Page 189

General information on parametrizing

Appendix C

Festo P.BE−CPX−SYS−EN en 0503b

C−1

Page 190

C. General information on parametrizing

Contents

C.

General information on parametrizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C−1

C.1 C.2 C.3

C.4 C.5

Input debouncing time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−4 Signal extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−6 Influence of signal states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−9 C.3.1 Force . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−12 C.3.2 Signal status in the event of a fault (Fail safe) . . . . . . . . . . . . . . . . . C−16 C.3.3 Signal status in Idle status (Idle mode) . . . . . . . . . . . . . . . . . . . . . . C−19 Diagnostic memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−21 Monitoring faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−24

C−2

Festo P.BE−CPX−SYS−EN en 0503b

Page 191

C. General information on parametrizing

Contents of this appendix

Further information

This appendix contains general information on ing the following:

input debouncing times signal extension times the signal status in the event of a fault (Fail safe)

the function forces the diagnostic memory the monitoring of faults.

Information on the structure of all the parameters and data of the CPX terminal can be found in appendix A. Information on the parameters and data which are supported by the field bus used, can be found in the manual for the field bus node used. Instructions on parameterisation via the handheld can be found in the manual for the handheld.

Festo P.BE−CPX−SYS−EN en 0503b

C−3

Page 192

C. General information on parametrizing

C.1

Input debouncing time Basic information Input debouncing times are specified in order to eliminate interfering changes of signal edge during switching cedures (bouncing of the input signal). For example, ical switches generate brief undesired signal edges during switching procedures. The signal states which are thereby produced can cause interference in the control sequence and should therefore frequently be suppressed. Interfering, undesired signal edges can be suppressed by a PLC program in the higher−order controller. Interference can therefore be avoided. With the CPX terminals, undesired nal edges can be suppressed simply by parameterisation.

CPX parameterisation With the CPX terminals, the input debouncing time can be set with an appropriate module parameter. The possible input debouncing times therefore depend on the particular type of module. Typical input debouncing times are: 3 ms (typical presetting), 10 ms and 20 ms.

Method of operation Changes of edge in the sensor signal will be accepted as a logical input signal (see only when the specified debouncing time has expired.

C−4

Festo P.BE−CPX−SYS−EN en 0503b

Page 193

C. General information on parametrizing

Time diagram 2

2

1 Start

3

Start

Start

End

Start

Start

Start

End

1 0

4

1 0 Start End

= debouncing time started = debouncing time completely expired Sensor signal is unstable (shorter than debouncing time) Sensor signal is sufficiently stable (= debouncing time)

1 Start and end (sequence) of the debouncing time

2 Debouncing time has expired

3 Sensor signal 4 Logical CPX signal

Input debouncing

Festo P.BE−CPX−SYS−EN en 0503b

C−5

Page 194

C. General information on parametrizing

C.2

Signal extension Basic information Signal extension times are specified when very short signals are to be taken into account in the control process. Short signals can occur, e.g. when an intermediate position is ceeded and evaluation is necessary in order to produce a time−optimised consequent process before an end position is reached. Depending on the type of sensor, the length of the signal, which is generated when the intermediate position is ceeded, can fluctuate according to the positioning speed. There is a danger here that the short signals are not always recognized" due to long cycle times of the higher−order troller. With CPX terminals, a signal extension time can be defined by parameterisation of the appropriate input signal. Short nals will then also be recognised reliably by the higher−order controller.

CPX parameterisation With the CPX terminals, the signal extension time for the ule is set with the appropriate module parameter. The ible signal extension times depend on the type of module. Typical signal extension times are: 15 ms, 50 ms and 100 ms. The signal extension time for each channel can be activated or deactivated with a further channel−orientated module meter. When preset, the signal extension time is inactive.

C−6

Festo P.BE−CPX−SYS−EN en 0503b

Page 195

C. General information on parametrizing

Method of operation Signal states accepted as logical input signals usually remain valid at least until the specified minimum signal duration has expired. Change of edge within the minimum signal duration are ignored (see Fixed debouncing times remain effective.

Case 1: Change of edge within the signal extension time The logical CPX signal is supplied when the signal extension time and, if applicable, the debouncing time has expired.

1 Sensor signal 2 Logical CPX signal 3 Change of edge within the signal extension time

3 a) Rising edge 1

1 2

0 1 0

3 b) Falling edge

1 2

1 0 1 0 Expiry of the debouncing time Expiry of the signal extension time

Change of edge within the signal extension time

Festo P.BE−CPX−SYS−EN en 0503b

C−7

Page 196

C. General information on parametrizing

Case 2: Change of edge after expiry of the signal extension time The logical CPX signal follows the input signal and is supplied after it. If a debouncing time has been defined, the logical CPX signal is supplied when the debouncing time has pired.

1 Sensor signal 2 Logical CPX signal 3 Change of edge after expiry of the signal extension time

3 a) Rising edge 1

1 2

0 1 0

3 b) Falling edge

1 2

1 0 1 0

Expiry of the debouncing time Expiry of the signal extension time

Change of edge after expiry of the signal extension time

C−8

Festo P.BE−CPX−SYS−EN en 0503b

Page 197

C. General information on parametrizing

C.3

Influence of signal states You can influence the signal states of the CPX terminal through the following functions:

Function

Priority Brief description

Signals able to be influenced

Forces 2)

1

Influences signal states independently of actual signal states (see also section C.3.1).

I/O signals

Fail safe

2

Determines signal states that become effective with field bus communication faults (see also section C.3.2).

O signals

Idle mode

3

Determines signal states that become effective when changing into the Idle status (see also section C.3.3).

O signals

1)

1) Only relevant for certain field bus protocols. 2) Mainly used for test purposes in the commissioning phase.

Functions for influencing signal states If several functions are active simultaneously, the following applies:

Force signals have the highest priority.

Fail safe signals have precedence over Idle mode signals.

Overview on the Force, Fail safe and Idle mode functions Influencing output signals With system parameters, you enter the fundamental settings for the respective function. With appropriate setting of the system parameter, you can determine, through cific module parameters, the desired signal state for each channel individually. The following diagrams give an overview of this:

Festo P.BE−CPX−SYS−EN en 0503b

C−9