The text of a manual · part 6 of 18

CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Commissioning, pages 35 to 44

Pages 35 to 44 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-FB-32

Page 35

Commissioning

Chapter 2

Commissioning

Festo P.BE-CPX-FB32-EN en 1111a

2-1

Page 36

2. Commissioning

Table of contents

2.

Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

2.1

Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.1 Ascertaining the address range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.2 Address assignment of the CPX terminal . . . . . . . . . . . . . . . . . . . . . 2.1.3 Address assignment after extension/conversion . . . . . . . . . . . . . . Bus configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2.1 Registering station properties in the configuration program . . . . . 2.2.2 Overview of configuration on the EtherNet/IP . . . . . . . . . . . . . . . . . 2.2.3 Set up a listen-only connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2.4 Configuration with RSLogix5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameterisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.1 Methods of parameterisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.2 Parameterisation via Configuration Assembly (method 1) . . . . . . . 2.3.3 Parameterisation via software (method 2a) . . . . . . . . . . . . . . . . . . . 2.3.4 Parameterisation with the Handheld (method 2b) . . . . . . . . . . . . . 2.3.5 Parameterisation via the PLC user program (method 3) . . . . . . . . . 2.3.6 Parameterisation with EDS files (method 4) . . . . . . . . . . . . . . . . . . Notes on parameters for Idle mode and Fault mode . . . . . . . . . . . . . . . . . . . Check list for commissioning the CPX terminal with FB32 . . . . . . . . . . . . . . .

2-3 2-4 2-10 2-17 2-20 2-20 2-23 2-24 2-25 2-29 2-31 2-32 2-36 2-36 2-37 2-38 2-39 2-40

2.2

2.3

2.4 2.5

2-2

Festo P.BE-CPX-FB32-EN en 1111a

Page 37

2. Commissioning

2.1

Addressing Before configuring, ascertain the exact number of available inputs/outputs. A CPX terminal consists of a different number of I/Os, depending on what you have ordered and on the configuration of the field bus node. The I/Os will be assigned automatically within the CPX terminal.

Note – Maximum 10 electric modules including the fieldbus node plus a pneumatic interface or MPA pneumatic modules are permitted on a CPX terminal. – If you configure the CPX terminal with an EDS file, the field bus node in the first location must be installed as module 0. – The CPX terminal has an address range of up to 64 bytes of inputs and 64 bytes of outputs.

Festo P.BE-CPX-FB32-EN en 1111a

2-3

Page 38

2. Commissioning

2.1.1

Ascertaining the address range Address assignment of the modules Electric modules The individual modules are displayed with their identifier on the handheld. In the case of the I/O modules, the identifier is also shown in the LED viewing window. With the aid of this identifier, you can read the type of module and therefore the number of inputs and outputs occupied by the module.

Electric modules

Type

Module identifier 1)

Assigned addresses Inputs

Outputs

Fieldbus node FB32

CPX-FB32

FB32-...

–

–

Digital 4-input module

CPX-4DE

4DI

4 E 2)

–

Digital 8-input module

CPX-8DE

8DI

8I

–

Digital 8-input module with channel diagnostics

CPX-8DE-D

8DI-D

8I

–

Digital 16-input module

CPX-16DE

16DI

16 I

–

Digital 16-input module with channel diagnostics

CPX-16DE-D

16DI-D

16 I

–

Digital 8-input module n-switching

CPX-8NDE

8NDI

8I

–

Digital 4-output module

CPX-4DA

4DO

–

4 O 2)

Digital 8-output module

CPX-8DA

8DO

–

8O

Digital 8-output module, high-current variant

CPX-8DA-H

8DO-H

–

8O

1) Module identification in Handheld 2) 8 bits are always occupied

Tab. 2/1: Overview of electric CPX modules (part 1)

2-4

Festo P.BE-CPX-FB32-EN en 1111a

Page 39

2. Commissioning

Electric modules 1)

Type

Module identifier

Assigned addresses Inputs

Outputs

Digital multi I/O module

CPX-8DE-8DA

8DI/8DO

8I

8O

Analogue 2-input module

CPX-2AE-U-I

2AI

32 I

–

Analogue 4-input module

CPX-4AE-U-I

4AI

64 I

–

Analogue 4-input module

CPX-4AE-I

4AI-I

64 I

–

Analogue 4-input module (temperature module)

CPX-4AE-T

4AI-T

32/64 I 2)

–

Analogue 2-output module

CPX-2AA-U-I

2AO

–

32 O

CP interface

CPX-CP-4-FB

CPI

128 I 3)

128 O 3)

Front End Controller

CPX-FEC

FEC

64/128 I 4)

64/128 O 4)

1) Additional modules in preparation 2) Number of inputs switchable between 2 and 4 3) Maximum number (actual allocation depends on the string allocation) 4) With the CPX-FB32, switchable via DIL switches (see 1.2.2)

Tab. 2/2: Overview of electric CPX modules (part 2) The address assignment within the individual I/O modules can be found in the manual for the I/O modules. Details on the CP interface can be found in the manual for the CP interface.

Festo P.BE-CPX-FB32-EN en 1111a

2-5

Page 40

2. Commissioning

Pneumatic modules and pneumatic interfaces The following table shows the number of output addresses occupied by the pneumatic modules: Pneumatic interfaces 1)

Type

Module identification 2)

Assigned addresses Inputs

Outputs

Pneumatic interface for MPA-S valves VMPA-FB-EPL-... (type 32)

–

–

–

Pneumatic interface for MPA-F valves VMPAF-FB-EPL-... (Type 33)

–

–

–

Pneumatic interface for MPA-L valves VMPAL-EPL-CPX (Type 34)

–

–

–

Pneumatic interface for CPA valves (type 12) with setting: 3) – 1 ... 8 valve coils – 1 ... 16 valve coils – 1 … 2 4 valve coils (22 can be used)

CPX-GP-CPA-10 CPX-GP-CPA-14

CPA10/14

–

Pneumatic interface for Midi/Maxi valves (type 03) with setting: 2) – 1 ... 8 valve coils – 1 ... 16 valve coils – 1 ... 24 valve coils – 1 … 32 valve coils (26 can be used)

CPX-GP-03-4.0

Pneumatic interface for VTSA pneumatic (ISO, Type44) 2) and VTSA-F pneumatic – 1 ... 8 valve coils – 1 ... 16 valve coils – 1 ... 24 valve coils – 1 ... 32 valve coils

VABA-10S6-x1

8O 16 O 24 O TYPE3

–

8O 16 O 24 O 32 O ISO plug-in or type 44 3)

– 8O 16 O 24 O 32 O

1) Additional interfaces in preparation 2) Module identification in Handheld 3) Setting with DIL switches in the pneumatic interface (see description, CPX-EA modules).

Tab. 2/3: Overview of pneumatic interfaces

2-6

Festo P.BE-CPX-FB32-EN en 1111a

Page 41

2. Commissioning

Pneumatic modules 1)

Type of electronic module

Module identification 2)

Assigned addresses Inputs

Outputs

MPA1 pneumatic module (type 32, 33) without galvanic isolation

VMPA1-FB-EMS-8

MPA1S

–

8O

MPA1 pneumatic module (type 32, 33) with galvanic isolation

VMPA1-FB-EMG-8

MPA1G

–

8O

MPA2 pneumatic module (type 32, 33) without galvanic isolation

VMPA2-FB-EMS-4

MPA2S

–

4 O 3)

MPA2 pneumatic module (type 32, 33) with galvanic isolation

VMPA2-FB-EMG-4

MPA2G

–

4 O 3)

MPA1 pneumatic module VMPA1-FB-EMS(type 32, 33) without galvanic D2-8 isolation with diagnostic function D2

MPA1S-D

–

8O

MPA1 pneumatic module (type 32, 33) with galvanic isolation with diagnostic function D2

VMPA1-FB-EMGD2-8

MPA1G-D

–

8O

MPA2 pneumatic module VMPA2-FB-EMS(type 32, 33) without galvanic D2-4 isolation with diagnostic function D2

MPA2S-D

–

4 O 3)

MPA2 pneumatic module (type 32, 33) with galvanic isolation with diagnostic function D2

MPA2G-D

–

4 O 3)

VMPA2-FB-EMGD2-4

1) Additional modules in preparation 2) Module identification in Handheld 3) 8 bits are always assigned

Tab. 2/4: Overview of pneumatic modules MPA-S and MPA-F

Festo P.BE-CPX-FB32-EN en 1111a

2-7

Page 42

2. Commissioning

Pneumatic modules 1)

Type of electrical interlinking

Module identification 2)

Assigned addresses Inputs

Outputs

MPA-L pneumatic module (type 34) for one solenoid valve, one solenoid coil

VMPAL-EVAP-10-1

MPAL

–

1A

MPA-L pneumatic module (type 34) for one solenoid valve, 2 solenoid coils

VMPAL-EVAP-10-2

MPAL

–

2A

MPA-L pneumatic module (type 34) VMPAL-EVAP-10-1-4 MPAL for 4 solenoid valves, 4 solenoid coils

–

4O

MPA-L pneumatic module (type 34) VMPAL-EVAP-10-2-4 MPAL for 4 solenoid valves, 8 solenoid coils

–

8O

1) Additional modules in preparation 2) Module identification in Handheld

Tab. 2/5: Overview of pneumatic modules MPA-L The address assignment within the pneumatic modules can be found in the manual for the valve terminal pneumatics. Additional information on MPA pneumatic modules can be found in the description CPX-EA modules (P.BE-CPX-EA-...).

2-8

Festo P.BE-CPX-FB32-EN en 1111a

Page 43

2. Commissioning

Calculating the number of inputs/outputs Use the following table for calculating the number of inputs and outputs on your CPX terminal. Input/output modules and system diagnostics

Inputs

Outputs

1. I/O diagnostic interface, if set

+ 16 I/O

+

_____ I

+

_____ O

2. Number of input modules CPX-4DE

+ __ x 8I 1)

+

_____ I

3. Number of input modules CPX-8DE, -8NDE, 8DE-D + __ x 8 I

+

_____ I

4. Number of input modules CPX-16DE

+ __ x 16I

+

_____ I

5. Number of output modules CPX-4DA

+ __ x 8O 1)

+

_____ O

6. Number of output modules CPX-8DA

+ __ x 8 O

+

_____ O

7. Number of Multi I/O modules CPX-8DE-8DA

+ __ x 8 I/O

+

_____ I

+

_____ O

+ __ x 32 I

+

_____ I

9. Number of analogue input modules CPX-4AE-I + __ x 64 E/ x 32 I

+

_____ I

10.Number of analogue input modules CPX-4AE-T

+ __ x 64 I

+

_____ I

11.Number of analogue output modules CPX-2AA-U-I

+ __ x 32 O

+

_____ O

+

_____ O

13.Midi/Maxi, CPA or VTSA pneumatic interface: Number of configured valve solenoid coils (+8 O, 16 O, 24 O, 32 O) Configured at the factory is 32 O (Midi/Maxi, VTSA) or 24 O (CPA)!

+

_____ O

+ __ x 8 O 1)

+

_____ O

8. Number of analogue input modules CPX-2AE-U-I

12.Number of inputs and outputs of other modules (e.g. CP interface)

14.Number of MPA1 or MPA2 pneumatic modules

+ __ I/O

15.Total number of Inputs/Outputs to be configured Total of 1. to 14.: 1)

+

_____ I

= ∑ _____ I

= ∑ _____ O

8 bits are always assigned (4 remain unused).

Tab. 2/6: Ascertaining the number of inputs and outputs

Festo P.BE-CPX-FB32-EN en 1111a

2-9

Page 44

2. Commissioning

2.1.2

Address assignment of the CPX terminal Note If necessary, status bits or an I/O diagnostic interface can be activated by DIL switch (see Tab. 1/2): – If the 8 status bits are activated, they will occupy the first 16 inputs in the address range (8 used). – If the I/O diagnostic interface is activated, it will occupy the first 16 inputs and outputs in the address range. If you configure the CPX terminal with an EDS file, the field bus node must be installed in the first location as module 0.

Basic rules for addressing

2-10

–

The address assignment of the inputs does not depend on the address assignment of the outputs.

–

Counting from left to right, addressing bytewise: Modules with less than 8 bits occupy an 8-bit address space, but do not use it completely.

–

The fieldbus node counts as a module with 0 inputs and 0 outputs if the status bits and the I/O diagnostic interface are deactivated.

–

The I/Os of different module types are assigned separately from each other. The sequence in the following table applies:

Festo P.BE-CPX-FB32-EN en 1111a