CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Diagnostics, pages 85 to 94

Pages 85 to 94 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-FB-32

Page 85

3. Diagnostics

NS – network status LED

Sequence

Status

ON

The CPX terminal is not online – Logic supply for bus interface not applied

OFF

Is off

ON OFF

Flashes green

ON OFF

Lights up green ON OFF

Meaning / error handling

• Check logic supply

CPX terminal is online and has received an IP address, but the CPX terminal does not have a configured connection.

• Check configuration; it is possible that the CPX terminal is not assigned to a master/scanner or • Check the status of the master, it is possible that the master is not in the RUN mode.

The CPX terminal is online and has a connection to the fieldbus

None (normal operating status)

One or more “I/O connections” are in the time-out status

Check the physical connection to the master/scanner (EtherNet cable).

Flashes red ON OFF

Communication has failed. – Non-permitted IP address set and already used in the network

• Correct IP address

Lights up red ON

CPX terminal is in self-test

None

OFF

Flashes red/green

*) Test algorithm which ensures that no station numbers are assigned double in the network.

The test is usually carried out automatically when the network connection is set up.

Festo P.BE-CPX-FB32-EN en 1111a

3-11

Page 86

3. Diagnostics

I/O (I/O status) LED

Sequence

Status

Meaning / error handling

ON

– Logic supply for bus interface not applied – Outputs are inactive

• Check logic supply

One or more outputs are controlled via EtherNet/IP. No output is faulty.

None

One or more outputs are in the idle state and none of the outputs is active or faulty.

I/O control via EtherNet/IP, but device is allocated by the master and the master is in idle mode, e.g. programming mode.

One or more outputs are defective, possibly in a faulty status.

Check the inputs/outputs and the communication connection to the master.

One or more outputs are forcibly switched off (perhaps an error which cannot be corrected); one or more inputs have an error which cannot be corrected

Check the other LEDs, if necessary request servicing

CPX terminal is in self-test

None

OFF

Is off ON

Lights up

OFF

ON OFF

Flashes green ON OFF

Flashes red ON OFF

Lights up red

ON OFF

Flashes red/green

3-12

Festo P.BE-CPX-FB32-EN en 1111a

Page 87

3. Diagnostics

TP (Link/Traffic) LED (green)

Sequence

Status

Error handling

ON

No Ethernet connection or Ethernet cable not connected

If necessary check Ethernet connection

Network connection OK (Link)

–

Data traffic (traffic) Illumination intensity is dependent on the traffic.

–

OFF

LED is off ON OFF

LED lights up ON OFF

LED flashes

Festo P.BE-CPX-FB32-EN en 1111a

3-13

Page 88

3. Diagnostics

3.3

Diagnostics via status bits Status bits are internal inputs (1 input byte), which serve to display common diagnostic messages (global error messages).

Note If status bits are to be transmitted via a “polled” or “change of state” connection, you have to set the DIL switch at the fieldbus node correspondingly (see Tab. 1/2). If all status bits supply a 0-signal, no fault will be registered. The following table shows the diagnostic information when there is a 1-signal: Bit

Diagnostic information with 1-signal

Description

0

Error in valve

Module type in which an error has occurred

1

Error at output

2

Error at input

3

Error at analogue module/technology module

4

Undervoltage

5

Short circuit/overload

6

Wire break

7

Other error

Type of error

Tab. 3/3: Overview of status bits If various errors occur simultaneously on different types of modules, these errors cannot be assigned via the status bits. Errors may be uniquely determined through the I/O diagnostics interface or diagnostics via EtherNet/IP access.

3-14

Festo P.BE-CPX-FB32-EN en 1111a

Page 89

3. Diagnostics

Further instructions on the function and content of the status bits can be found in the CPX system description.

3.4

Diagnosis via I/O diagnostic interface For the fieldbus node CPX-FB32,access to the EtherNet/IP Objects through Explicit Message programming is in principle more appropriate than the use of the I/O diagnostic interface (see Appendix B.1). Detailed diagnostic information can be accessed via the I/O diagnostic interface. You can ascertain exactly, for example, on which module and on which channel an error has occurred. 16 input bits and 16 output bits, through which all diagnostic data can be read, are available for accessing the system diagnosis.

Note In order to use the I/O diagnostic interface, it must be activated with the DIL switch on the fieldbus node (see Tab. 1/2). If the I/O diagnostic interface is active, it will occupy the first 16 inputs and outputs in the address range (see Tab. 2/7). Information on the I/O diagnostic interface (diagnostic information, function numbers) can be found in the CPX system description.

Festo P.BE-CPX-FB32-EN en 1111a

3-15

Page 90

3. Diagnostics

Overview of diagnostic data Diagnostic data

Contents / description

Global diagnostic data

– General overview of errors

Module diagnostic data

– Detail diagnosis per module

Status of diagnostic memory

– Number of entries in the diagnostic memory – Operating mode

Diagnostic memory data

– Long-term memory – Detail diagnosis + relative time stamp per error event

Tab. 3/4: Diagnostic data

3.5

Diagnosis via EtherNet/IP The CPX system enables diagnosis via EtherNet/IP. The following diagnostic options are supported here:

3-16

–

Explicit Messaging via Ethernet/IP Master

–

Diagnosis via user program The I/O diagnostic interface can also be read out here.

Festo P.BE-CPX-FB32-EN en 1111a

Page 91

3. Diagnostics

Overview of diagnostic data with Explicit Messaging The following EtherNet/IP Objects offer detailed diagnostic information: Object classes

Name

Diagnostic data

101d

General Module Parameter Object

– Faulty channel type – Number of the faulty channel – Module error number

133d

Status and Diagnostic Object

– Number of the module in which an error has occurred – Diagnostic status (specifies whether there are diagnostic data). – System error number

134d

Diagnostic Trace Object

– Long-term memory (max. 40 entries) – Detail diagnosis + relative time stamp per error event

135d

Diagnostic Trace Status Object

– Number of entries in the diagnostic memory – Trace status

Tab. 3/5: Diagnostic data with Explicit Messaging

Festo P.BE-CPX-FB32-EN en 1111a

3-17

Page 92

3. Diagnostics

Possible sequence of diagnosis Possible sequence of diagnosis

Diagnostic data

Object which supplies the diagnostic data

1. Check to see if there are diagnostic data available

Diagnostic status

Status and Diagnostic Object (133d)

2. Ascertain the number of the module in which an error has occurred

Number of the module

Status and Diagnostic Object (133d)

3. Ascertain relevant module diagnostic data

Error number, channel type and number of the faulty channel

General Parameter Object Module (101d)

Tab. 3/6: Possible sequence of diagnosis

3-18

Festo P.BE-CPX-FB32-EN en 1111a

Page 93

3. Diagnostics

3.6

Error handling With the following malfunctions, the reaction of the CPX terminal depends on the configured reaction of the master module and on the parameterised Fail Safe setting: –

Telegram failure

–

The master has stopped

–

Interruption in the bus cable

Depending on the parameterisation, the outputs (valves and electric outputs) will be switched off (factory setting), switched on or retain their status (see CPX system manual).

Warning • Ensure that valves and outputs are put into a safe state if the stated malfunctions occur. An incorrect status of the valves and outputs can lead to dangerous situations!

Note Please observe the following if the outputs are reset in the event of a PLC stop or fieldbus interruption or malfunction: – Single-solenoid valves move to the basic position. – Double-solenoid valves remain in the current position. – Mid-position valves go into mid-position (pressurized, exhausted or closed, depending on valve type).

Festo P.BE-CPX-FB32-EN en 1111a

3-19

Page 94

3. Diagnostics

3-20

Festo P.BE-CPX-FB32-EN en 1111a