Page 133

Technical appendix

Appendix A

Festo P.BE−CPX−SYS−EN en 0503b

A−1

Page 134

A. Technical appendix

Contents

A.

Technical appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A−1

A.1 A.2

Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable length and cross−sectional area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A−3 A−6

A−2

Festo P.BE−CPX−SYS−EN en 0503b

Page 135

A. Technical appendix

A.1

Technical specifications

General information Temperature range Operation Storage/transport

− 5 ... + 50 °C − 20 ... + 70 °C

Relative humidity non−condensing

Protection against electric shock (protection against direct and indirect contact as per EN 60204−1/IEC 204)

By means of PELV power units (Protected Extra−Low Voltage)

Protection class as per EN 60 529 (plug connector inserted or provided with protective cap)

Depending on the connections and configuration used. The lowest protection class of the weakest components used is always valid for the complete device (see manual for the relevant module) e.g. terminal connections: IP20 e.g. M8 and M12 connections: IP65 and IP67

Electromagnetic compatibility Interference emitted Immunity against interference Vibration and shock 3) Vibration

Shock

Resistance to continuous shock

Tested as per EN 61000−6−4 (industry) 1) Tested as per EN 61000−6−2 (industry) Tested as per DIN/IEC 68/EN 60068 part 2−6; when fitted on a wall 2): severity class 2 when fitted on a hat rail 2): severity class 1 Tested as per DIN/IEC 68/EN 60068 part 2−27; when fitted on a wall 2): severity class 2 when fitted on a hat rail 2): severity class 1 Tested as per DIN/IEC 68/EN 60068 part 2−29; fitting onto a wall or hat rail: severity class 1

1) The component is intended for industrial use. 2) For MPA valve terminals, the vibration and shock resistance depends on the number of installed sub−bases (see pneumatic description). 3) Explanations on the severity classes see following table.

Festo P.BE−CPX−SYS−EN en 0503b

A−3

Page 136

A. Technical appendix

Severity class

Vibration

Shock

Continuous shock

1

0.15 mm path at 10...58 Hz 2 g acceleration at 58...150 Hz

± 15 g at 11 ms duration 5 shocks per direction

± 15 g at 6 ms duration; 1000 shocks per direction

2

0.35 mm path at 10...60 Hz 5 g acceleration at 60...150 Hz

± 30 g at 11 ms duration 5 shocks per direction

Operating voltage for the bus interface Rated value Tolerance

See manual for the CPX field bus node

Caution The maximum permitted current per pin on the supply is: 16 A. Note that with system supply via pin 3 (0 V), the sum of both currents from pin 1 and pin 2 flows via pin 2. M18 plug: 16A 7/8 plug, 4−pin: 12 A*) 7/8 plug, 5−pin: 12 A*) *) limited by the specifications of the connected plug nector. Please note that with system supply with 4 pin plug via pin 0 V", the sum of both currents of the operating and load voltages flows.

Operating voltage for electronics/sensor supply Power supply Rated value Tolerance

24 V DC (protected against incorrect polarity) 18...30 V

Current consumption

Sum of the current consumption of all modules without sensor supply; max. 1.5 A; see also the manual for the modules

Residual ripple

4 Vpp (within tolerance)

A−4

Festo P.BE−CPX−SYS−EN en 0503b

Page 137

A. Technical appendix

Load voltage for outputs Power supply Rated value Tolerance

24 V DC (protected against incorrect polarity) 18...30 V

Current consumption

Sum of all switched−on outputs (see manual for output modules)

Residual ripple

4 Vpp (within tolerance)

Load voltage for the valves Power supply Rated value

24 V DC (protected against incorrect polarity)

Tolerance *)

Without pneumatics: With pneumatics of type Midi/Maxi: With pneumatics of type CPA: With pneumatics of type MPA: With CPX−CP interface:

Current consumption

Current consumption of the pneumatic interface: See manual for the CPX I/O modules Sum of all switched−on valve solenoid coils; see Pneumatics Manual

Residual ripple

4 Vpp (within tolerance)

18...30 V 21.6...26.4 V 20.4...26.4 V 18...30 V 20.4...26.4 V

*) The module with the lowest tolerance is always decisive for the permitted voltage tolerances

(see manual for relevant module or for relevant pneumatics).

Special technical specifications on the pneumatics used, on CPX modules, sub−bases and the field bus node can be found in the relevant manuals.

Festo P.BE−CPX−SYS−EN en 0503b

A−5

Page 138

A. Technical appendix

A.2

Cable length and cross−sectional area

Please note The following information assumes that the reader is iar with the facts contained in the chapter Installation" in this manual, and is for the exclusive use of personnel trained in electrotechnology. A load−dependent drop in voltage occurs on all three cables of theoperating voltage supply to a node. This can cause the voltage at pin 1 or pin 2 of the operating voltage connection to be outside the permitted tolerance. Recommendation: ·

Avoid long distances between the power unit and the node.

·

Ascertain the most suitable cross−sectional area and the maximum cable length for the operating voltage cable in accordance with the following formula.

Please note The following formula assumes that the cross−sectional areas of the operating voltage supply are the same.

A−6

Festo P.BE−CPX−SYS−EN en 0503b

Page 139

A. Technical appendix

Ascertain by formula Proceed as follows: 1. Calculate the maximum current consumption of the inputs and electronics (I1) as well as of the outputs and valves (I2). 2. Ascertain the lowest voltage to be expected during ation (VBmin) on the power unit. Take the following into account: · the load dependency of the power unit

· the fluctuations in the primary mains voltage

· the operating temperature of the devices.

3. Enter the values in the relevant formula. The equivalent circuit diagram as well as the example explain the tions.

Festo P.BE−CPX−SYS−EN en 0503b

A−7

Page 140

A. Technical appendix

Power supply

Equivalent circuit diagram

VB

I1: Electronics/sensors I2: Outputs/valves AC DC

RL1 Terminal I1 Pin *) : I2 : Pin *)

VL1

RL2

VL2

1

I1

I2

RI1

RI2

RL0

VL2+VL1

VOUT/VAL

I0 : Pin *)

2

L

3

*) Pin assignment, see

1 Line resistor (outgoing) RL1 + RL2 2 Line resistor (returning) RL0 3 L = distance (cable length) Equivalent circuit diagram for power supply

A−8

Festo P.BE−CPX−SYS−EN en 0503b

Page 141

A. Technical appendix

Formula for maximum cable length:

Lv

NJǒV Bmin * V OUTńVALminǓ @ A @ ËCUNj {2 @ l 2 ) l 1}

Meaning ·

Without pneumatics: With Midi/Maxi pneumatics: With CPA pneumatics:

·

VBmin = minimum operating voltage supply (on the power unit)

·

Current I1 = current for electronics and sensors

·

Current I2 = current for valves and outputs

·

A = cross−sectional area (uniform e.g. 1.5 mm2)

·

κ = conductance value of the cables (uniform e.g. κCU = 56

Example: I1 I2 VBmin CPA pneumatics:

κCU = 56

VOUT/VALmin w 18 V VOUT/VALmin w 21.6 V VOUT/VALmin w 20.4 V m ) mm2 @

=1A =5A = 24 V VOUT/VALmin = 20.4 V m mm2 @

Result: L ≤ 27.49 m for A = 1.5 mm2 L ≤ 45.81 m for A = 2.5 mm2

Festo P.BE−CPX−SYS−EN en 0503b

A−9

Page 142

A. Technical appendix

A−10

Festo P.BE−CPX−SYS−EN en 0503b