Page 25
1. Installation
Number of I/O bytes (Remote Controller operating mode)
Setting DIL switch 2
8 byte I/8 byte O for communication of the fieldbus node with the CPX-FEC or CPX-CEC.
2.1: OFF 2.2: OFF (default)
Reserved
2.1: ON 2.2: OFF
16 byte I/16 byte O for communication of the fieldbus node with the CPX-FEC or CPX-CEC.
2.1: OFF 2.2: ON
Reserved
2.1: ON 2.2: ON
Tab. 1/3: Setting the number of I/O bytes with DIL switch 2 (operating mode Remote Controller)
Festo P.BE-CPX-FB32-EN en 1111a
1-11
Page 26
1. Installation
Setting the IP addressing with DIL switch 3 With DIL switch 3 you can set the type of addressing or the IP address of the fieldbus node.
7
7
6
6
5
5
2 1
Setting: All switches OFF (factory setting)
3
4
4 3 2 1
Fixed addressing via DIL switch
8
8
Dynamic addressing via BOOTP/DHCP or saved addressing
Setting: Host ID of the IP address
Tab. 1/4: Settings of DIL switch 3 for different types of addressing The factory setting is the dynamic addressing. Observe the detailed information on addressing in section 1.3.3.
1-12
Festo P.BE-CPX-FB32-EN en 1111a
Page 27
1. Installation
1.3
Connecting the Ethernet fieldbus
1.3.1
Ethernet cable Note Faulty installation or high transmission rates may cause data transmission errors as a result of signal reflections and attenuations. Causes of the transmission errors can be: – incorrect screened connection – branches – transmission over long distances – inappropriate cables Observe the cable specifications. Refer to the manual for your control system for information on the type of cable to be used.
Cable specification
Screened, flexible Ethernet round cable of category 5 Max. exterior diameter: 5.4 mm Wire diameter: 0.89 ... 1.0 mm AWG24-26 Pre-assembly: Plug screwed on, Type NECU-M-S-D12G4-C2-ET, Part no. 543109
Note If the CPX terminal is mounted movably into a machine, the fieldbus cable on the movable part must be provided with strain relief. Also observe the corresponding regulations in EN 60204 Part 1. Applicable for the fieldbus length are the specifications for Ethernet networks according to ANSI/TIA/EIA-568-B.1
Festo P.BE-CPX-FB32-EN en 1111a
1-13
Page 28
1. Installation
1.3.2
Fieldbusinterface of the CPX-FB32 There is a 4-pin M12 socket with D-code on the fieldbus node for connecting the valve terminal to the fieldbus. The socket is compatible with SPEEDCON® plugs.
M12 socket EtherNet/IP
Pin allocation
Explanation
Pin equivalent with RJ45 plug
1. TX+ 2. RX+ 3. TX– 4. RX– Housing: screen
Transmitted data+ Received data+ Transmitted data– Received data–
1 3 2 6
Tab. 1/5: Pin assignment of the fieldbus interface of the CPX-FB32 (M12 4pin)
Connection with fieldbus plugs from Festo With the fieldbus plug from Festo (type NECU-M-S-D12G4C2-ET, TN 543109), you connect the CPX terminal to the fieldbus.
1-14
Festo P.BE-CPX-FB32-EN en 1111a
Page 29
1. Installation
1.3.3
Setting the IP address For setting the IP address, CPX-FB32 four options are available to you.
Note When changes are made to the network settings of the CPX-FB32, the Modify LED “M” flashes yellow: • In this case, restart the CPX-FB32 with Power OFF/ON.
Dynamic addressing via BOOTP/DHCP Factory setting
In the factory setting, all switch elements of the DIL switch 3 are set to OFF and BOOTP/DHCP is activated in the CPX-FB32. The dynamic addressing via BOOTP/DHCP is then set (see Tab. 1/4). For dynamic addressing, a BOOTP/DHCP server must be located in the network. If you wish to change from another type of addressing back to dynamic addressing: 1. Set all switch elements of DIL switch 3 to OFF (see Tab. 1/4). 2. Activate DHCP with the Handheld (CPX-MMI) or the program “BOOTP-DHCP Server” from Rockwell Automation. Use network settings stored in the CPX-FB32 The CPX-FB32 offers the option to save the network settings in a non-volatile memory. DHCP/BOOTP is thereby deactivated. 1. If necessary, set all switch elements of the DIL switch to OFF (see Tab. 1/4).
Festo P.BE-CPX-FB32-EN en 1111a
1-15
Page 30
1. Installation
2. Set the network settings with the Handheld (CPX-MMI) or the program “BOOTP-DHCP Server” from Rockwell Automation. This activates saving of the network settings. Fixed addressing via DIL switch Tip
The fixed setting of the IP address is to be recommended for test purposes during commissioning or for small networks.
Settings
If a (binary coded) number not equal to 0 or 255 is set with the switch elements of DIL switch 3, the IP address is assigned fixed. The set number specifies the host ID of the address “192.168.1.xxx” (see Fig. 1/4).
7
7
6
6
5
5
2 1
20 + 22 = 1+4= 5
3
4
4 3 2 1
Example: Set IP address: 192.168.1.038 8
8
Example: Set IP address: 192.168.1.005
21 + 22 + 25 = 2 + 4 + 32 = 38
Fig. 1/4: Examples of set IP addresses (binary coded) with fixed addressing In case of fixed addressing, the setting of the network mask and the gateway are set unchangeably to: Network mask: 255.255.255.0 Gateway: 0.0.0.0
1-16
Festo P.BE-CPX-FB32-EN en 1111a
Page 31
1. Installation
Network setting stored in the CPX-FB32 and setting with DIL switches Analogously to the section “Fixed addressing via DIL switches”, the last octet of the IP address is set with the DIL switch 3. But the first 3 octets are not necessarily “192.168.1”, but can be freely selected via the IP address parameter. The settings can be changed with the Handheld (CPX-MMI) or via the CPX Festo Maintenance Tool (CPX-FMT).
This addressing option is available to you from Revision 18.
Festo P.BE-CPX-FB32-EN en 1111a
1-17
Page 32
1. Installation
1.3.4
Extended Ethernet settings Via the “Ethernet Link Object” (see appendix B.2.3), you can undertake additional settings for the Ethernet connection. Configure the Ethernet Link Object via your EtherNet/IP Master or scanner. The extended Ethernet settings are described in the following. Automatic setting (factory setting) It is standard for the fieldbus baud rate and the Duplex mode to be recognised automatically by the CPX-FB32. Baud rate The field bus baud rate can be switched via EtherNet/IP and is set via Attribute no. 6 (Interface Speed) of the Ethernet Link Object. The following settings are possible: –
10 MBd
–
100 MBd
Duplex mode The full Duplex mode can be activated/deactivated.
1.3.5
Use Webserver functions of the CPX-FB32 A Webserver is integrated in the CPX-FB32. The Webserver makes available read access to the most important parameters and diagnostic functions.
1-18
Festo P.BE-CPX-FB32-EN en 1111a
Page 33
1. Installation
1.4
Pin assignment of power supply Warning • Use for the electrical power supply only PELV circuits in accordance with EN 60204-1 (Protective Extra-Low Voltage, PELV). • Also consider the general requirements for PELV circuits in accordance with EN 60204-1. • Use only voltage sources that ensure a reliable electric separation of operating voltage in accordance with EN 60204-1. Through the use of PELV circuits, protection from electric shock (protection from direct and indirect contact) in accordance with EN 60204-1 is ensured (Electrical equipment of machines. General requirements). The current consumption of a CPX terminal depends on the number and type of integrated modules and components. Read the information on power supply as well as on the earthing measures to be carried out in the CPX system manual.
Festo P.BE-CPX-FB32-EN en 1111a
1-19
Page 34
1. Installation
System power supply, additional power supply and valve power supply
Plug
Pin assignment of interlinking block with
1 2 4 M18 system supply type CPX-GE-EV-S...
additional supply type CPX-GE-EV-Z...
valve supply type CPX-GE-EV-V...
1: 24 VEL/SEN 2: 24 VVAL / 24 VOUT 3: 0 VEL/SEN / 0 VVAL / 0 VOUT 4: Earth connection
1: Free (not connected) 2: 24 VOUT 3: 0 VOUT 4: Earth connection
1: Free (not connected) 2: 24 VVAL 3: 0 VVAL 4: Earth connection
A: 24 VEL/SEN B: 24 VVAL / 24 VOUT C: Earth connection D: 0 VEL/SEN / 0 VVAL / 0 VOUT (leading)
A: Free (not connected) B: 24 VOUT C: Earth connection D: 0 VOUT (leading)
A: Free (not connected) B: 24 VVAL C: Earth connection D: 0 VVAL (leading)
3 C D
B 7/8”-4POL
A
Pin designation: Pay attention to the specifications on the plug.
2 1
3 4 7/8”-5POL VEL/SEN: VOUT: VVAL:
Through the interlinking blocks with system, additional and valve power supply of type CPX-GE-EV-S..., CPX-GE-EV-Z... or CPX-GE-EV-V..., the CPX terminal is supplied with operating and load voltage.
1: 0 VVAL / 0 VOUT 2: 0 VEL/SEN 3: Earth connection (leading) 4: 24 VEL/SEN 5: 24 VVAL / 24 VOUT
1: 0 VOUT 2: Free (not connected) 3: Earth connection (leading) 4: Free (not connected) 5: 24 VOUT
–
5
Operating voltage electronics/sensors Load voltage outputs Load voltage valves
Tab. 1/6: Pin assignment for system supply, additional supply and valve supply
1-20