The text of a manual · part 16 of 18
CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Ethernet/IP Objects of the CPX-FB32, pages 126 to 134
Pages 126 to 134 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Festo CPX-FB-32
Page 126
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Force mode Objects Force mode: Instances:
109, 111, 117, 119, 125, 127 (see Tab. B/8 ... Tab. B/10) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Value for Force mode: Channel 0: 0 = Force blocked 1 = Force enabled
BOOL
2
Get/Set
Channel 1: 0 = Force blocked 1 = Force enabled
BOOL
...
...
...
...
64
Get/Set
Channel 63: 0 = Force blocked 1 = Force enabled
BOOL
100
Get
Number of channels
BYTE
101
Get
All channels: values for Force mode
ARRAY
Tab. B/11: Basic composition of the Objects for Force mode
B-28
Festo P.BE-CPX-FB32-EN en 1111a
Page 127
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Force state for digital I/O modules Objects Force state: Instances:
108, 110 (see Tab. B/8) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Value for Force state: Channel 0: 0 = Reset signal 1 = Set signal
BOOL
2
Get/Set
Channel 1: 0 = Reset signal 1 = Set signal
BOOL
...
...
...
...
64
Get/Set
Channel 63: 0 = Reset signal 1 = Set signal
BOOL
100
Get
Number of channels
BYTE
101
Get
All channels: values for Force state
ARRAY
Tab. B/12: Composition of the Objects for Force state for digital I/O modules
Festo P.BE-CPX-FB32-EN en 1111a
B-29
Page 128
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Force state for analogue I/O modules Objects Force state: Instances:
116, 118 (see Tab. B/9) 1 ... 32, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Channel 0: Value for Forcing
WORD
2
Get/Set
Channel 1: Value for Forcing
WORD
...
...
...
...
32
Get/Set
Channel 31: Value for Forcing
WORD
Tab. B/13: Composition of the Objects for Force state for analogue I/O modules
B-30
Festo P.BE-CPX-FB32-EN en 1111a
Page 129
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Force state for technology modules Objects Force state: Instances:
124, 126 (see Tab. B/10) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Channel 0: Value for Forcing
BYTE
2
Get/Set
Channel 1: Value for Forcing
BYTE
...
...
...
...
64
Get/Set
Channel 63: Value for Forcing
BYTE
65
Get/Set
Channel 0: Value for Forcing
WORD
...
...
...
...
96
Get/Set
Channel 31: Value for Forcing
WORD
100
Get
Number of channels
BYTE
101
Get
Data type: – D1h: BYTE – D2h: WORD
BYTE
102
Get/Set
All channels: values for Force state
ARRAY
Tab. B/14: Composition of the Objects for Force state technology modules
Festo P.BE-CPX-FB32-EN en 1111a
B-31
Page 130
B. Ethernet/IP Objects of the CPX-FB32
B.4.8 Fail Safe and Idle parameters The first word receives the lowest instance number of the relevant Object. The second word receives the second lowest instance number, etc. Object
Description
112
Fault state digital outputs
113
Fault mode digital outputs
114
Idle state digital outputs
115
Idle mode digital outputs
Tab. B/15: Objects for Fail Safe and Idle parameters of digital output modules Object
Description
120
Fault state analogue outputs
121
Fault mode analogue outputs
122
Idle state analogue outputs
123
Idle mode analogue outputs
Tab. B/16: Objects for Fail Safe and Idle parameters of analogue output modules
B-32
Festo P.BE-CPX-FB32-EN en 1111a
Page 131
B. Ethernet/IP Objects of the CPX-FB32
Object
Description
128
Fault state outputs technology module
129
Fault mode outputs technology module
130
Idle state outputs technology module
131
Idle mode outputs technology module
Tab. B/17: Objects for the Fail Safe and Idle parameters for technology modules
Composition of the Objects for Fault/Idle mode Objects Fault state: Objects Fault mode: Instances:
112, 120, 128 113, 121, 119 (see Tab. B/15 ... Tab. B/17) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Values for Fault/Idle mode: Channel 0: 0 = Hold last state 1 = Fault/Idle state
BOOL
2
Get/Set
Channel 1: 0 = Hold last state 1 = Fault/Idle state
BOOL
...
...
...
...
64
Get/Set
Channel 64: 0 = Hold last state 1 = Fault/Idle state
BOOL
100
Get
Number of channels
BYTE
101
Get
All channels: values for Fault/Idle mode
ARRAY
Tab. B/18: Composition of the Objects for Fault/Idle mode Festo P.BE-CPX-FB32-EN en 1111a
B-33
Page 132
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Fault/Idle state for digital output modules Object Fault state: Object Idle state: Instances:
112 114 (see Tab. B/15) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Channel 0: 0 = Hold last state 1 = Fault/Idle state
BOOL
2
Get/Set
Channel 1: 0 = Hold last state 1 = Fault/Idle state
BOOL
...
...
...
...
64
Get/Set
Channel 64: 0 = Hold last state 1 = Fault/Idle state
BOOL
100
Get
Number of channels
BYTE
101
Get
All channels: values for Fault/Idle state
ARRAY
Tab. B/19: Composition of the Objects for Fault/Idle state for digital output modules
B-34
Festo P.BE-CPX-FB32-EN en 1111a
Page 133
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Fault/Idle state for analogue output modules Object Fault state: Object Idle state: Instances:
120 122 (see Tab. B/16) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Channel 0: Value for Fault/Idle state
WORD
2
Get/Set
Channel 1: Value for Fault/Idle state
WORD
...
...
...
...
32
Get/Set
Channel 31: Value for Fault/Idle state
WORD
Tab. B/20: Composition of the Objects for Fault/Idle state for analogue output modules and technology modules
Festo P.BE-CPX-FB32-EN en 1111a
B-35
Page 134
B. Ethernet/IP Objects of the CPX-FB32
Composition of the Objects for Fault/Idle state for technology modules Object Fault state: Object Idle state: Instances:
128 130 (see Tab. B/17) 1 ... 64, 100, 101
Attr. No.
Access
Description
Type
1
Get/Set
Channel 0: Value for Fault/Idle state
BYTE
2
Get/Set
Channel 1: Value for Fault/Idle state
BYTE
...
...
...
...
64
Get/Set
Channel 63: Value for Fault/Idle state
BYTE
65
Get/Set
Channel 64: Value for Fault/Idle state
WORD
...
...
...
...
96
Get/Set
Channel 31: Value for Fault/Idle state
WORD
100
Get
Number of channels
BYTE
101
Get
Data type: – D1h: BYTE – D2h: WORD
BYTE
102
Get/Set
All channels: values for Fault/Idle state
ARRAY
Tab. B/21: Composition of the Objects for Fault/Idle state for analogue output modules and technology modules
B-36
Festo P.BE-CPX-FB32-EN en 1111a