CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Ethernet/IP Objects of the CPX-FB32, pages 108 to 116
Pages 108 to 116 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Festo CPX-FB-32
Page 108
B. Ethernet/IP Objects of the CPX-FB32
B.3
Objects for the I/O connection
B.3.1 Assembly Object Object class: Instances:
4 3
The Assembly Object bundles together Attributes of various Objects, so that the exchange of data with the Objects can take place via one connection. The following Object instances are saved in the Assembly Object:
B-10
Instance
Description
101
Input data
100
Output data
102
Configuration data
Festo P.BE-CPX-FB32-EN en 1111a
Page 109
B. Ethernet/IP Objects of the CPX-FB32
Remote I/O operating mode Each data range begins on the LSB (least significant bit) of a word. Instance 101: Input Within the instance “Input Assembly Object” all inputs of the CPX system are transmitted cyclically over the network by means of a communication connection. The following sequence applies during transmission: Sequence of transmission 1.
I/O diagnostic interface, if active (16-bit orientated)
2.
Object instances of the analogue channels (16-bit orientated)
3.
Instances of the technology modules (16 or 8-bit orientated)
4.
Object instances of the digital inputs (8-bit orientated)
Instance 101 (input) possesses the following member list in the operating mode Remote I/O: Obj.
Instances Attributes (= Module no. + 1) (channel)
Entries in member list
Type
133
1 ... 48
0/1
I/O diagnostic interface data, if active
WORD
104
1 ... 48
1 ... 32
Analogue channel data
WORD
106
1 ... 48
1 ... 64 / 65 ... 96
Technology module
BYTE/ WORD
102
1 ... 48
1 ... 64
Digital Data
BOOL
Festo P.BE-CPX-FB32-EN en 1111a
B-11
Page 110
B. Ethernet/IP Objects of the CPX-FB32
Instance 100: Output Within the Instance Output in the Assembly Object all outputs of the CPX system will be transmitted over the network by means of one communication connection. The following sequence applies during transmission: Sequence of transmission 1.
I/O diagnostic interface/status byte, if active (16-bit orientated)
2.
Object instances of the analogue channels (16-bit orientated)
3.
Instances of the technology modules (16 or 8-bit orientated)
4.
Object instances of the digital outputs (8-bit orientated)
Instance 100 (Output) possesses the following member list in the operating mode Remote I/O: Obj.
Instances Attributes (= Module no. + 1) (channel)
Entries in member list
Type
133
1 ... 48
0/1
I/O diagnostic interface data, if active
WORD
105
1 ... 48
1 ... 32
Analogue channel data
WORD
107
1 ... 48
1 ... 64 / 65 ... 96
Technology module
BYTE/ WORD
103
1 ... 48
1 ... 64
Digital Data
BOOL
Instance 102: Configuration Instance 102 (Configuration) possesses the following member list:
B-12
Obj.
Number of
Entries in member list
Type
199
1
Configuration Array data
ARRAY
Festo P.BE-CPX-FB32-EN en 1111a
Page 111
B. Ethernet/IP Objects of the CPX-FB32
The I/O Objects 102 ... 107 also possess the following attributes:
Festo P.BE-CPX-FB32-EN en 1111a
Attribute
Entries ...
Type
100
Number of data of the module in BYTE or WORD
BYTE
101
Data type: – D1h: BYTE – D2h: WORD
BYTE
102
All data values
ARRAY
B-13
Page 112
B. Ethernet/IP Objects of the CPX-FB32
Remote controller operating mode Each data range begins on the LSB (least significant bit) of a word. Instance 100: Output Instance 100 (Output) possesses the following member list in the operating mode Remote Controller: Obj.
Number of
Entries in member list
Type
107
1 ... 64 / 65 ... 96
Technology module
BYTE/ WORD
Instance 101: Input Instance 101 (input) possesses the following member list: Obj.
Number of
Entries in member list
Type
106
1 ... 64 / 65 ... 96
Technology module
BYTE/ WORD
Transmission by communication types Polled I/O or COS/Cyclic. Instance 102: Configuration Instance 102 (Configuration) must have the value “0” in the operating mode Remote Controller.
B-14
Festo P.BE-CPX-FB32-EN en 1111a
Page 113
B. Ethernet/IP Objects of the CPX-FB32
B.4
Objects for system data and diagnosis
B.4.1 Identity Object Object class: Instances:
01 1
The Identity Object contains the identification and general information on the CPX-FB32.
Festo P.BE-CPX-FB32-EN en 1111a
Attr. No.
Access
Description
Type
1
Get
Vendor ID
WORD
2
Get
Device type
WORD
3
Get
Product code
WORD
4
Get
Revision (major/minor)
WORD
5
Get
Status
WORD
6
Get
Serial number
DOUBLE
7
Get
Product name
ARRAY
14
Get/Set
Semaphore
ARRAY
100
Get
Operating Mode
BOOL
101
Get
External Module Identifiers
ARRAY
B-15
Page 114
B. Ethernet/IP Objects of the CPX-FB32
B.4.2 System Object (for operating mode Remote I/O) Object class: Instances:
132 1
This Object is only available in the operating mode Remote I/O. Attr. No.
Access
Description
Type
Function no.
1
Get
CPX operating mode (bit 0 ... 3) 0: Remote I/O without FEC/CEC 1: Remote I/O with FEC or CEC 2: Remote controller without bus node 3: Remote controller with bus node
BYTE
0 (bit 0 ... 3)
B-16
CPX equipment status (bit 4) Specifies whether the current equipment fitted to the CPX corresponds to the saved CPX equipment status. 0: equal 1: unequal
0 (bit 4)
Handheld (bit 5) Specifies whether or not a handheld is connected. 0: No handheld connected 1: Handheld connected
0 (bit 5)
Force mode (bit 6) Specifies whether Force is blocked or enabled. 0: blocked 1: enabled
0 (bit 6)
Bit 7: reserved
0 (bit 7)
Festo P.BE-CPX-FB32-EN en 1111a
Page 115
B. Ethernet/IP Objects of the CPX-FB32
Attr. No.
Access
Description
Type
Function no.
2
Get
Fail safe Specifies whether Fail Safe is active or inactive. 0: inactive 1: active
BYTE
1 (bit 0, 1)
System Idle mode Specifies whether Idle mode is active or inactive. 0: inactive 1: active
1 (bit 2, 3)
3
Get
Monitoring CPX terminal (bit 0 ... 7) Specifies whether the monitoring of short circuit/overload and undervoltage is active or inactive. Bit 0: Monitoring SCS (short circuit/ overload sensor supply) Bit 1: Monitoring SCO (short circuit/ overload outputs) Bit 2: Monitoring VOut (Undervoltage outputs) Bit 3: Monitoring VVal (Undervoltage valves) Bit 4: Monitoring SCV (short circuit valves) Bits 5 ... 7: reserved 0: inactive 1: active
BYTE
2 (bit 0 ... 7)
4
Get
Number of input bytes (Rx size) Specifies the number of input bytes of the CPX terminal.
BYTE
-
5
Get
Number of output bytes (Tx size) Specifies the number of output bytes of the CPX terminal.
BYTE
-
Festo P.BE-CPX-FB32-EN en 1111a
B-17
Page 116
B. Ethernet/IP Objects of the CPX-FB32
Attr. No.
Access
Description
Type
Function no.
9
Get/Set
Monitoring (bit 0 ... 7) Bit 0: Monitoring SCS (short circuit/ overload sensor supply) Bit 1: Monitoring SCO (short circuit/ overload outputs) Bit 2: Monitoring Uout (Undervoltage outputs) Bit 3: Monitoring Uval (Undervoltage valves) Bit 4: Monitoring SCV (short circuit valves) Bits 5 ... 7:reserved 1: active (presetting) 0: inactive
BYTE
4401 (bit 0 ... 7)
10
Get/Set
Fail safe 0: Reset all outputs (presetting) 1: Hold last state (Retain signal status) 2: Assume Fault mode
BYTE
4402 (bit 0, 1)
11
Get/Set
Force mode 0: blocked 1: enabled
BYTE
4402 (bit 2, 3)
12
Get/Set
System Idle mode 0: Reset all outputs (presetting) 1: Hold last state (Retain signal status) 2: Assume Idle mode
BYTE
4402 (bit 4, 5)
13
Get/Set
System start 0: System start with default parameterisation (factory setting) and current CPX disassembly; external parameterisation possible (presetting) 1: System start with stored parameterisation and stored CPX expansion; Parameter and CPX-expansion are stored remanently; external parameterisation is blocked; the M-LED on the fieldbus node is lit
BYTE
4402 (bit 6)
B-18
Festo P.BE-CPX-FB32-EN en 1111a