Page 163
B. Parameters and data of the CPX terminal
Module parameters: Monitoring wire fracture channel x (only for CPA pneumatics) Modules
For CPA pneumatic interface (see description for pneumatic interface)
Function no. Channel 0...7 Channel 8...15 Channel 16...23 Channel 24...31
4828 + m * 64 + 6 4828 + m * 64 + 7 4828 + m * 64 + 8 4828 + m * 64 + 9
Description m = module number (0...47)
Determines whether monitoring of the wire fracture for the relevant channel is active or inactive (CPA: channel 0...21). Monitoring wire fracture output channel ... 0 = Inactive 1 = Active
Note
[Monitor open circuit Out CH ...] [Inactive] [Active]
With monitoring wire fracture, a missing valve or a wire fracture (connection fault between the pneumatic interface and the valve coil) is recognised.
Monitoring wire fracture channel x (channel−specific) Module parameters: Fail safe channel x Modules
For modules with digital and analogue outputs (see manual for the module)
Function no.
Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).
Description
Fault mode channel x: Fault state channel x:
Note
Hold last state Fault state (presetting) Set output Reset output (presetting)
With the aid of the so−called Fail safe parameterisation, the signal status which the outputs are to assume in the event of field bus communication faults can be specified (see also section C.3).
Fail safe channel x (channel−specific)
Festo P.BE−CPX−SYS−EN en 0503b
B−21
Page 164
B. Parameters and data of the CPX terminal
Module parameters: Idle mode channel x Modules
For modules with digital and analogue outputs (see manual for the module)
Function no.
Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).
Description
Only relevant for certain field bus protocols Idle mode channel x Hold last state Idle state (presetting) Idle state channel x: Set output Reset output (presetting)
Note
With the aid of the so−called Idle mode parameterisation, the signal status which the outputs/valves are to assume during a change into the Idle status can be determined (see also section C.3.3).
Idle mode channel x (channel specific) Module parameters: Force channel x Modules
For modules with digital and analogue inputs and outputs (see manual for the module)
Function no.
Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).
Description
Force mode inputs channel x: Force state inputs channel x: Force mode outputs channel x: Force state outputs channel x:
Note
Blocked (presetting) Force state Set signal Reset signal (presetting) Blocked (presetting) Force state Set signal Reset signal (presetting)
The function Force permits the manipulation of signal states independent of actual operating conditions (see also section C.3.1).
Force channel x (channel−specific) For additional channel−specific module parameters as well as detailed information, see manual for the relevant module.
B−22
Festo P.BE−CPX−SYS−EN en 0503b
Page 165
B. Parameters and data of the CPX terminal
B.2.4 Diagnostic memory parameters The working method of the diagnostic memory can be adapted to individual requirements by means of the tic parameters. The diagnostic memory parameters retain their last setting after power off/on. They are saved securely against power outages. The parameter values marked with presetting spond to the factory condition. Further information on the working method of the diagnostic memory can be found in section C.4. The following parameters can be influenced: Function no.
Diagnostic memory parameters
3480
Entries remanent with Power ON
3480
Run/Stop filter 1
3484
Run/Stop filter 2
3484
Fault end filter
3484
Fault number filter
3484
Module/channel filter
3485
Module number MN
3486
Channel number CN
3487
Error number FN
Overview Diagnostic parameters
Festo P.BE−CPX−SYS−EN en 0503b
B−23
Page 166
B. Parameters and data of the CPX terminal
Diagnostic memory parameters: Entries remanent with Power on Function no.
3480
Description
Determines whether the contents of the diagnostic memory are to be retained after new power on or whether they are to be deleted. Bit 0
Entries remanent with new power ON
[Entries remanent at Power ON]
Values
1 = Inactive 0 = Active (presetting)
[Inactive] [Active]
Note
The diagnostic memory will be deleted if the mode is changed.
Entries remanent with Power on Diagnostic memory parameters: Run/Stop filter 1 Function no.
3480
Description
Diagnostic memory filter with which you can determine whether the first 40 faults or the last 40 faults are to be saved.
Bit
Bit 1
Values Bit 1 0 1 Note
Run/Stop filter 1:
[Run/Stop 1]
Save the first 40 entries (stop after 40 entries); Save the last 40 entries (overwrite old entries, presetting)
[Save the first 40 entries] [Save the last 40 entries]
The diagnostic memory will be deleted if the mode is changed.
Run/Stop filter 1
B−24
Festo P.BE−CPX−SYS−EN en 0503b
Page 167
B. Parameters and data of the CPX terminal
Diagnostic memory parameters: Run/Stop filter 2 Function no.
3484
Description
Diagnostic memory filter with which you can determine when the registering of faults is to be started or stopped.
Bit
Bits 0...2
Values
Run/Stop filter 2 MN = module number, CN = channel number, FN = fault number
[Run/Stop 2]
Description Run/Stop filter 2 inactive (presetting)
[Inactive]
Bit2 0
1 0
0 0
0
0
1
Register up to the defined FN
[Rec. up to def. FN]
0
1
0
Register up to the defined FN + MN
[Rec. up to def. FN + MN]
0
1
1
Register up to the defined FN + MN + CN
[Rec. up to def. FN + MN + CN]
1
0
0
Register as from the defined FN
[Rec. as of def. FN]
1
0
1
Register as from the defined FN + MN
[Rec. as of def. FN + MN]
1
1
0
Register as from the defined FN + MN + CN
[Rec. as of def. FN + MN + CN]
1
1
1
Reserved
Note
The numbers are determined by means of the diagnostic memory parameters Module, channel and fault numbers" (function nos. 3485...3487).
Run/Stop filter 2
Festo P.BE−CPX−SYS−EN en 0503b
B−25
Page 168
B. Parameters and data of the CPX terminal
Diagnostic memory parameters: Fault end filter Function no.
3484
Description
Diagnostic memory filter with which you can determine whether running faults are to be registered or not.
Bit
Bit 3
Values Bit 3 0 1
Note
Fault end filter Description Register running faults (end of fault) (filter inactive, presetting) Do not register running faults (end of fault) (filter active)
[Fault end filter] [Rec. outg. faults] [Do not rec. outg. faults]
By registering the outgoing fault, you can ascertain how long the fault has sted. Incoming and running faults each represent one entry. With running faults the fault number 0" is entered. Maximum 40 entries are saved together.
Fault end filter Diagnostic memory parameters: Fault number filter Function no.
3484
Description
With this diagnostic memory filter you can: suppress the registering of a desired fault message register exclusively a desired fault message
Bit
Bits 4, 5
Values
Fault number filter FN = fault number Description Fault number filter inactive (presetting) Register only defined FN Do not register defined FN Reserved
Bit 5 4 0 0 0 1 1 0 1 1 Note
[Fault numbers filter]
[Inactive] [Rec. only def. FN] [Do not rec. def. FN]
The fault number is determined by means of the diagnostic memory parameter Fault number" (function no. 3487).
Fault number filter
B−26
Festo P.BE−CPX−SYS−EN en 0503b
Page 169
B. Parameters and data of the CPX terminal
Diagnostic memory parameters: Module/channel filter Function no.
3484
Description
With this diagnostic memory filter, the registering of faults of other modules or channels can be suppressed in order that faults in a particular module or channel can be analysed.
Bit
Bits 6, 7
Values
Module/channel filter FN = fault number Description Module/channel filter inactive (presetting) Register only the FN of a module Register only the FN of a channel Reserved
Bit 7 6 0 0 0 1 1 0 1 1 Note
[Module/channel filter]
[Inactive] [Rec. FN of a mod.] [Rec, FN of a ch.]
The numbers are determined by means of the diagnostic memory parameters Module and channel numbers" (function nos. 3485...3486).
Module/channel filter Diagnostic memory parameters: Module number (MN) Function no.
3485
Description
Module number for the diagnostic memory filter
Bit
0...7
Values
Module number (MN) 0...47 Module number (0 = presetting)
Note
Is only effective if an appropriate diagnostic memory filter is active.
(1 byte) [Module number MN]
Module number (MN)
Festo P.BE−CPX−SYS−EN en 0503b
B−27
Page 170
B. Parameters and data of the CPX terminal
Diagnostic memory parameters: Channel number (CN) Function no.
3486
Description
Channel number for the diagnostic memory filter
Bit
0...7
Values
Channel number (CN) 0...63 Channel number (0 = presetting)
Note
Is only effective if an appropriate diagnostic memory filter is active.
(1 byte) [Channel number CN]
Channel number (CN) Diagnostic memory parameters: Fault number (FN) Function no.
3487
Description
Fault number for the diagnostic memory filter
Bit
0...7
Values
Fault number (FN) 0...255 Fault number (0 = presetting)
Note
Is only effective if an appropriate diagnostic memory filter is active.
(1 byte) [Fault number FN]
Fault number (FN)
B−28
Festo P.BE−CPX−SYS−EN en 0503b
Page 171
B. Parameters and data of the CPX terminal
B.2.5 Diagnostic memory data The following diagnostic memory data is available: Function no.
Diagnostic memory data
3482
Number of entries in the diagnostic memory
3483
Overflow
3483
Status
3488 + n
Diagnostic memory data (10 bytes per diagnostic entry, max. 40 entries)
Overview Diagnostic memory data Diagnostic memory data: Number of entries in the diagnostic memory Function no.
3482
Description
Specifies the number of entries in the diagnostic memory
Bit
0...7
Values
Number of entries in the diagnostic memory 0...40
Note
Can be used as a loop counter if the complete diagnostic memory is to be read out by PLC program.
(1 byte) [recorded faults ...]
Number of entries in the diagnostic memory
Festo P.BE−CPX−SYS−EN en 0503b
B−29
Page 172
B. Parameters and data of the CPX terminal
Diagnostic memory data: Overflow Function no.
3483
Description
Specifies whether the diagnostic memory has overflowed.
Bit
0
Values Bit 0 0 1 Note
Overflow Description No overflow Overflow
[no overflow] [overflow]
The overflow is displayed when the first 40 faults are registered as well as when the last 40 faults are registered. Overrun means that more than 40 faults have occurred.
Overflow Diagnostic memory data: Status Function no.
3483
Description
Specifies whether the error display is active or inactive.
Bit
1
Values Bit 1 0 1 Note
Description Registering active Registering inactive
[Recording active] [Recording inactive]
The fault registering can be stopped and started with the run/stop filters.
Status
Structure of thediagnostic memory The diagnostic memory contains up to 40 diagnostic entries. a diagnostic entry consists of 10 bytes. The first five bytes contain information on the fault time. The last five bytes tain information on the fault. The following table shows the structure of diagnostic entries.
B−30
Festo P.BE−CPX−SYS−EN en 0503b