module if new message after power off/on

203... 254

Reserved

255

[unknown fault]

5−12

Possible faults (fault class 1)

Festo P.BE−CPX−SYS−EN en 0503b

Page 119

5. Diagnosis and error treatment

5.1.2

On−the−spot diagnosis with LEDs The LEDs of the electric modules are situated under the parent cover on the upper part of the module. The right−hand row of LEDs is identical on the different types of modules (standardised).

Field bus node LEDs Field bus nodes have field bus specific LEDs and CPX−specific LEDs. The CPX−specific LEDs are to be found on each CPX field bus node:

1 Field bus specific LEDs (see manual for field bus node)

2

1

2 CPX−specific LEDs (can be found on every node; see section 5.1.3)

PS PL SF M

LED display on the field bus node (example)

Festo P.BE−CPX−SYS−EN en 0503b

5−13

Page 120

5. Diagnosis and error treatment

5.1.3

CPX−specific LEDs

PS (power system) power sensor/logic supply LED (green)

Sequence

Status

Meaning/fault treatment

ON

No fault Operating voltage/ sensor supply applied

Operating voltage/sensor supply outside tolerance range

Eliminate undervoltage

Internal fuse of the ing voltage/sensor supply has responded

1. Eliminate short circuit/overload on module 2. Depends on the parameterisation of the module (module meters): · The sensor supply voltage will be switched on again automati cally when the short circuit is eliminated (default) · Power off/on necessary

Operating voltage/sensor supply not applied

Check operating voltage connection of the electronics

OFF

LED lights up ON OFF

LED flashes ON OFF

ON OFF

LED is out

PL (power load) power load supply (outputs/valves) LED (green)

Sequence

Status

Meaning/fault treatment

ON

No fault Load voltage applied

None

Load voltage at system supply or additional supply outside the tolerance range

Eliminate undervoltage

OFF

LED lights up ON OFF

LED flashes

5−14

Festo P.BE−CPX−SYS−EN en 0503b

Page 121

5. Diagnosis and error treatment

SF (system failure) system fault LED (red)

Sequence 1)

Status

Meaning/fault treatment

ON

No fault

Simple fault/information (fault class 1)

See explanation of error numbers in section 5.1.1

Fault (fault class 2)

See explanation of error numbers in section 5.1.1

Serious fault (fault class 3)

See explanation of error numbers in section 5.1.1

OFF

LED is out ON OFF

LED flashes ON OFF

LED flashes ON OFF

LED flashes 1) The system fault LED flashes depending on the fault class.

Fault class 1 (simple fault): Fault class 2 (fault): Fault class 3 (serious fault):

Festo P.BE−CPX−SYS−EN en 0503b

1 flash, interval 2 flashes, interval 3 flashes, interval

5−15

Page 122

5. Diagnosis and error treatment

M (modify) parametrizing modified or Force active LED (yellow)

Sequence

Status

Meaning/fault treatment

ON

System Start with default parametrizing (factory setting) and current CPX equipment status is set; external parametrizing is possible (pre−setting) 1)

None

Force is active 2)

The Force function is enabled (see system parameter Force mode"; function no. 4402).

System start with saved parametrizing and saved CPX equipment status is set; parameters and CPX equipment status are saved remanently; external parametrizing is blocked 1) 2)

Be careful when replacing CPX valve terminals with saved parametrizing. With these CPX valve terminals, parametrizing is not carried out matically by the higher−order PLC/IPC when the terminal is replaced. In these cases check before replacing to see which settings are required and, if necessary, carry out these settings.

OFF

LED is out

ON OFF

LED flashes ON OFF

LED lights up

1) With CPX−FEC in the operating modes Stand Alone and Remote Controller (control function active) without meaning. 2) The display of the Force function (LED flashes) has precedence over the display of the setting for System start (LED lights up).

5−16

Festo P.BE−CPX−SYS−EN en 0503b

Page 123

5. Diagnosis and error treatment

LEDs on electric modules In addition to the module−specific LEDs, all electric modules usually have a module common error LED for module nosis.

1 Module common

1 error LED (red); exists on all I/O modules

1

2 Status LEDs (e.g. green for digital inputs, yellow for digital outputs)

3 Channel error LED

0

4

0

1

5

1

6

2

7

3

8 DI 2 3

4 DO

(e.g. with digital outputs)

2

2

3

LED display of electric modules (example)

Status LEDs There is a status LED for each channel. This LED indicates the status of the signal. The LEDs indicate the following: Status LED (green or yellow)

Sequence

Status

ON

Channel logical 1 (signal present)

OFF

LED lights up *) ON OFF

Channel logical 0 (no signal)

LED is out 1) Lights up green for inputs and yellow for outputs

Festo P.BE−CPX−SYS−EN en 0503b

5−17

Page 124

5. Diagnosis and error treatment

Module common error LED The red module common error LED indicates a module fault short circuit or overload). The display of faults can be suppressed by module meters.

Module common error LED LED (red)

Sequence

Status

Fault treatment

ON

Faultless operation

None

OFF

LED is out Error−specific See manual for the relevant module

See manual for the relevant module

LED flashes ON OFF

Module common error e.g. (see manual for the module) Eliminate short circuit/undervoltage

LED lights up

Channel error LED Explanations on this can be found in the manual for the relevant CPX module

5−18

Festo P.BE−CPX−SYS−EN en 0503b