B. Ethernet/IP Objects of the CPX-FB32
B.4.3 Status and Diagnostic Object Object class: Instances:
133 1
The status bits and the I/O diagnostic interface are mapped here. Attr. No.
Access
Description
Type
Function no.
1
Get
Status bits (8 bit) Source of error: Bit 0: Valve Bit 1: Output Bit 2: Input Bit 3: Analogue/ technology module Error type: Bit 4: Undervoltage Bit 5: Short circuit/overload Bit 6: Wire break Bit 7: Other error
BYTE
1936
2
Get
Number of the first module in which a fault has occurred
BYTE
1937
3
Get
Diagnostic status
BYTE
4
Get
Error number
BYTE
5
Get/Set
Address I/O diagnostic interface 16 output bits (task data) of the I/O diagnostic interface
WORD
6
Get
Data I/O diagnostic interface 16 input bits (reply data) of the I/O diagnostic interface
WORD
Festo P.BE-CPX-FB32-EN en 1111a
1938
B-19
Page 118
B. Ethernet/IP Objects of the CPX-FB32
B.4.4 Diagnostic Trace Object Object class: Instances:
134 1 ... 40
An instance is created for each diagnostic entry. Attr. No.
Access
1
Get
2
Get
3 4
Designation
Description
Type
Function no. 3488 + n 1)
Marking the first entry after Power on Supplies 1 if it is the first entry after Power on.
BYTE n = 10 * d + 4 (bit 7)
Days
Number of days 2)
BYTE n = 10 * d + 0
Get
Hours
Number of hours 2)
BYTE n = 10 * d + 1
Get
Minutes
Number of minutes 2)
BYTE n = 10 * d + 2
BYTE n = 10 * d + 3
5
Get
Seconds
Number of seconds 2)
6
Get
Milliseconds
Number of 10 msec 2)
BYTE n = 10 * d + 4 (bits 0 ... 6)
7
Get
Module code 3)
Module code of the module which registered the error
BYTE n = 10 * d + 5
8
Get
Module number
Module position of the module which registered the error; 63 = error not module-related
BYTE n = 10 * d + 6 (bits 6, 7)
9
Get
Channel number 3)
Number of the first faulty channel
BYTE n = 10 * d + 7 (bits 0 ... 5)
1) d (diagnostic event) = 0 ... 39; most current diagnostic event = 0; 2) Measured from the time the power supply was switched on 3) If the error number = 0, the content is also 0. If the error number is between 128 ... 199
(error class 3), the content is not relevant (service case).
B-20
Festo P.BE-CPX-FB32-EN en 1111a
Page 119
B. Ethernet/IP Objects of the CPX-FB32
Attr. No.
Access
Designation
Description
Type
Function no. 3488 + n 1)
10
Get
Error number
Possible error messages see System Manual chapter 5
BYTE n = 10 * d + 8
11
Get
Subsequent channels 3)
Number of subsequent channels with the same error
BYTE n = 10 * d + 9
1) d (diagnostic event) = 0 ... 39; most current diagnostic event = 0; 2) Measured from the time the power supply was switched on 3) If the error number = 0, the content is also 0. If the error number is between 128 ... 199
(error class 3), the content is not relevant (service case).
Festo P.BE-CPX-FB32-EN en 1111a
B-21
Page 120
B. Ethernet/IP Objects of the CPX-FB32
B.4.5 Diagnostic Trace Status Object Object class: Instances:
135 1
Attr. No.
Access
Name
Type
Function no.
1
Get
Number of trace entries in the diagnostic memory
BYTE
3482 (bits 0 ... 7)
2
Get
Status of diagnostic memory 0: Recording active 1: Recording inactive
BYTE
3483 (bits 0, 1)
3
Get/Set
Clear_trace1, access via EDS
BYTE
-
4
Get/Set
Clear_trace2, access via explicit messaging; Confirms activity carried out by resetting (0) the attribute value
BYTE
-
5
Get/Set
Entries remanent with Power on 0: active (presetting) 1: inactive
BYTE
3480 (bit 0)
6
Get/Set
Run/stop filter 1 0: Stop after 40 entries (store the first 40 entries) 1: Overwrite old entries (store the last 40 entries), presetting)
BYTE
3480 (bit 1)
7
Get/Set
Run/stop filter 2 0: Run/stop filter 2 inactive (presetting) 1: Record up to the defined FN 2: Record up to the defined FN + MN 3: Record up to the defined FN + MN + KN 4: Record from the defined FN 5: Record from the defined FN + MN 6: Record from the defined FN + MN + KN 7: reserved
BYTE
3484 (bits 0 ... 2)
8
Get/Set
End of error filter 0: Record going errors (end of error) (filter inactive, presetting) 1: Do not record going errors (end of error) (filter active)
BYTE
3484 (bit 3)
B-22
Festo P.BE-CPX-FB32-EN en 1111a
Page 121
B. Ethernet/IP Objects of the CPX-FB32
Attr. No.
Access
Name
Type
Function no.
9
Get/Set
Error number filter FN = error number 0: Error number filter inactive (presetting) 1: Record only defined FN 2: Do not record defined FN 3: reserved
BYTE
3484 (bits 4, 5)
10
Get/Set
Module/channel filter With this diagnostic memory filter, the registering of errors of other modules or channels can be suppressed in order that errors in a particular module or channel can be analysed. FN = error number 0: Module/channel filter inactive (presetting) 1: Record only FN of a module 2: Record only FN of a channel 3: reserved
BYTE
3484 (bits 6, 7)
11
Get/Set
Module number Module number for the diagnostic memory filter
BYTE
3485 (bits 0 ... 7)
12
Get/Set
Channel number Channel number for the diagnostic memory filter
BYTE
3486 (bits 0 ... 7)
13
Get/Set
Error number Fault number for the diagnostic memory filter
BYTE
3487 (bits 0 ... 7)
Festo P.BE-CPX-FB32-EN en 1111a
B-23
Page 122
B. Ethernet/IP Objects of the CPX-FB32
B.4.6 General Module Parameter Object Object class: Instances:
101 1 ... 48
Applicable is: Instance number = Module number + 1 This Object enables general access to the module parameters of all existing and future CPX modules. Use the general parameter Module Object for parameterising modules with word or double-word parameters. Examples for modules with word or double-word parameters are: the analogue 4-way input module CPX-4AE-I, the temperature module CPX-4AE-T or the CPX-CP interface. You can access three types of parameters via the Attributes of the general Module Parameter Object: – byte parameters through the Attribute 1 ... 64 – word parameters through the Attribute 65 ... 127 – double-word parameters through the Attribute 129 ... 189 Procedure for parameterisation
1. Refer to the module manual for the function number of the parameter which you wish to set. 2. Search for this function number in the last column of Tab. B/6 (byte and word parameter) or Tab. B/7 (double-word parameter) 3. Read the appropriate Attribute number from the table. Examples for parameterisation with the general Module Parameter Object can be found in Appendix B.5.2.
B-24
Festo P.BE-CPX-FB32-EN en 1111a
Page 123
B. Ethernet/IP Objects of the CPX-FB32
Attribute no. Byte
Word
1
Parameters
Function no.
See relevant module manual for the parameter
4828 + m * 64 + 0
Word –
65 4828 + m * 64 + 1
2 66
4828 + m * 64 + 2
3 67
4828 + m * 64 + 3
4 68
4828 + m * 64 + 4
5 69
4828 + m * 64 + 5
6 70
4828 + m * 64 + 6
7 71
4828 + m * 64 + 7
8 72
4828 + m * 64 + 8
9 73
4828 + m * 64 + 9
10 74
4828 + m * 64 + 10
11 75
4828 + m * 64 + 11
12 76 ...
4828 + m * 64 + ... ...
...
4828 + m * 64 + ... ...
...
4828 + m * 64 + ... ... 4828 + m * 64 + 59
... 124
4828 + m * 64 + 60
61 125
4828 + m * 64 + 61
62 126
4828 + m * 64 + 62
63 127 64
–
4828 + m * 64 + 63
Tab. B/6: General module parameter object: Assignment of the Attributes for word parameters to the function numbers
Festo P.BE-CPX-FB32-EN en 1111a
B-25
Page 124
B. Ethernet/IP Objects of the CPX-FB32
Attribute no. Byte
–
–
–
129
4828 + m * 64 + 3 131
5
133
4828 + m * 64 + 7 135
9 10 ...
4828 + m * 64 + 11 ...
4828 + m * 64 + ... ...
... 185
4828 + m * 64 + 59 187
61 62
4828 + m * 64 + 60 188
– 189
4828 + m * 64 + ... 4828 + m * 64 + ...
186
...
4828 + m * 64 + 9 4828 + m * 64 + 10
...
...
64
4828 + m * 64 + 8 136
12
4828 + m * 64 + 5 4828 + m * 64 + 6
134
8
63
4828 + m * 64 + 4 132
6
...
4828 + m * 64 + 0
4828 + m * 64 + 2 130
4
11
See relevant module manual for the parameter
4828 + m * 64 + 1
2
7
Function no.
DWord DWord DWord DWord
1
3
Parameters
4828 + m * 64 + 61 4828 + m * 64 + 62
– –
4828 + m * 64 + 63
Tab. B/7: General module parameter object: Assignment of the Attributes for double-word parameters to the function numbers
B-26
Festo P.BE-CPX-FB32-EN en 1111a
Page 125
B. Ethernet/IP Objects of the CPX-FB32
B.4.7 Force parameter The first word receives the lowest instance number of the relevant Object. The second word receives the second lowest instance number, etc. Object
Description
108
Force state digital inputs
109
Force mode digital inputs
110
Force state digital outputs
111
Force mode digital outputs
Tab. B/8: Objects for Force Parameter of digital I/O modules Object
Description
116
Force state analogue inputs
117
Force mode analogue inputs
118
Force state analogue outputs
119
Force mode analogue outputs
Tab. B/9: Objects for Force Parameter of analogue I/O modules Object
Description
124
Force state inputs technology module
125
Force mode inputs technology module
126
Force state outputs technology module
127
Force mode outputs technology module
Tab. B/10: Objects for Force Parameter for technology module
Festo P.BE-CPX-FB32-EN en 1111a
B-27