Page 173

B. Parameters and data of the CPX terminal

Diagnostic memory data (10 bytes per entry, max. 40 entries)

Function no. 1)

Byte no.

Title

Description

Value

3488 + n

1

Days [day]

Number of days 2)

0...255 n = 10 * d + 0

2

Hours [h]

Number of hours 2)

0...23 n = 10 * d + 1

3

Minutes [m]

Number of minutes 2)

0...59 n = 10 * d + 2

4

Seconds [s]

Number of seconds 2)

0...59 n = 10 * d + 3

5

Milliseconds [ms]

Number of 10 msec 2) Additionally: bit 7 is set if it is the first entry after Power ON.

0...99 or 128...227 n = 10 * d + 4

6

Module code 3)

Module code of the module which registered the fault.

0...255 n = 10 * d + 5

7

Module position [Pos]

Module number of the module which registered the fault; 63 = fault not module−related

0...47, n = 10 * d + 6

Bit 7 0

6 0

0...255 n = 10 * d + 7

1

0

0 1

1 1

5...0: Description 0...63: No. of the 1st defective A channel 0...63: No. of the 1st defective Input channel 0...63: Module error 0...63: Reserved

8

Channel number 3)

63

9

Fault number [FN]

0...255:

Error number (possible error messages see section 5.1.1)

0...255 n = 10 * d + 8

10

Subsequent channels 3)

Number of subsequent channels with the same fault

0...63 n = 10 * d + 9

1) d (diagnostic event) [NB] = 0...39; most current diagnostic event = 0 2) Measured from the moment the power supply is switched on. 3) If the fault number = 0, the contents of these bytes are also 0. If the fault number lies between

128...199 (error class 3), the contents of these bytes are not relevant (servicing required).

Diagnostic memory data

Festo P.BE−CPX−SYS−EN en 0503b

B−31

Page 174

B. Parameters and data of the CPX terminal

B.2.6 System−Diagnostic data The following system diagnostic data is available: Function no.

System diagnostic data

1936

Status bits (error type and error source)

1937

Module number and diagnostic status

1938

Fault number

Overview Diagnostic data System diagnostic data: Status bits Function no.

1936

Description

The 8 status bits display common diagnostic messages (global error messages). Bits 0...3 display the source of the fault and bits 4...7 display the type of the fault.

Bit

Status bits Fault source: Bit 0: valve Bit 1: output Bit 2: input Bit 3: analogue/function module *) Fault type: Bit 4: undervoltage Bit 5: short circuit/overload Bit 6: wire fracture Bit 7: other faults

Values

1 = there is a fault; 0 = no fault

[System diagnostics] [Valve] [Output] [Input] [Analogue/function module] [Undervoltage] [Short circuit/overload] [Wire fracture] [Other error]

*) Function modules are also known as technology modules (e.g. CPX−CP interface).

Status bits

B−32

Festo P.BE−CPX−SYS−EN en 0503b

Page 175

B. Parameters and data of the CPX terminal

System diagnostic data: Module number and diagnostic status Function no.

1937

Description

Function no. 1937 specifies whether there are diagnostic data and contains, where applicable, the number of the first module on which a fault has occurred. With the aid of the module number of the faulty module you can ascertain the function numbers of the relevant diagnostic data.

Bit

Bit 0...5: Module number of the first faulty module Bit 6: Diagnostic status Bit 7: Reserved

Values

Bits 0...5: 0...47 (module number) Bit 6: 1 = there are diagnostic data 0 = there are no diagnostic data

Note

Function no. 1938 contains the relevant error number. Examples see and

[First faulty module]

Module number and diagnostic status System diagnostic data: Fault number Function no.

1938

Description

Contains the current fault number

Bit

Bit 0...7

Error number

Values

0...255

Fault number

Note

Possible error messages see section 5.1.1) Function no. 1937 specifies whether there are diagnostic data and contains, where applicable, the number of the first module on which the fault occurred.

[Fault number]

Fault number

Festo P.BE−CPX−SYS−EN en 0503b

B−33

Page 176

B. Parameters and data of the CPX terminal

B.2.7 Module diagnostic data The module diagnostic data are assigned to the function numbers 2008 to 2199. There are 4 diagnostic information items in 4 consecutive bytes for each module. The function numbers of the diagnostic data of the faulty module are therefore calculated as follows: Function no. = 2008 + (4 * module number) + information no. You can ascertain the module number of the first faulty ule with the aid of the system diagnostic data (function no. 1937). The following module diagnostic data is available: Function no. 1)

Module diagnostic data

2008 + m * 4 + 0

Number of the first faulty channel

2008 + m * 4 + 1

Module fault number

2008 + m * 4 + 2

Information 2 (reserved)

2008 + m * 4 + 3

Information 3 (reserved)

1) m = module number (0...47)

Overview Module diagnostic data Module diagnostic data for CP modules on the CPX−CP interface see the manual for the CPX−CP interface type

B−34

Festo P.BE−CPX−SYS−EN en 0503b

Page 177

B. Parameters and data of the CPX terminal

Module diagnostic data: Number of the first faulty channel Function no.

2008 + m * 4 + 0

Description

Specifies the number of the faulty channel (bits 0...5)

Bit

Bit 7 0 1 0 1

Values

Bits 0...5 Bit 6 Bit 7

Note

With the aid of the module number of the faulty module (see system diagnostic data, byte address 1937) you can ascertain the function numbers of the relevant diagnostic data.

6 0 0 1 1 m = module number (0...47)

5 ... 0 : Description 0 ... 63 : No. of the 1st defective A channel 0 ... 63 : No. of the 1st defective Input channel 0 ... 63 : Module error 0 ... 63 : Reserved 0...63 0...1 0...1

(channel number)

Number of the first faulty channel Module diagnostic data: Module fault number Function no.

2008 + m * 4 + 1 m = module number (0...47)

Description

Fault number

Bit

Bit 0...7

Error number

Values

0...255

(Fault number)

Note

Possible error messages see section 5.1.1

Module fault number Module diagnostic data: Information 2 (reserved) Function no.

2008 + m * 4 + 2

Description

Reserved m = module number (0...47)

Information 2 (reserved)

Festo P.BE−CPX−SYS−EN en 0503b

B−35

Page 178

B. Parameters and data of the CPX terminal

Module diagnostic data: Information 3 (reserved) Function no.

2008 + m * 4 + 3

Description

Reserved m = module number (0...47)

Information 3 (reserved)

B−36

Festo P.BE−CPX−SYS−EN en 0503b

Page 179

B. Parameters and data of the CPX terminal

B.2.8 System data System data give information on global system settings and system states. They will be lost after Power Off ent). The following system data is available: Function no.

System data

0

CPX operating mode

0

CPX equipment status

0

Handheld

0

Force mode

0

System start

1

Fail safe

1

System Idle mode 1)

2

Monitoring the CPX terminal

Number of input bytes (Rx size) 1)

Number of output bytes (Tx size) 1)

1) Only relevant for certain field bus protocols

Overview System data

Festo P.BE−CPX−SYS−EN en 0503b

B−37

Page 180

B. Parameters and data of the CPX terminal

System data: CPX operating mode Function no.

0

Description

Specifies the CPX operating mode which is currently active. In the operating mode Remote I/O" all functions are controlled via the protocol implemented in the field bus node. In the operating mode Remote Controller" the FEC takes complete control of the I/Os. 8 I/O bytes are intended for communication with the field bus node.

Bit

Bits 0...3

Values Bit 3 0 0 0 1

2 0 0 1 0

1 0 1 0 0

0 1 0 0 0

Note

CPX operating mode Description Remote I/O without FEC Remote I/O with FEC Remote Controller without field bus node Remote Controller with field bus node

[CPX mode] [Remote I/O] [Remote I/O with FEC] [Remote controller] [Remote control with FB]

The CPX operating mode is ascertained and entered during the start−up phase.

CPX operating mode System data: CPX equipment status Function no.

0

Description

Specifies whether the current equipment fitted to the CPX corresponds to the saved CPX equipment status.

Bit

Bit 4

Values Bit 4 0 1 Note

CPX equipment status Description equal not equal

[CPX structure] [equal] [unequal]

See also system parameter System start".

CPX equipment status

B−38

Festo P.BE−CPX−SYS−EN en 0503b

Page 181

B. Parameters and data of the CPX terminal

System data: Handheld Function no.

0

Description

Specifies whether a handheld is connected or not.

Bit

Bit 5

Values Bit 5 0 1 Note

Handheld Description Handheld not connected Handheld connected

[Handheld]

[connection OK]

Information for the higher−order controller If necessary for test purposes, a parameterisation carried out by handheld is to be cancelled by reloading the parameters, or forcing by higher−order PLC/IPC is to be blocked whilst a handheld is connected.

Handheld System data: Force mode Function no.

0

Description

Specifies whether Force is blocked or enabled.

Bit

Bit 6

Values Bit 6 0 1 Note

Force mode Description Blocked Enabled

[Force mode] [Disabled] [Enabled]

See also system parameter Force mode".

Force mode

Festo P.BE−CPX−SYS−EN en 0503b

B−39

Page 182

B. Parameters and data of the CPX terminal

System data: System start Function no.

0

Description

Specifies how the system start of the CPX terminal is to be carried out.

Bit

Bit 7

Values Bit 7 0 1

Note

System start Description System start with default parameterisation (factory setting) and current CPX equipment status System start with saved parameterisation and saved CPX equipment status

[System start] [Default parameters] [Saved parameters]

See also system parameter System start".

System start System data: Fail safe Function no.

1

Description

Specifies whether Fail safe is active or inactive.

Bit

Bits 0, 1

Values Bit 1 0 0 0 0 1 1 1

Fail safe Description Reset all outputs Hold last state (retain signal status) Assume fault mode

[Fail safe] [Reset outputs] [Hold last state] [Assume fault mode]

Fail safe

B−40

Festo P.BE−CPX−SYS−EN en 0503b