The text of a manual · part 24 of 26
CPX terminal Electronics manual: System description, installing and commissioning CPX terminals: General information on parametrizing, pages 198 to 206
Pages 198 to 206 of 221, from CPX terminal Electronics manual: System description, installing and commissioning CPX terminals
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-CP-4-FB
Page 198
C. General information on parametrizing
Memory
1 0
Idle mode is only relevant for certain field bus protocols 0
No
Yes
Memory
1 0
0
Yes
No
Force
0 1 disable enable disable
1
Output
1 Status LED of the respective output Influencing output signals C−10
Festo P.BE−CPX−SYS−EN en 0503b
Page 199
C. General information on parametrizing
Influencing input signals Input
Force
0 1
1 disable enable disable
1 Status LED of the respective input Influencing input signals Forcing of an input does not change the input signal and can also not be observed on the corresponding situation LED. The logical status of the input only changes internally and may be effective programme technically. Obtain further information on Idle mode, Fail safe and Forcing from the following sections.
Festo P.BE−CPX−SYS−EN en 0503b
C−11
Page 200
C. General information on parametrizing
C.3.1
Force Basic information The function Force permits the manipulation of signal states independent of actual operating conditions. Force enables input and output signals to be overwritten, Input signals actually present or changes of status by program will be nored. The input signals actually present and the output nals generated by the user program only become valid again when the function Force is deactivated.
Warning Depending on the function of the machine/system, the manipulation of signal states can cause serious injury to human beings and damage to property. Use the Force function very carefully, in order to avoid damage. The Force" function is used mainly in the commissioning phase in order to set certain signals to the desired status for test purposes even if the wiring is not complete.
CPX parameterisation With CPX terminals, Force parameterisation can be used for:
C−12 digital inputs digital outputs valves
I/Os of the I/O diagnostic interface and status bits analogue inputs analogue outputs.
Festo P.BE−CPX−SYS−EN en 0503b
Page 201
C. General information on parametrizing
By means of a system parameter, Force is enabled globally for the CPX terminal or blocked. System parameters
Settings
Description
Force mode
Blocked (presetting)
Force is blocked for the complete CPX terminal
Enabled
Force is enabled for the complete CPX terminal
System parameter Force mode The signal status can be determined channel−orientated (output/valve/input) for each module (see following table).
Module parameters
Settings
Description
Force mode
Blocked (presetting)
Force is blocked for the channel
Force state
Accept the signal status defined by Force state
Rest signal (presetting)
Reset input/output signal
Set signal
Set input/output signal
Analogue value (0 = presetting)
Value of the analogue signal
Force state Digital signal Analogue signal
Module parameters Force mode" and Force state"
Festo P.BE−CPX−SYS−EN en 0503b
C−13
Page 202
C. General information on parametrizing
Method of operation Input information actually present will be replaced by the values entered in the Force table in the process image inputs. Information actually present in the process image outputs will be replaced by the values entered in the Force table and transmitted to the physical outputs. 1
1
1
0
1
0
1
0
Force mode 0 = Force blocked 1 = Force state
1
1
0
0
1
0
0
0
Force state 0 = Reset signal 1 = Set output
0
1
0
1
0
1
1
0
0
1
1
0
0
0
1
0
1
2
3 1 Signal status previously
3 Signal status afterwards
2 Module parameter (channel−orientated) Force parameterisation Example for binary signals
C−14
Festo P.BE−CPX−SYS−EN en 0503b
Page 203
C. General information on parametrizing
1
2
Force mode 0 = Force blocked 1 = Force state
321 288 333 432 400 505 11
500
0
0
0
0
100 505 100 321 202 110
80
50
100 505 333 432 202 505 11
500
1
1
0
1
Force state
3 1 Analogue signal previously
3 Analogue signal afterwards
2 Module parameter (channel−orientated) Force parameterisation Example for analogue signals
Festo P.BE−CPX−SYS−EN en 0503b
C−15
Page 204
C. General information on parametrizing
C.3.2
Signal status in the event of a fault (Fail safe) Basic information With the aid of the so−called Fail safe parameterisation, the signal status which the outputs are to assume in the event of field bus communication faults, can be determined (Fail safe status). In this way, a defined machine/system status should be created in the event of field bus communication faults (e.g. failure of the higher−order PLC/IPC).
Warning Depending on the function of the machine/system, the manipulation of signal states can cause serious injury to human beings and damage to property. Use the Fail safe parameterisation very carefully, in order to avoid damage.
CPX parameterisation With CPX terminals, Fail safe parameterisation can be used for:
digital outputs analogue outputs valves.
By means of the system parameter Fail safe, you can globally determine the signal status which the outputs/valves are to assume in the event of field bus communication faults, e.g. in the event of:
C−16 communication failure (bus interruption, PLC failure)
communication stop.
Festo P.BE−CPX−SYS−EN en 0503b
Page 205
C. General information on parametrizing
System parameters
Settings
Description
Fail safe
Reset outputs (presetting)
Reset all outputs/valves
Hold last state
Retain current signal status for all outputs/ valves
Assume Fault mode value
Accept the signal status defined for the relevant channel
System parameter Fail safe" If Accept fault mode value" is activated, the signal states defined by module parameter for the relevant channel will become effective (see
Module parameters
Settings
Description
Fault mode
Hold last state
Retain current signal status
Fault state (presetting)
Accept the signal status defined by Fault state
Reset output (presetting)
Reset output signal (output/valve)
Set output
Set output signal (output/valve)
Analogue value
Value of the analogue signal
Fault state Digital signal
Analogue signal
Module parameters Fault mode" and Fault state"
Method of operation The Fault mode" parameter is used to determine whether the current signal status is to be retained or whether the nal status defined by Fault state" is to be accepted.
Festo P.BE−CPX−SYS−EN en 0503b
C−17
Page 206
C. General information on parametrizing
1
1
0
0
1
1
1
0
Fault mode 0 = hold last state 1 = Fault state
0
1
0
1
1
1
0
0
Fault state 0 = Reset output 1 = Set output
0
0
0
1
0
1
0
0
1
0
0
1
0
1
1
0
100 321 444 230 700 604
0
333
0
0
0
1
2
3 1 Signal status before the fault
3 Signal status after the fault
2 Module parameter (channel−orientated) Fail safe parameterisation Example for binary signals
1
2
Fault mode 0 = hold last state 1 = Fault state
1
0
1
1
1
Fault state
222 500 500 500 333 321 100 200
3
100 500 444 500 333 321
1 Signal status before the fault
0
333
3 Signal status after the fault
2 Module parameter (channel−orientated) Fail safe parameterisation Example for analogue signals C−18
Festo P.BE−CPX−SYS−EN en 0503b