Page 183
B. Parameters and data of the CPX terminal
System data: Idle mode Function no.
1
Description
Specifies whether Idle mode is active or inactive.
Bit
Bits 2, 3
Values Bit 3 2 0 0 0 1 1 1
Idle mode Description Reset all outputs Hold last state (retain signal status) Assume Idle mode
[Idle mode] [Reset outputs] [Hold last state] [Assume idle mode]
Idle mode System data: Monitoring the CPX terminal Function no.
2
Description
Specifies whether the monitoring of short circuit/overload and undervoltage is active or inactive. Bit 0 1 2 3 4 5 6 7
Monitoring Description Short circuit/overload in sensor supply Short circuit/overload at the outputs Undervoltage outputs (VOUT) Undervoltage at valves (VVAL) Short circuit at the valve Reserved Reserved Reserved
Values
1 = Active 0 = Inactive
Note
See system parameter Diagnostic monitoring".
[Monitor] [Monitor SCS] [Monitor SCO] [Monitor Vout] [Monitor Vval] [Monitor SCV]
Monitoring the CPX terminal
Festo P.BE−CPX−SYS−EN en 0503b
B−41
Page 184
B. Parameters and data of the CPX terminal
System data: Number of input bytes (Rx size) Function no.
Description
Specifies the number of input bytes of the CPX terminal.
Note
Only relevant with certain field bus protocols (see manual for CPX field bus node)
Number of input bytes System data: Number of output bytes (Tx size) Function no.
Description
Specifies the number of output bytes of the CPX terminal.
Note
Only relevant with certain field bus protocols (see manual for CPX field bus node)
Number of output bytes
B−42
Festo P.BE−CPX−SYS−EN en 0503b
Page 185
B. Parameters and data of the CPX terminal
B.2.9 Module data The following module data is available for identifying modules: Function no.
Module data
16 +16m + 0
Module code
16 +16m + 13
Revision code
784 + m * 4 + 0 784 + m * 4 + 1 784 + m * 4 + 2 784 + m * 4 + 3
Series number m = module number
Overview of module data Module data: Module code Function no.
16 + 16m + 0
Description
Specifies the module code of the module (see also
Bit
0...7
Values
Module code 0 1...63 64...79 80...127 128...152: 153...196: 197...201: 202...245: 246...255:
Note m = module number (0...47)
[Module code] Reserved Digital modules Pneumatic interfaces Pneumatic modules Analogue modules Function or technology modules Special modules Field bus node Reserved
See manual for the relevant module
Module code
Festo P.BE−CPX−SYS−EN en 0503b
B−43
Page 186
B. Parameters and data of the CPX terminal
Module
Module type
Handheld display
1 2 3 4 66 67 80 81 82 83 128 129 153 154 155 156 157 15... 195 202 203 204 205 206 20... 208 210
Input module CPX−4DE Input module CPX−8DE Output module CPX−4DA Multi I/O module CPX−8DE−8DA Pneumatic interface CPX−GP−CPA−... Pneumatic interface CPX−GP−03−4.0 MPA electronic module VMPA1−FB−EMG−8 MPA electronic module VMPA2−FB−EMG−4 MPA electronic module VMPA1−FB−EMS−8 MPA electronic module VMPA2−FB−EMS−4 Inut module CPX−2AE−U−I Output module CPX−2AA−U−I Bus node CPX−FB13; Remote Controller Bus node CPX−FB06; Remote Controller Bus node CPX−FB11; Remote Controller Bus node CPX−FB14; Remote Controller Bus node CPX−FB23; Remote Controller Bus node CPX−FB...; Remote Controller Technology module CPX−CP−4−FB Bus node CPX−FB13; Remote I/O Bus node CPX−FB6; Remote I/O Bus node CPX−FB11; Remote I/O Bus node CPX−FB14; Remote I/O Bus node CPX−FB23; Remote I/O Bus node CPX−FB...; Remote I/O CPX−FEC (Stand Alone and Remote Controller) CPX−FEC (Remote I/O)
[4DI input module] [8DI input module] [4DO output module] [8DI/8DO multi I/O module] [CPA10/14 pneumatic interface] [Type3 pneumatic interface] [MPA1G valve module] [MPA2G valve module] [MPA1S valve module] [MPA2S valve module] [2AI analogue input] [2AO analogue output] [FB13−RC PROFIBUS bus node] [FB6−RC Interbus bus node] [FB11−RC DeviceNet bus node] [FB14−RC CANopen bus node] [FB23−RC CC−Link bus node] [FB...−RC ... bus node] [CPI CP interface] [FB13−RIO PROFIBUS remote I/O] [FB6−RIO Interbus remote I/O] [FB11−RIO DeviceNet remote I/O] [FB14−RIO CANopen remote I/O] [FB23−RIO CC−Link remote I/O] [FB...−RIO ... remote I/O] [FEC controller] [FEC Modbus TCP]
*)
*)
*)
*) Further modules in preparation module code see technical specifications for the relevant module
List of the module codes
B−44
Festo P.BE−CPX−SYS−EN en 0503b
Page 187
B. Parameters and data of the CPX terminal
Module data: Revision code Function no.
16 + 16m + 13 m = module number (0...47)
Description
Specifies the output status of the module.
Bit
0...7
Values
Revision code
[Revision]
0...255 Note
See type plate
Revision code
Festo P.BE−CPX−SYS−EN en 0503b
B−45
Page 188
B. Parameters and data of the CPX terminal
Module data: Series number Function no.
Description
784 + m * 4 + 0 784 + m * 4 + 1 784 + m * 4 + 2 784 + m * 4 + 3
(byte 0) (byte 1) (byte 2) (byte 3)
m = module number (0...47)
Specifies the series number of the module. In byte 0 one nibble (4 bits) contains the year and the other nibble contains the month of the series (hexadecimal coding). Of bytes 1...3 each nibble contains a figure of the series number (BCD coded 1)).
1) BCD = binary coded decimal number (example see following table)
Function no.
Example 1)
Bit number 7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Nibble
Nibble
Nibble
Nibble
784 + m * 4 + 0
Year 2)
Month 3)
0
0
0
1
1
1
0
0
784 + m * 4 + 1
100,000
10,000
0
1
1
0
0
1
0
1
784 + m * 4 + 2
1 000
100
0
1
0
0
0
0
1
1
784 + m * 4 + 3
10
1
0
0
1
0
0
0
0
1
1) Example: Series number 1C654321 2) 0001 (1) = year 2001; 0010 (2) = year 2002 etc. 3) 0001 (1) = January; 0010 (2) = February ... 1011 (B) = November; 1100 (C) = December