Page 107
Diagnosis and error treatment
Chapter 5
Festo P.BE−CPX−SYS−EN en 0503b
5−1
Page 108
5. Diagnosis and error treatment
Contents
5.
Diagnosis and error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−1
5.1
General instructions on diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 Possible error numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.2 On−the−spot diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.3 CPX−specific LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnosis via status bits or the I/O diagnostic interface . . . . . . . . . . . . . . . . 5.2.1 Structure of the status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.2 The I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−4 5−6 5−13 5−14 5−19 5−20 5−22
5.2
5−2
Festo P.BE−CPX−SYS−EN en 0503b
Page 109
5. Diagnosis and error treatment
Contents of this chapter
Further information
This chapter provides an overview of the diagnostic lities with the CPX terminal. These include diagnosis with:
the LED on the electric and pneumatic modules the handheld the 8 status bits (common diagnostic messages)
the I/O diagnostic interface (read out detailed diagnostic information)
field bus specific diagnostic functions.
All diagnostic information can be read via the I/O diagnostic interface. The different field buses support different field bus specific diagnostic functions. Information on this can be found in the manual for the field bus node used. Instructions on diagnosing with the handheld can be found in the manual for the handheld. Information on on−the−spot agnosis with the LED on the I/O modules, on the field bus node or on the valves can be found in the manual for the evant module or in the pneumatics manual.
Festo P.BE−CPX−SYS−EN en 0503b
5−3
Page 110
5. Diagnosis and error treatment
5.1
General instructions on diagnosis The CPX terminal offers extensive possibilities of diagnosis and error treatment. The following possibilities are available (see also
1
2
3
1 On−the−spot diagnosis with LED
3 Diagnosis with the field bus
2 On−the−spot diagnosis with handheld Diagnostic possibilities of the CPX terminal
5−4
Festo P.BE−CPX−SYS−EN en 0503b
Page 111
5. Diagnosis and error treatment
Diagnostic possibilities
Brief description
1
On−the−spot diagnosis with LED
The LEDs on the electric and pneumatic modules show hardware faults, bus faults, etc.
2
On−the−spot diagnosis with the handheld
The handheld: shows current error messages in clear text offers access to the diagnostic memory.
3
System status scanning with the field bus (status bits scanning)
The 8 status bits display common diagnostic messages (global error messages).
System diagnosis with the (via I/O diagnostic interface)
Internal diagnostic data can be read via the I/O diagnostic interface. In this way detailed diagnostic information can be accessed, even if the field bus used does not offer any sive field bus specific diagnostic functions. The I/O diagnostic interface offers: access to the current error message access to the diagnostic memory read access to internal parameters and data.
Field bus specific diagnostic functions
Special diagnostic functions or communication services are available, depending on the field bus used. For example munication services on: the DPVI (PROFIBUS) the PCP channel (Interbus) SDO access (CANopen)
Diagnostic possibilities of the CPX terminal
Festo P.BE−CPX−SYS−EN en 0503b
5−5
Page 112
5. Diagnosis and error treatment
5.1.1
Possible error numbers Detailed information on module−specific diagnosis can be found in the manual for the relevant module. Possible faults of the CPX terminals are divided into three error classes with different priority depending on the ness of the fault. If a fault occurs, the system error LED will flash depending on the error class.
Error class
Flashing sequence of the SF LED
Error weighting
Priority
1
1 * flashes, pause time
Simple (e.g. simple user fault)
Low
2
2 * flashes, pause time
Medium (standard diagnosis and extended diagnosis)
Medium
3
3 * flashes, pause time
High (hardware fault/internal fault)
High
Error classification If several faults occur together, the fault with the highest priority will have precedence. This means that:
the system error LED flashes according to the higher priority.
the number of the fault with the higher priority will be entered in the system diagnostic data under function number 1938 (error number).
Within an error class faults of modules with a lower module number have higher priority, e.g. faults of module number 0 have the highest priority within an error class. Faults of ule number 1 have the second highest priority, etc.
5−6
Festo P.BE−CPX−SYS−EN en 0503b
Page 113
5. Diagnosis and error treatment
Faults of fault class 2 No.
Handheld display
Operating status
Fault treatment
0
[No error]
No fault
1
[General diagnosis]
General diagnosis (module−specific fault)
See manual for the module
2
[Short circuit]
Short circuit/overload in sensor Eliminate short circuit/ overload supply or output (see manual for
3
[Wire fracture/idling current I/O]
Break in wire/idling current input/output
Check and, if necessary, replace the cable and connected sensors/ actuators
4
[Short circuit in actuator supply]
Failure in load voltage supply due to short circuit/overload (on output side)
Check connected actuators as well as their connections
5
[Undervoltage in power supply]
Undervoltage in the power supply (on the input side)
Eliminate undervoltage at system supply or additional supply (pin assignment see
6...8
Reserved
9
[Lower limit exceeded]
Less than rated range
Check signal area and parameterised limit
10
[Upper limit exceeded]
Rated range exceeded
Check signal area and parameterised limit
11
[Short circuit valve]
Short circuit at the valve
Check valve and pneumatic interface
12
Reserved
13
[Wire fracture (open load)]
Wire break at valve
Check valve
14
Reserved
15
[Module/channel failure]
Module/channel has failed
Check module
Festo P.BE−CPX−SYS−EN en 0503b
5−7
Page 114
5. Diagnosis and error treatment
Faults of fault class 2 No.
Handheld display
Operating status
Fault treatment
16
[Module code incorrect]
Module code not permitted or incorrect module
· Check CPX equipment status or
With CPX−CP interface: The saved string assignment of the CPX−CP interface is not the same as the ation saved in the CPX field bus node or CPX−FEC
With CPX field bus node: · Modify the System Start meter to Default ing and current CPX equipment status" With CPX−FEC: · Save the actual configuration as nominal configuration with FST software
Number of I/O points exceeded
Check the DIL switch settings.
Fault in parameterisation parameter)
Check the parameterisation dertaken and, if necessary, take the parameterisation again with the correct parameters.
save CPX equipment status again (procedure see meter System start; function
17
Reserved
18
[Address range exceeded]
19...20
Reserved
21
[Fault in parametrizing data format]
22
Reserved
23
[Fault in filter meas.value]
Fault in parameterisation (parameter measurement value smoothing")
Check the parameterisation dertaken and, if necessary, take the parameterisation again with the correct parameters.
24
[Fault in parametrizing lower limit]
Fault in parameterisation (parameter lower limit")
Check the parameterisation dertaken and, if necessary, take the parameterisation again with the correct parameters.
25
[Fault in parametrizing upper limit]
Fault in parameterisation (parameter upper limit")
Check the parameterisation dertaken and, if necessary, take the parameterisation again with the correct parameters.
5−8
Festo P.BE−CPX−SYS−EN en 0503b
Page 115
5. Diagnosis and error treatment
Faults of fault class 2 No.
Handheld display
Operating status
Fault treatment
26
[Fault in actuator supply]
Fault in actuator supply
1. Eliminate short load or check actuator supply, if necessary, check connected actuators
27...29
Reserved
30
[No new output data (slave)]
Fault in CBUS communication (no new output data)
Module exchange with renewed message after Power Off/On
31
[No bus Bus connection interrupted connection (slave)]
Make bus connection or check configuration
32
[No STI read access (slave)]
STI read access defective
Repeat STI read access
33
[No parameter access (slave)]
Read access parameter defective
Repeat read access parameter
34
[CP module lost / fault]
Incorrect string assignment ascertained during operation (e.g. CP module failed or CP cable defective) More than one module failed during operation modules are no longer recognized
· Check CP strings (CP modules
[CP configuration failure]
When the power supply is switched on, the string assignment does not match the saved string assignment or Incorrect module recognized during operation (different type, see manual for CPX−CP interface)
· Check CP strings (CP modules
[Short circuit CP−Line]
Short circuit CP string Communication faulty on the CP string
· Check CP string, replace CP
35
36
37...39 and CP cables), if necessary replace CP modules or CP cables · Switch power supply off and then on again. If fault still occurs, check and, if necessary, replace CP cables and CP modules and CP cables), if necessary replace CP modules or CP cables · With correct string assignment: String assignment must be saved or (see manual for CPX−CP interface) · Check string assignment, if necessary replace CP module cable if necessary
Reserved
Festo P.BE−CPX−SYS−EN en 0503b
5−9