Page 15
Installation
Chapter 1
Installation
Festo P.BE-CPX-FB32-EN en 1111a
1-1
Page 16
1. Installation
Table of contents
1.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.1 1.2
General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings of the DIL switches on the fieldbus node . . . . . . . . . . . . . . . . . . . . . 1.2.1 Removing and mounting the cover for the DIL switches . . . . . . . . . 1.2.2 Settingthe DIL switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Ethernet fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.1 Ethernet cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.2 Fieldbusinterface of the CPX-FB32 . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.3 Setting the IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.4 Extended Ethernet settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.5 Use Webserver functions of the CPX-FB32 . . . . . . . . . . . . . . . . . . . Pin assignment of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 1-7 1-7 1-8 1-13 1-13 1-14 1-15 1-18 1-18 1-19
1.3
1.4
1-2
Festo P.BE-CPX-FB32-EN en 1111a
Page 17
1. Installation
1.1
General installation instructions Warning Before carrying out installation and maintenance work, switch off the following: – Compressed air supply – Operating voltage supply for the electronics/sensors – Load voltage supply for the outputs/valves In this way, you can avoid: – uncontrolled movements of loose tubing
– unexpected movements of the connected actuators
– non-defined switching states of the electronic components
Caution The CPX fieldbus node contains electrostatically sensitive components. • Therefore, do not touch any components. • Observe the handling specifications for electrostatically sensitive devices. They will help you avoid damage to the electronics.
Note Use protective caps or blanking plugs to seal unused connections. This is how you achieve protection class IP65/IP67.
Information about mounting of the CPX terminal can be found in the CPX system description (P.BE-CPX-SYS-...).
Festo P.BE-CPX-FB32-EN en 1111a
1-3
Page 18
1. Installation
Electrical connection and display elements On the fieldbus node CPX-FB32 you will find the following connection and display elements:
1 4
3
2
1 Bus-status-specific and CPX-specific LEDs
4 Service interface for the Handheld (V24)
2 Fieldbus interface: Ethernet connection (4-pin M12 socket, D-coded)
3 Transparent cover for the DIL switches Fig. 1/1: Connecting and display elements on the CPX fieldbus node
1-4
Festo P.BE-CPX-FB32-EN en 1111a
Page 19
1. Installation
Dismantling and mounting The fieldbus node is fitted in an interlinking block of the CPX terminal (see Fig. 1/2). Dismantling
Dismantle the fieldbus node as follows: 1. Loosen the 4 screws in the field bus node with a Torx screwdriver size T10. 2. Pull the fieldbus node carefully and without tilting away from the contact rails of the manifold base.
1 Fieldbus node CPX-FB32
3
2 Interlinking block with contact rails
1
3 Torx T10 screws 2
Fig. 1/2: Dismantling/mounting the fieldbus node
Festo P.BE-CPX-FB32-EN en 1111a
1-5
Page 20
1. Installation
Mounting
Mount the fieldbus node as follows: 1. Place the fieldbus node in the interlocking block. Make sure that the grooves with the power contact terminals on the bottom of the fieldbus node lie above the contact rails. 2. Push the field bus node carefully and without tilting into the interlocking block up to the stop. 3. Only tighten the screws by hand. Place the screws so that the self-cutting threads can be used. 4. Tighten the screws with a Torx screwdriver size T10 with torque 0.9 ... 1.1 Nm.
1-6
Festo P.BE-CPX-FB32-EN en 1111a
Page 21
1. Installation
1.2
Settings of the DIL switches on the fieldbus node In order to set the CPX fieldbus node, you must first remove the cover over the DIL switches.
Caution The CPX fieldbus node contains electrostatically sensitive components. • Do not therefore touch any contacts. • Observe the handling specifications for electrostatically sensitive devices. You will then prevent the electronics in the node from being damaged.
1.2.1
Removing and mounting the cover for the DIL switches In order to set the CPX fieldbus node, you must first remove the cover over the DIL switches.
Removing
1. Switch off the power supply. 2. Unscrew the two mounting screws in the switch cover. 3. Lift off the cover.
Mounting
1. Place the cover carefully on the node. Note • Make sure that the seal is seated correctly. 2. Tighten the two fastening screws at first by hand and then with a torque of 0.4 Nm.
Festo P.BE-CPX-FB32-EN en 1111a
1-7
Page 22
1. Installation
1.2.2
Settingthe DIL switches You can set the following parameters with the DIL switches under the cover (see Fig. 1/3): –
Operating mode
–
Diagnostic mode or number of I/O bytes
–
IP addressing
Procedure: 1. Switch off the power supply. 2. Remove the cover over the DIL switches (section 1.2.1). 3. Carry out the setting as described on the following pages. 4. Mount the cover again (section 1.2.1).
1 DIL switch 1: Operating mode
2 DIL switch 2:
1
Diagnostic mode or number of I/O bytes for Remote Controller
2
3
3 DIL switch 3: IP addressing
Fig. 1/3: DIL switch in the fieldbus node
1-8
Festo P.BE-CPX-FB32-EN en 1111a
Page 23
1. Installation
Setting the operating mode with DIL switch 1 You can set the operating mode of the fieldbus node with switch element 1 of DIL switch 1: Operating mode
Setting DIL switch 1
Remote I/O operating mode All functions of the CPX terminal are controlled directly by the master. An FEC integrated in the CPX terminal works as a passive function module without controller.
DIL 1.1: OFF DIL 1.2: OFF (factory setting)
Operating mode Remote Controller An FEC integrated in the CPX terminal takes control of the I/Os. This operating mode is only useful if an FEC is integrated in the CPX terminal.
DIL 1.1: ON DIL 1.2: OFF
Tab. 1/1: Setting the operating mode with DIL switch 1
Festo P.BE-CPX-FB32-EN en 1111a
1-9
Page 24
1. Installation
Setting the diagnostic mode or the data size for Remote Controller with DIL switch 2 The function of this DIL switch is dependent on the set operating mode of the CPX terminal (see Tab. 1/1): The diagnostic mode is set In the Remote I/O operating mode; the number of I/O bytes is set in the Remote Controller operating mode. Diagnostic mode (Remote I/O operating mode)
Setting DIL switch 2
The I/O diagnostic interface and the status bits are switched off (+ 0 I/O bits)
2.1: OFF 2.2: OFF (default)
The I/O diagnostic interface is switched on 1) (+ 16 I/O bits)
2.1: ON 2.2: OFF
Status bits are switched on (+ +16 E-bits (8 used))
2.1: OFF 2.2: ON
Reserved for future extensions
2.1: ON 2.2: ON
1) The I/O diagnostic interface occupies an additional 16 I/O bits.
Tab. 1/2: Setting the diagnostic mode with DIL switch 2 (Remote I/O operating mode)
1-10
Festo P.BE-CPX-FB32-EN en 1111a