The text of a manual · part 19 of 26
CPX terminal Electronics manual: System description, installing and commissioning CPX terminals: Parameters and data of the CPX terminal, pages 153 to 162
Pages 153 to 162 of 221, from CPX terminal Electronics manual: System description, installing and commissioning CPX terminals
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-CP-4-FB
Page 153
B. Parameters and data of the CPX terminal
System parameters: Fail safe (reaction to communication faults) Function no.
4402
Description
Determines the signal status which the outputs/valves are to assume in the event of field bus communication faults, e.g. in the event of: communication failure (bus interruption, PLC/IPC failure) communication stop. In the following case, the channel−orientated Fail safe settings (module ters Fault mode and Fault state) are reset automatically for safety reasons in order to avoid undesired signal states. When changing from Accept fault mode" to Reset all outputs" or to Hold last state".
Bit
Bits 0, 1
Values
Fail safe Description Reset all outputs (presetting)
[Fail safe]
0 1
Hold last state (retain signal status)
[Hold last state]
1 0
Assume fault mode
[Assume fault mode]
Bit 1 0 0 0
Note
[Reset outputs]
The Fault mode status is set with the channel−specific module parameters. Further information on this parameter can be found in section C.3.
Fail safe
Festo P.BE−CPX−SYS−EN en 0503b
B−11
Page 154
B. Parameters and data of the CPX terminal
System parameters: Force mode Function no.
4402
Description
Determines for the complete CPX terminal whether the Force function is blocked or enabled. By changing these parameters, in the following cases the channel−orientated Force settings (module parameters Force mode and Force state) are reset matically for safety reasons in order to avoid undesired signal states. Change over handheld: When changing from enabled" to blocked". Change over field bus: When changing from blocked" to enabled".
Bit
Bits 2, 3
Values Bit 3 2 0 0 0 1 Note
B−12
Force mode Description Blocked (presetting)
[Force mode]
Enabled
[Enabled]
[Disabled]
Force signals have precedence over Fail safe signals.
Force mode
Festo P.BE−CPX−SYS−EN en 0503b
Page 155
B. Parameters and data of the CPX terminal
System parameters: System Idle mode Function no.
4402
Description
Defines the signal status which outputs/valves are to assume when the CPX terminal changes into the Idle status. In the following case, the channel−orientated Idle mode settings (module meters Idle mode and Idle state) are reset automatically for safety reasons in order to avoid undesired signal states: When changing from Accept Idle mode" to Reset all outputs" or to Hold last state".
Bit
Bits 4, 5
Values
System Idle mode Description Reset all outputs (presetting)
[Idle mode]
0 1
Hold last state (retain signal status)
[Hold last state]
1 0
Assume Idle mode
[Assume idle mode]
Bit 5 4 0 0
Note
[Reset outputs]
Only relevant for certain field bus protocols Explanations on this can be found in the manual for the relevant CPX field bus node.
Idle mode
Festo P.BE−CPX−SYS−EN en 0503b
B−13
Page 156
B. Parameters and data of the CPX terminal
System parameters: System start *) Function no.
4402
Description
With this parameter you can determine the start−up reaction of the CPX terminal and save all current parameter settings and the current CPX equipment status.
Bit
Bit 6 System start *) Description
[System start]
0
System start with default parametrizing (factory ting) and current CPX equipment status; external parametrizing is possible (presetting)
[Default parameters]
1
System start with saved parametrizing and saved CPX equipment status; parameters and CPX equipment status are saved remanently; external parametrizing is blocked; the M−LED on the field bus node lights up.
[Saved parameters]
Values Bit 6
Note
If bit 6 is set to 1, the current parameter settings will be frozen" tected) and the current CPX equipment status will be saved, except for bit 6 itself and the module parameter Force channel X". Recommendation: Select System start with default parametrizing and current CPX equipment status". The desired parametrizing can then be created in the start−up phase or after field bus interruptions e.g. by the plug−in module or the scanner/bus master (depending on the field bus used). If System start with default parametrizing and current CPX equipment status" is active, the factory settings for all module and system parameters will become valid after Power On.
*) This parameter does not exist with the CPX−FEC in the operating modes Stand Alone and Remote
Controller (control function active).
B−14
System start
Festo P.BE−CPX−SYS−EN en 0503b
Page 157
B. Parameters and data of the CPX terminal
B.2.3 Module parameters Module parameters refer to module−specific or cific functions. 64 bytes are available for parameters in each module. Detailed information on the module parameters, which are supported by the module used, can be found in the manual for the relevant module. There you will find tion on possible parameters and their settings. Function number 1)
Module parameters
4828 + m * 64 + 0
Monitoring the CPX module
4828 + m * 64 + 1
Reaction after short circuit/overload
4828 + m * 64 + 1
Input debouncing time
4828 + m * 64 + 1
Signal extension time
4828 + m * 64 + 3
Data format analogue value inputs
4828 + m * 64 + 3
Data format analogue value outputs
1) m = module number (counting on the modules from left to right, beginning with 0)
Overview of module parameters for module−specific functions
Function no.
Example of some channel−specific module parameters
4828 + m * 64 + 6
Signal extension channel x
− 1)
Monitoring wire fracture channel X
− 2)
Fail safe channel x
− 2)
Idle mode channel x
− 2)
Force channel x
1) Function number see manual for CPX modules 2) Access is protocol−specific (see manual for field bus node)
Overview Example of some channel−specific module parameters
Festo P.BE−CPX−SYS−EN en 0503b
B−15
Page 158
B. Parameters and data of the CPX terminal
Module parameters: Monitoring the CPX module Modules
Depending on the monitoring function for modules with digital and analogue inputs and outputs (see description on the respective module)
Function no.
4828 + m * 64 + 0
Description
For each module the monitoring of the possible faults can be activated or vated (suppressed) independently of each other. Active monitoring causes the following: The fault is: sent to the CPX field bus node displayed by the module common error LED.
m = module number (0...47)
Monitoring Description Short circuit/overload in sensor supply
[Monitor]
Bit 0 1
Short circuit/overload at the outputs
[Monitor SCO]
2
Undervoltage at outputs/valves (VOUT/VAL)
[Monitor VOUT/VAL]
3
Short circuit at the valve
[Monitor SCV]
4
Reserved
5
Reserved
6
Reserved
7
Monitoring parameterisation faults
[Monitor parameters]
Values
1 = Active (presetting) 0 = Inactive
[Active] [Inactive]
Note
Monitoring can also be set for the complete CPX terminal (see system parameter Monitoring").
[Monitor SCS]
Monitoring the CPX module For parametrizing the Monitoring CP modules" on the CPX−CP interface see the manual for the CPX−CP interface typeP.
B−16
Festo P.BE−CPX−SYS−EN en 0503b
Page 159
B. Parameters and data of the CPX terminal
Module parameters: Reaction after short circuit/overload Modules
Depending on the function for modules with digital and analogue inputs and outputs (see description on the respective module)
Function no.
4828 + m * 64 + 1
Description
Determines after a short circuit in the sensor supply or the outputs whether the power is to remain switched off or whether it is to be switched on again tically.
m = module number (0...47)
Reaction after short circuit/overload Description Short circuit/overload in sensor supply Short circuit/overload at the outputs Short circuit/overload at the analogue signal
[Behaviour after]
Values
0 = Voltage/current remains switched off 1 = Switch voltage/current on again
[Leave switched off ] [Resume]
Note
With the setting voltage/current remains switched off", you must switch the power off/on or set/reset the relevant signals in order to apply power again. Ascertain the setting which is necessary for reliable operation of your machine or system. Further information can be found in the manual for the CPX I/O modules.
Bit 0 1 3
[Behaviour after SCS] [Behaviour after SCO] [Behaviour after SCA]
Reaction after short circuit/overload
Festo P.BE−CPX−SYS−EN en 0503b
B−17
Page 160
B. Parameters and data of the CPX terminal
Module parameters: Input debouncing time Modules
For modules with digital inputs (see manual for the module)
Function no.
4828 + m * 64 + 1
Description
Determines when a change of edge of the sensor signal on this module is to be accepted as a logical input signal.
Bit
Bits 4, 5
Typical values Bit 5 4 0 0 0 1 1 0 1 1
Input debouncing time Description 0.1 ms 3 ms (typical presetting) 10 ms 20 ms
Note
Input debouncing times are specified in order to eliminate interfering changes of signal edge during switching procedures (bouncing of the input signal). Further information on this parameter can be found in section C.1.
m = module number (0...47)
[Debounce time]
Input debouncing time
B−18
Festo P.BE−CPX−SYS−EN en 0503b
Page 161
B. Parameters and data of the CPX terminal
Module parameters: Signal extension time Modules
For modules with digital inputs (see manual for the module)
Function no.
4828 + m * 64 + 1
Description
Determines the signal extension time for the relevant module. Signal states cepted as logical input signals usually remain valid at least until the specified signal extension time (minimum signal duration) has expired. Changes of edge within the extension time are ignored.
Bit
Bits 6, 7
Typical values Bit 7 6 0 0 0 1 1 0 1 1
Signal extension time Description 0.5 ms 15 ms (typical presetting) 50 ms 100 ms
Note
There is a danger here that short signals are not recognized" due to long cycle times of the higher−order controller. In order that such signals are taken into consideration in the control sequence, a signal extension time can be specified (see section C.2). The signal extension time can be activated by nel (see channel−specific module parameters).
m = module number (0...47)
[Signal extension]
Signal extension time Module parameters: Data format for analogue value inputs Modules
For modules with analogue inputs (see manual for the module)
Function no.
4828 + m * 64 + 3
Description
Determines the data format with which the relevant analogue values are processed internally.
Bit
Bits 0, 1
Values
Data format analogue value inputs See manual for the relevant analogue module
Note
The choice of data format depends on the field bus or field bus master used and simplifies evaluation of the analogue values.
m = module number (0...47)
[Input format]
Data format analogue value inputs
Festo P.BE−CPX−SYS−EN en 0503b
B−19
Page 162
B. Parameters and data of the CPX terminal
Module parameters: Data format for analogue value outputs Modules
For modules with analogue outputs (see manual for the module)
Function no.
4828 + m * 64 + 3
Description
Determines the data format with which the relevant analogue values are processed internally.
Bit
Bits 4, 5
Values
Data format analogue value outputs See manual for the relevant analogue module
Note
The choice of data format depends on the field bus or field bus master used and simplifies evaluation of the analogue values.
m = module number (0...47)
[Output format]
Data format analogue value outputs
Example of some channel−specific module parameters Module parameters: Signal extension channel x Modules
For modules with digital inputs (see manual for the module)
Function no.
4828 + m * 64 + 6
Description
Determines whether the signal extension for the relevant input channel is enabled or blocked.
Bit
Bit 0...7 (channel 0...7)
Values
Signal extension input channel ... 0 = Blocked 1 = Enabled
Note
The signal extension time can be specified separately for each module (see function no. 4828 + n; n = m * 64 + 1).
m = module number (0...47)
[Signal extension Inp Ch ...] [Disabled] [Enabled]
Signal extension channel x (channel−specific)
B−20
Festo P.BE−CPX−SYS−EN en 0503b