Manual · Festo
CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP
Manual146 pagesPDF 2.3 MB
Manual for the Festo CPX-FB32 EtherNet/IP fieldbus node of the CPX terminal: installation, commissioning, parameters and diagnostics.
Covers · 1 model
The models it covers
Summary
What is in it
Festo's electronics manual for the CPX-FB32 fieldbus node, which connects a CPX terminal to EtherNet/IP. It covers setting the DIL switches, connecting the Ethernet fieldbus, setting the IP address and using the built-in web server, power supply pin assignment, addressing, bus configuration (including RSLogix5000), parameterisation methods, Idle and Fault mode settings, diagnostics via LEDs, status bits and EtherNet/IP, technical data and the node's EtherNet/IP objects.
Its parts
- Installation
- Commissioning
- Diagnostics
From the manual
Key facts from this manual
Each line names its page in the PDF.
Festo manual P.BE-CPX-FB32-EN (edition en 1111a) for the CPX-FB32 fieldbus node, which makes a CPX terminal a station on EtherNet/IP. It shows how to mount the node, set its DIL switches and IP address, wire the Ethernet and power connections, and read its LEDs when diagnosing faults.
- Product type
- Fieldbus node for the CPX terminal, used as a station on EtherNet/IP p. 8
- Fieldbus connector
- 4-pin M12 socket, D-coded, compatible with SPEEDCON plugs p. 28
- Fieldbus plug
- NECU-M-S-D12G4-C2-ET, part no. 543109 p. 98
- Baud rate
- 10/100 MBd, full/half duplex p. 98
- Operating modes
- Remote I/O (factory setting) or Remote Controller, where an integrated FEC controls the I/Os; set with DIL switch 1 p. 23
- IP addressing
- Factory setting BOOTP/DHCP; fixed addressing with DIL switch 3 sets the host ID of 192.168.1.xxx p. 29, 30
- Power supply
- 24 V through interlinking blocks CPX-GE-EV-S..., CPX-GE-EV-Z... or CPX-GE-EV-V...; PELV circuits only p. 33, 34
- Current draw
- Typically 65 mA at 24 V for the internal electronics p. 97
- Ethernet cable
- Screened, flexible category 5 round cable, max. outer diameter 5.4 mm, wire 0.89 ... 1.0 mm AWG24-26 p. 27
- Controller I/O size
- Remote Controller mode: 8 byte I/8 byte O (default) or 16 byte I/16 byte O with CPX-FEC or CPX-CEC p. 25
- Diagnostic mode
- Remote I/O mode: DIL switch 2 turns on the I/O diagnostic interface (16 extra I/O bits) or status bits p. 24
- LEDs
- PS, PL, SF, M (CPX-specific); MS, NS, IO, TP (EtherNet/IP-specific) p. 79
- Service interface
- V24 service interface for the Handheld p. 18
- Webserver
- Built in, with read access to the main parameters and diagnostic functions p. 32
What this manual walks you through
- Removing and mounting the node in the interlinking block p. 19, 20
- Removing and refitting the DIL switch cover p. 21
- Setting the operating mode with DIL switch 1 p. 23
- Setting the diagnostic mode or I/O data size with DIL switch 2 p. 24, 25
- Setting the IP address p. 29, 30, 31
- Wiring the Ethernet fieldbus to the M12 socket p. 27, 28
- Changing the baud rate and duplex mode p. 32
- Pin assignment of the system, additional and valve power supplies p. 34
- Reading the node's LEDs to diagnose faults p. 79, 80
- How outputs react to a bus fault or stopped master p. 93
Good to know
- Switch off the compressed air, the electronics/sensor supply and the load supply before installation or maintenance. p. 17
- Unused connections must be sealed with protective caps or blanking plugs to reach IP65/IP67. p. 17
- After a change to the network settings the M LED flashes yellow and the node must be restarted with power off/on. p. 29
- With saved parameterisation, a replacement terminal is not parameterised automatically by the PLC; check the settings first. p. 83
- Combining stored network settings with the DIL switch host ID is available only from Revision 18. p. 31
Questions this manual answers
What IP address does the CPX-FB32 get with DIL switch addressing?
DIL switch 3 sets the host ID of 192.168.1.xxx, with network mask 255.255.255.0 and gateway 0.0.0.0. With all switches off (factory setting) it uses BOOTP/DHCP. p. 29, 30
What is the pinout of the CPX-FB32 Ethernet M12 socket?
Pin 1 TX+, pin 2 RX+, pin 3 TX-, pin 4 RX-, with the screen on the housing. p. 28
Which plug connects the CPX-FB32 to the Ethernet fieldbus?
The Festo M12 plug NECU-M-S-D12G4-C2-ET, part no. 543109. p. 98
What does a flashing SF LED mean on the CPX-FB32?
The red SF LED flashes once, twice or three times before a pause for error class 1 (simple error), 2 (error) or 3 (serious error). p. 82
What happens to the outputs if the EtherNet/IP connection fails?
Depending on the parameterisation, outputs and valves are switched off (factory setting), switched on or keep their state. p. 93
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 18 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 71-7
- Pages 8 to 108-10
- Important user instructions11-14
- Installation, pages 15 to 2415-24
- Installation, pages 25 to 3425-34
- Commissioning, pages 35 to 4435-44
- Commissioning, pages 45 to 5445-54
- Commissioning, pages 55 to 6455-64
- Commissioning, pages 65 to 7465-74
- Diagnostics, pages 75 to 8475-84
- Diagnostics, pages 85 to 9485-94
- Technical appendix95-98
- Ethernet/IP Objects of the CPX-FB32, pages 99 to 10799-107
- Ethernet/IP Objects of the CPX-FB32, pages 108 to 116108-116
- Ethernet/IP Objects of the CPX-FB32, pages 117 to 125117-125
- Ethernet/IP Objects of the CPX-FB32, pages 126 to 134126-134
- Ethernet/IP Objects of the CPX-FB32, pages 135 to 140135-140
- Index141-146