Page 207

C. General information on parametrizing

C.3.3

Signal status in Idle status (Idle mode) This function is only relevant with certain field bus protocols (see manual for CPX field bus node).

Basic information The so−called Idle mode parameterisation helps determine which signal status outputs/valves should take when ing into the Idle status. In this way a defined machine/system status should be created.

Warning Depending on the function of the machine/system, the manipulation of signal states can cause serious injury to human beings and damage to property. Use the Idle mode parameterisation very carefully, in order to avoid damage.

CPX parameterisation With CPX terminals, Idle mode parameterisation can be used for:

digital outputs analogue outputs valves.

By means of the system parameter Idle mode, you can bally determine the signal status which the outputs/valves are to assume when changing into the Idle status.

Festo P.BE−CPX−SYS−EN en 0503b

C−19

Page 208

C. General information on parametrizing

System parameters

Settings

Description

System Idle mode

Reset outputs (presetting)

Reset all outputs/valves

Hold last state

Retain current signal status for all outputs/ valves

Assume Idle mode value

Accept the signal status defined for the relevant channel

System parameter System Idle mode If Accept Idle mode value" is activated, the signal states defined by module parameter for the relevant channel will become effective (see

Module parameters

Settings

Description

Idle mode

Hold last state

Retain current signal status

Idle state (presetting)

Accept the signal status defined by the Idle state

Reset output (presetting)

Reset output signal (output/valve)

Set output

Set output signal (output/valve)

Analogue value

Value of the analogue signal

Idle state Digital signal

Analogue signal

Module parameters Idle mode" and Idle state"

Method of operation Is functionally identical with the Fail safe parameterisation (see also and

C−20

Festo P.BE−CPX−SYS−EN en 0503b

Page 209

C. General information on parametrizing

C.4

Diagnostic memory Basic information A diagnostic memory serves for protocolling fault states. If the time when faults occur and if fault sequences are tered, this will facilitate the search for the cause of the faults which are otherwise difficult to locate. If the causes are inated, faults can be avoided over long periods.

CPX parameterisation Various diagnostic memory filters can be parameterised by means of diagnostic memory parameters (see section B.2.4). With these filters the registering of certain system states can be suppressed, and both starting and stopping can be trolled. The method of operation of the diagnostic memory filters is shown in

Festo P.BE−CPX−SYS−EN en 0503b

C−21

Page 210

C. General information on parametrizing

Start: Fault

Run/Stop filter 1

The first 40 faults or the last 40 faults

Fault end filter

Register end of fault or not

Fault number filter

Register defined fault number or not

Module/channel filter

Register only fault number of a module/channel

Run/Stop filter 2

0 = Always register 1 = Register up to the defined FN Diagnostic memory

2 = Register up to the defined FN + MN 3 = Register up to the defined FN + MN + CN 4 = Register as from the defined FN 5 = Register as from the defined FN + MN 6 = Register as from the defined FN + MN + CN MN = module number, CN = channel number, FN = fault number

The method of operation of the diagnostic memory filters

C−22

Festo P.BE−CPX−SYS−EN en 0503b

Page 211

C. General information on parametrizing

Method of operation With the CPX terminals the start and end of a fault can be protocolled in the internal diagnostic memory. The diagnostic memory contains up to 40 entries. In addition to information on localising the fault, the relevant time point is saved, measured from the moment the power supply is switched on. a diagnostic entry consists of 10 bytes. The first five bytes contain information on the time point. The last five bytes tain information on the fault (see section B.2.5). With the aid of the function number, entries in the diagnostic memory can be read out via the I/O diagnostic interface spective of the field bus protocol used. The various field bus protocols provide, where applicable, further possibilities for reading out and configuring the CPX diagnostic memory (see the manual for the CPX field bus node).

Festo P.BE−CPX−SYS−EN en 0503b

C−23

Page 212

C. General information on parametrizing

C.5

Monitoring faults Basic information Monitoring functions which run automatically can be vated and deactivated by parameterisation. The activation of monitoring functions helps to guarantee the functionality of the machine/system and to avoid ary idle periods. The deactivation of monitoring functions helps to avoid disturbing error messages, e.g.:

during commissioning.

during an EMERGENCY STOP, if the EMERGENCY STOP concept of the machine/system requires that the load voltage for the valves and output modules be switched off. The error messages (e.g undervoltage), which are triggered when the load voltage is switched off, should be frequently suppressed here.

CPX parameterisation The CPX terminal permits the monitoring of various types of fault (e.g. short circuit, wire fracture, undervoltage, etc.). The different monitoring functions can be activated or deactivated globally by system parameters for the complete CPX terminal and by module parameters for a single CPX module or an individual channel. Activation of a monitoring function causes the following:

C−24

Festo P.BE−CPX−SYS−EN en 0503b

Page 213

C. General information on parametrizing

Monitoring

Reaction to activation

Module parameters Monitoring

A fault on the module will be: passed on to the CPX field bus node displayed by the module common error LED

System parameters Monitoring

A fault registered by the module will be: sent to the higher−order field bus master displayed by the red on the node entered in the module diagnostic data and, if applicable, in the status bits entered, if applicable, in the diagnostic memory

Monitoring The reaction of the channel fault LED will be controlled mally by hardware functions and does not therefore depend on the setting of the monitoring functions. The following monitoring functions can be activated or vated globally:

System parameter monitoring

Description

Undervoltage in valves

Monitors the load voltage supply for the valves

Undervoltage in the outputs

Monitors the load voltage supply for the outputs

Short circuit/overload at the outputs

Monitors whether outputs are overloaded or short circuited

Short circuit/overload in sensor supply

Monitors whether sensor supply is overloaded or short circuited

System parameter monitoring

Festo P.BE−CPX−SYS−EN en 0503b

C−25

Page 214

C. General information on parametrizing

The following monitoring functions can be activated or vated by modules, providing the module supports the evant monitoring function: Module parameter monitoring

Description

Short circuit/overload in sensor supply

Monitors whether sensor supply is overloaded or short circuited

Short circuit/overload at the outputs

Monitors whether outputs are overloaded or short circuited

Undervoltage for outputs/valves

Monitors the load voltage supply for the valves/outputs

Short circuit/overload at the valve

Monitors whether valve outputs are overloaded or short circuited

Upper/lower limit

Monitors the upper/lower limit

Parameterisation fault

Monitors the parameterisation module (plausibility check)

Monitoring wire fracture (channel−specific)

Monitoring can be activated and deactivated for each channel (0 = inactive; 1 = active).

Module parameter monitoring The meaning of the module parameter depends on the ule used. Detailed information can be found in the manual for the relevant module.

C−26

Festo P.BE−CPX−SYS−EN en 0503b