The text of a manual · part 12 of 18
CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Technical appendix
Pages 95 to 98 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Festo CPX-FB-32
Page 95
Technical appendix
Appendix A
Technical appendix
Festo P.BE-CPX-FB32-EN en 1111a
A-1
Page 96
A. Technical appendix
Table of contents
A.
Technical appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
A.1 A.2
Technical data fieldbus node type CPX-FB32 . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-3 A-4
A-2
Festo P.BE-CPX-FB32-EN en 1111a
Page 97
A. Technical appendix
A.1
Technical data fieldbus node type CPX-FB32
General information General technical data
See CPX system description: – Description P.BE-CPX-SYS-...
Protection class according to EN 60 529, CPX-FB32 completely mounted, plug connector, like accessories, plugged in or equipped with protective cap
IP65 / IP67
Protection against electric shock
Through use of PELV circuits (Protection against direct and indirect contact in accordance with EN 60204-1)
Current consumption fieldbus node CPX-FB32 Internal current consumption at 24 V (internal electronics): – from operating voltage supply for electronics/ sensors (VEL/SEN) Galvanic isolation – Ethernet/IP interface type 65 mA electrically isolated (optocoupler)
Module code (CPX-specific)
Remote I/O: Remote Controller:
Module identification (Handheld)
Remote I/O: – “CPX-FB32 Remote/IO” Remote Controller: – “CPX-FB32 Remote Controller”
Festo P.BE-CPX-FB32-EN en 1111a
212 160
A-3
Page 98
A. Technical appendix
Fieldbus Protocols
– IEEE 802.3 (Ethernet) according to RFC 894 – Internet Protocol (RFC 791) – User Datagram Protocol (UDP) (RFC 768) – Transmission Control Protocol (TCP) (RFC 793) – Address Resolution Protocol (ARP) (RFC 826) – Internet Control Messaging Protocol (ICMP) (RFC 792) – Internet Group Management Protocol (IGMP) (RFC 1112 & 2236) – HTTP – FTP – DHCP
Baud rate
10/100 MBd, full/half duplex
Cable type and length see Ethernet specification according to IEEE 802.3
A.2
Accessories
Accessories
Type
Part No.
M12 plug for connection to the fieldbus
NECU-M-S-D12G4-C2-ET
543109
Tab. A/1: Accessories
A-4
Festo P.BE-CPX-FB32-EN en 1111a