The text of a manual · part 15 of 26
CPX terminal Electronics manual: System description, installing and commissioning CPX terminals: Diagnosis and error treatment, pages 116 to 124
Pages 116 to 124 of 221, from CPX terminal Electronics manual: System description, installing and commissioning CPX terminals
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-CP-4-FB
Page 116
5. Diagnosis and error treatment
Faults of fault class 2 No.
Handheld display
Operating status
Fault treatment
40
[CO−Life Guard]
Fault resulting from Life Guard monitoring
Check cabling, check CAN bus load, check Guard Time and Life Factor and adjust if necessary
41
[CO−Heart Beat]
Fault resulting from Heart Beat monitoring
Check cabling, check CAN bus load, check Heart Beat Time, adjust if necessary
42
Reserved
43
[CO−CAN Overrun (Objects lost)]
Telegrams have been lost
Check CAN bus load
44
[CO−Invalid PDO received]
PDO received with two few data Possibly correct PDO mapping or bytes increase number of PDO bytes
45
[CO−CAN WarnLimit reached]
Some defective CAN telegrams have been discovered
Check cabling
46
[CO−CAN recovered from BusOff ]
Defective CAN telegrams have been increasingly discovered
Check cabling; a CAN participant may be defective
47
[CO−Bus Power lost]
No power supply at the CAN interface
Check power supply at Bus and Bus
48...63
Reserved
64
[Number of Modules incorrect]
The number of modules in the current CPX equipment status does not equal the saved equipment status
Correct module equipment status or save new one
65...69
Reserved
70
[CC−L Station equip. status incorrect]
CPX equipment status is greater than the number of stations set
Check DIL switch setting of stations)
5−10
Festo P.BE−CPX−SYS−EN en 0503b
Page 117
5. Diagnosis and error treatment
Faults of fault class 2 No.
Handheld display
Operating status
Fault treatment
71
[CC−L Bus connection lost]
Bus connection interrupted
Check cabling
72...127
Reserved
Possible faults (fault class 2)
Faults of fault class 3 No.
Handheld texts
Operating status
Fault treatment
128
[Switch unit defective]
Hardware defective
Replace module
129
[CBUS asic not ready]
Fault in the CBUS communication
Check module installation
130
[CPU Hardware Trap]
System error has occurred
Replace module if new message after power off/on
131
[CBUS C−manager not ready]
Fault in the CBUS communication
Replace module if new message after power off/on
132 reserved
133
[Remanent memory defective]
Hardware defective
Replace module
134
[Flash system memory defective]
Hardware defective
Replace module
135
[Number of mod. params.more than 64]
Fault in the CBUS configuration
Replace module
136
Reserved
137
[CBUS diagnostic telegram]
An invalid diagnostic telegram was received from a module
Replace module
138
[CBUS init fault (gap)]
Fault in the CBUS configuration
Check module array
139
[Order queue full]
System error has occurred
Replace module if new message after power off/on
140
[CBUS−EEPROM error]
Hardware defective
Replace module
Festo P.BE−CPX−SYS−EN en 0503b
5−11
Page 118
5. Diagnosis and error treatment
Faults of fault class 3 No.
Handheld texts
Operating status
Fault treatment
141
[CBUS C−timeout error]
Fault in the CBUS communication
Replace module if new message after power off/on
142
[CBUS telegram fault]
Fault in the CBUS communication
Replace module if new message after power off/on
143... 199
Reserved
Possible faults (fault class 3)
Faults of fault class 1 No.
Handheld texts
Operating status
Fault treatment
200
[Fault param. transfer module n]
Fault in parameterisation (parameter transfer failed)
Replace module if new message after power off/on
201
[Invalid field bus address]
Address incorrect
Check the DIL switch setting.
202
[Protokoll Asic not ready]
Initialisation of the Asics protocol defective
Replace module if new message after power off/on
203... 254
Reserved
255
[unknown fault]
5−12
Possible faults (fault class 1)
Festo P.BE−CPX−SYS−EN en 0503b
Page 119
5. Diagnosis and error treatment
5.1.2
On−the−spot diagnosis with LEDs The LEDs of the electric modules are situated under the parent cover on the upper part of the module. The right−hand row of LEDs is identical on the different types of modules (standardised).
Field bus node LEDs Field bus nodes have field bus specific LEDs and CPX−specific LEDs. The CPX−specific LEDs are to be found on each CPX field bus node:
1 Field bus specific LEDs (see manual for field bus node)
2
1
2 CPX−specific LEDs (can be found on every node; see section 5.1.3)
PS PL SF M
LED display on the field bus node (example)
Festo P.BE−CPX−SYS−EN en 0503b
5−13
Page 120
5. Diagnosis and error treatment
5.1.3
CPX−specific LEDs
PS (power system) power sensor/logic supply LED (green)
Sequence
Status
Meaning/fault treatment
ON
No fault Operating voltage/ sensor supply applied
Operating voltage/sensor supply outside tolerance range
Eliminate undervoltage
Internal fuse of the ing voltage/sensor supply has responded
1. Eliminate short circuit/overload on module 2. Depends on the parameterisation of the module (module meters): · The sensor supply voltage will be switched on again automati cally when the short circuit is eliminated (default) · Power off/on necessary
Operating voltage/sensor supply not applied
Check operating voltage connection of the electronics
OFF
LED lights up ON OFF
LED flashes ON OFF
ON OFF
LED is out
PL (power load) power load supply (outputs/valves) LED (green)
Sequence
Status
Meaning/fault treatment
ON
No fault Load voltage applied
None
Load voltage at system supply or additional supply outside the tolerance range
Eliminate undervoltage
OFF
LED lights up ON OFF
LED flashes
5−14
Festo P.BE−CPX−SYS−EN en 0503b
Page 121
5. Diagnosis and error treatment
SF (system failure) system fault LED (red)
Sequence 1)
Status
Meaning/fault treatment
ON
No fault
Simple fault/information (fault class 1)
See explanation of error numbers in section 5.1.1
Fault (fault class 2)
See explanation of error numbers in section 5.1.1
Serious fault (fault class 3)
See explanation of error numbers in section 5.1.1
OFF
LED is out ON OFF
LED flashes ON OFF
LED flashes ON OFF
LED flashes 1) The system fault LED flashes depending on the fault class.
Fault class 1 (simple fault): Fault class 2 (fault): Fault class 3 (serious fault):
Festo P.BE−CPX−SYS−EN en 0503b
1 flash, interval 2 flashes, interval 3 flashes, interval
5−15
Page 122
5. Diagnosis and error treatment
M (modify) parametrizing modified or Force active LED (yellow)
Sequence
Status
Meaning/fault treatment
ON
System Start with default parametrizing (factory setting) and current CPX equipment status is set; external parametrizing is possible (pre−setting) 1)
None
Force is active 2)
The Force function is enabled (see system parameter Force mode"; function no. 4402).
System start with saved parametrizing and saved CPX equipment status is set; parameters and CPX equipment status are saved remanently; external parametrizing is blocked 1) 2)
Be careful when replacing CPX valve terminals with saved parametrizing. With these CPX valve terminals, parametrizing is not carried out matically by the higher−order PLC/IPC when the terminal is replaced. In these cases check before replacing to see which settings are required and, if necessary, carry out these settings.
OFF
LED is out
ON OFF
LED flashes ON OFF
LED lights up
1) With CPX−FEC in the operating modes Stand Alone and Remote Controller (control function active) without meaning. 2) The display of the Force function (LED flashes) has precedence over the display of the setting for System start (LED lights up).
5−16
Festo P.BE−CPX−SYS−EN en 0503b
Page 123
5. Diagnosis and error treatment
LEDs on electric modules In addition to the module−specific LEDs, all electric modules usually have a module common error LED for module nosis.
1 Module common
1 error LED (red); exists on all I/O modules
1
2 Status LEDs (e.g. green for digital inputs, yellow for digital outputs)
3 Channel error LED
0
4
0
1
5
1
6
2
7
3
8 DI 2 3
4 DO
(e.g. with digital outputs)
2
2
3
LED display of electric modules (example)
Status LEDs There is a status LED for each channel. This LED indicates the status of the signal. The LEDs indicate the following: Status LED (green or yellow)
Sequence
Status
ON
Channel logical 1 (signal present)
OFF
LED lights up *) ON OFF
Channel logical 0 (no signal)
LED is out 1) Lights up green for inputs and yellow for outputs
Festo P.BE−CPX−SYS−EN en 0503b
5−17
Page 124
5. Diagnosis and error treatment
Module common error LED The red module common error LED indicates a module fault short circuit or overload). The display of faults can be suppressed by module meters.
Module common error LED LED (red)
Sequence
Status
Fault treatment
ON
Faultless operation
None
OFF
LED is out Error−specific See manual for the relevant module
See manual for the relevant module
LED flashes ON OFF
Module common error e.g. (see manual for the module) Eliminate short circuit/undervoltage
LED lights up
Channel error LED Explanations on this can be found in the manual for the relevant CPX module
5−18
Festo P.BE−CPX−SYS−EN en 0503b