Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 15 of 18

CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Ethernet/IP Objects of the CPX-FB32, pages 117 to 125

Pages 117 to 125 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-FB-32

Page 117

B. Ethernet/IP Objects of the CPX-FB32

B.4.3 Status and Diagnostic Object Object class: Instances:

133 1

The status bits and the I/O diagnostic interface are mapped here. Attr. No.

Access

Description

Type

Function no.

1

Get

Status bits (8 bit) Source of error: Bit 0: Valve Bit 1: Output Bit 2: Input Bit 3: Analogue/ technology module Error type: Bit 4: Undervoltage Bit 5: Short circuit/overload Bit 6: Wire break Bit 7: Other error

BYTE

1936

2

Get

Number of the first module in which a fault has occurred

BYTE

1937

3

Get

Diagnostic status

BYTE

4

Get

Error number

BYTE

5

Get/Set

Address I/O diagnostic interface 16 output bits (task data) of the I/O diagnostic interface

WORD

6

Get

Data I/O diagnostic interface 16 input bits (reply data) of the I/O diagnostic interface

WORD

Festo P.BE-CPX-FB32-EN en 1111a

1938

B-19

Page 118

B. Ethernet/IP Objects of the CPX-FB32

B.4.4 Diagnostic Trace Object Object class: Instances:

134 1 ... 40

An instance is created for each diagnostic entry. Attr. No.

Access

1

Get

2

Get

3 4

Designation

Description

Type

Function no. 3488 + n 1)

Marking the first entry after Power on Supplies 1 if it is the first entry after Power on.

BYTE n = 10 * d + 4 (bit 7)

Days

Number of days 2)

BYTE n = 10 * d + 0

Get

Hours

Number of hours 2)

BYTE n = 10 * d + 1

Get

Minutes

Number of minutes 2)

BYTE n = 10 * d + 2

BYTE n = 10 * d + 3

5

Get

Seconds

Number of seconds 2)

6

Get

Milliseconds

Number of 10 msec 2)

BYTE n = 10 * d + 4 (bits 0 ... 6)

7

Get

Module code 3)

Module code of the module which registered the error

BYTE n = 10 * d + 5

8

Get

Module number

Module position of the module which registered the error; 63 = error not module-related

BYTE n = 10 * d + 6 (bits 6, 7)

9

Get

Channel number 3)

Number of the first faulty channel

BYTE n = 10 * d + 7 (bits 0 ... 5)

1) d (diagnostic event) = 0 ... 39; most current diagnostic event = 0; 2) Measured from the time the power supply was switched on 3) If the error number = 0, the content is also 0. If the error number is between 128 ... 199

(error class 3), the content is not relevant (service case).

B-20

Festo P.BE-CPX-FB32-EN en 1111a

Page 119

B. Ethernet/IP Objects of the CPX-FB32

Attr. No.

Access

Designation

Description

Type

Function no. 3488 + n 1)

10

Get

Error number

Possible error messages see System Manual chapter 5

BYTE n = 10 * d + 8

11

Get

Subsequent channels 3)

Number of subsequent channels with the same error

BYTE n = 10 * d + 9

1) d (diagnostic event) = 0 ... 39; most current diagnostic event = 0; 2) Measured from the time the power supply was switched on 3) If the error number = 0, the content is also 0. If the error number is between 128 ... 199

(error class 3), the content is not relevant (service case).

Festo P.BE-CPX-FB32-EN en 1111a

B-21

Page 120

B. Ethernet/IP Objects of the CPX-FB32

B.4.5 Diagnostic Trace Status Object Object class: Instances:

135 1

Attr. No.

Access

Name

Type

Function no.

1

Get

Number of trace entries in the diagnostic memory

BYTE

3482 (bits 0 ... 7)

2

Get

Status of diagnostic memory 0: Recording active 1: Recording inactive

BYTE

3483 (bits 0, 1)

3

Get/Set

Clear_trace1, access via EDS

BYTE

-

4

Get/Set

Clear_trace2, access via explicit messaging; Confirms activity carried out by resetting (0) the attribute value

BYTE

-

5

Get/Set

Entries remanent with Power on 0: active (presetting) 1: inactive

BYTE

3480 (bit 0)

6

Get/Set

Run/stop filter 1 0: Stop after 40 entries (store the first 40 entries) 1: Overwrite old entries (store the last 40 entries), presetting)

BYTE

3480 (bit 1)

7

Get/Set

Run/stop filter 2 0: Run/stop filter 2 inactive (presetting) 1: Record up to the defined FN 2: Record up to the defined FN + MN 3: Record up to the defined FN + MN + KN 4: Record from the defined FN 5: Record from the defined FN + MN 6: Record from the defined FN + MN + KN 7: reserved

BYTE

3484 (bits 0 ... 2)

8

Get/Set

End of error filter 0: Record going errors (end of error) (filter inactive, presetting) 1: Do not record going errors (end of error) (filter active)

BYTE

3484 (bit 3)

B-22

Festo P.BE-CPX-FB32-EN en 1111a

Page 121

B. Ethernet/IP Objects of the CPX-FB32

Attr. No.

Access

Name

Type

Function no.

9

Get/Set

Error number filter FN = error number 0: Error number filter inactive (presetting) 1: Record only defined FN 2: Do not record defined FN 3: reserved

BYTE

3484 (bits 4, 5)

10

Get/Set

Module/channel filter With this diagnostic memory filter, the registering of errors of other modules or channels can be suppressed in order that errors in a particular module or channel can be analysed. FN = error number 0: Module/channel filter inactive (presetting) 1: Record only FN of a module 2: Record only FN of a channel 3: reserved

BYTE

3484 (bits 6, 7)

11

Get/Set

Module number Module number for the diagnostic memory filter

BYTE

3485 (bits 0 ... 7)

12

Get/Set

Channel number Channel number for the diagnostic memory filter

BYTE

3486 (bits 0 ... 7)

13

Get/Set

Error number Fault number for the diagnostic memory filter

BYTE

3487 (bits 0 ... 7)

Festo P.BE-CPX-FB32-EN en 1111a

B-23

Page 122

B. Ethernet/IP Objects of the CPX-FB32

B.4.6 General Module Parameter Object Object class: Instances:

101 1 ... 48

Applicable is: Instance number = Module number + 1 This Object enables general access to the module parameters of all existing and future CPX modules. Use the general parameter Module Object for parameterising modules with word or double-word parameters. Examples for modules with word or double-word parameters are: the analogue 4-way input module CPX-4AE-I, the temperature module CPX-4AE-T or the CPX-CP interface. You can access three types of parameters via the Attributes of the general Module Parameter Object: – byte parameters through the Attribute 1 ... 64 – word parameters through the Attribute 65 ... 127 – double-word parameters through the Attribute 129 ... 189 Procedure for parameterisation

1. Refer to the module manual for the function number of the parameter which you wish to set. 2. Search for this function number in the last column of Tab. B/6 (byte and word parameter) or Tab. B/7 (double-word parameter) 3. Read the appropriate Attribute number from the table. Examples for parameterisation with the general Module Parameter Object can be found in Appendix B.5.2.

B-24

Festo P.BE-CPX-FB32-EN en 1111a

Page 123

B. Ethernet/IP Objects of the CPX-FB32

Attribute no. Byte

Word

1

Parameters

Function no.

See relevant module manual for the parameter

4828 + m * 64 + 0

Word –

65 4828 + m * 64 + 1

2 66

4828 + m * 64 + 2

3 67

4828 + m * 64 + 3

4 68

4828 + m * 64 + 4

5 69

4828 + m * 64 + 5

6 70

4828 + m * 64 + 6

7 71

4828 + m * 64 + 7

8 72

4828 + m * 64 + 8

9 73

4828 + m * 64 + 9

10 74

4828 + m * 64 + 10

11 75

4828 + m * 64 + 11

12 76 ...

4828 + m * 64 + ... ...

...

4828 + m * 64 + ... ...

...

4828 + m * 64 + ... ... 4828 + m * 64 + 59

... 124

4828 + m * 64 + 60

61 125

4828 + m * 64 + 61

62 126

4828 + m * 64 + 62

63 127 64

–

4828 + m * 64 + 63

Tab. B/6: General module parameter object: Assignment of the Attributes for word parameters to the function numbers

Festo P.BE-CPX-FB32-EN en 1111a

B-25

Page 124

B. Ethernet/IP Objects of the CPX-FB32

Attribute no. Byte

–

–

–

129

4828 + m * 64 + 3 131

5

133

4828 + m * 64 + 7 135

9 10 ...

4828 + m * 64 + 11 ...

4828 + m * 64 + ... ...

... 185

4828 + m * 64 + 59 187

61 62

4828 + m * 64 + 60 188

– 189

4828 + m * 64 + ... 4828 + m * 64 + ...

186

...

4828 + m * 64 + 9 4828 + m * 64 + 10

...

...

64

4828 + m * 64 + 8 136

12

4828 + m * 64 + 5 4828 + m * 64 + 6

134

8

63

4828 + m * 64 + 4 132

6

...

4828 + m * 64 + 0

4828 + m * 64 + 2 130

4

11

See relevant module manual for the parameter

4828 + m * 64 + 1

2

7

Function no.

DWord DWord DWord DWord

1

3

Parameters

4828 + m * 64 + 61 4828 + m * 64 + 62

– –

4828 + m * 64 + 63

Tab. B/7: General module parameter object: Assignment of the Attributes for double-word parameters to the function numbers

B-26

Festo P.BE-CPX-FB32-EN en 1111a

Page 125

B. Ethernet/IP Objects of the CPX-FB32

B.4.7 Force parameter The first word receives the lowest instance number of the relevant Object. The second word receives the second lowest instance number, etc. Object

Description

108

Force state digital inputs

109

Force mode digital inputs

110

Force state digital outputs

111

Force mode digital outputs

Tab. B/8: Objects for Force Parameter of digital I/O modules Object

Description

116

Force state analogue inputs

117

Force mode analogue inputs

118

Force state analogue outputs

119

Force mode analogue outputs

Tab. B/9: Objects for Force Parameter of analogue I/O modules Object

Description

124

Force state inputs technology module

125

Force mode inputs technology module

126

Force state outputs technology module

127

Force mode outputs technology module

Tab. B/10: Objects for Force Parameter for technology module

Festo P.BE-CPX-FB32-EN en 1111a

B-27