Page 45
2. Commissioning
Sequence of addressing
Description
1.
I/O diagnostic interface 1)
Can be activated by DIL switch. If the interface is activated, it will occupy the first 16 inputs and outputs in the address range.
2.
Analogue modules
Modules with analogue inputs/outputs
3.
Technology modules e.g. CP interface, Front End Controller CPX-FEC
4.
Digital modules
Modules with digital inputs/outputs
1) Depending on the setting, this address range can also be occupied by status bits
(see note above and Tab. 1/2).
Tab. 2/7: Sequence of addressing
Configuration examples Example 1: CPX terminal with MPA1- and MPA2 pneumatic The following diagram shows as an example a CPX terminal with MPA pneumatics and the following setting: – 1
Module no.: 0
Status bits and I/O diagnostic interface deactivated
2
8DI
3 4DO
8DI
2
3
5
6
8O
4O
4O
8DO
8O
1
4
4
1 Fieldbus node CPX-FB32
3 MPA1 pneumatic modules (8 DO each)
2 MPA pneumatic interface
4 MPA2 pneumatic modules (4 DO each)
Fig. 2/1: Example terminal 1: (with MPA1- and MPA2 pneumatic)
Festo P.BE-CPX-FB32-EN en 1111a
2-11
Page 46
2. Commissioning
The following table shows the address assignment for the CPX terminal in Fig. 2/1: Module no.
Module
Input address
Output address
0
Fieldbus node CPX-FB32
–
–
1
Digital 8-input module CPX-8DE
I0 ... I7
–
2
Digital 4-output module CPX-4DA
–
O0 ... O7*)
3
MPA1 pneumatic module (8 DO)
–
O8 ... O15
4
MPA1 pneumatic module (8 DO)
–
O16 ... O23
5
MPA2 pneumatic module (4DO)
–
O24 ... O31*)
6
MPA2 pneumatic module (4DO)
–
O32 ... O39*)
*) 8 bits occupied, 4 bits used
Tab. 2/8: Addressing the example terminal 1 (see Fig. 2/1) If modular EDS is used, the addresses will be assigned in bytes. In the example above, the output addresses therefore change as from modules 2, 5 and 6.
2-12
Festo P.BE-CPX-FB32-EN en 1111a
Page 47
2. Commissioning
Example 2: CPX terminal with CP interface The address assignment for this CPX terminal can be found on the next page in Tab. 2/9. The settings are: – Module no.:
1
0 8DI
Status bits and I/O diagnostic interface deactivated 2
3 4DO
4 8DI
5
6
8O
8O
8DO
1 3 2 4 5 6 1 Fieldbus node CPX-FB32
4 Sensor
2 CPV valve terminal (16DO) on the CP
5 Cylinder interface (string 1)
3 CP input module (16 DI)
6 CP output module (16DO) on the CP interface (string 4)
Fig. 2/2: Example terminal 2 (with CP interface)
Festo P.BE-CPX-FB32-EN en 1111a
2-13
Page 48
2. Commissioning
Module no.
Module
Input address
Output address
0
Fieldbus node CPX-FB32
–
–
1
Digital 8-input module CPX-8DE
I32 ... I39
–
2
Digital 4-output module CPX-4DA
–
O128 ... O135*)
3
CP interface CP-I, here: 4 byte I, 16 byte O
I0 ... I32
O0 ... O127
4
Digital multi I/O module CPX-8DE-8DA
I40 ... I47
O136 ... O143
5
MPA1 pneumatic module (8 DO)
–
O144 ... O151
6
MPA1 pneumatic module (8 DO)
–
O152 ... O159
*) 8 bits occupied, 4 bits used
Tab. 2/9: Addressing the example terminal 2 (see Fig. 2/2)
2-14
Festo P.BE-CPX-FB32-EN en 1111a
Page 49
2. Commissioning
Example 3: CPX terminal with analogue module and VTSA pneumatic The address assignment for this CPX terminal can be found on the next page in Tab. 2/10. The settings are:
Module no.: 0
1 8DI
–
Status bits activated and I/O diagnostic interface deactivated
–
On the pneumatic interface set with DIL switch to 1 ... 8 valve coils (8 DO).
2
3
8DI
4DO
4
5
8DI 8DO
6
2AO
8O
1 1 Fieldbus node CPX-FB32
2
3
3 VTSA pneumatics (type 44)
(with DIL 3.2 at ON for status bits)
2 Pneumatic interface (set with DIL switch to 1 ... 8 valve coils) Fig. 2/3: Example terminal 3 (with analogue module and VTSA pneumatics)
Festo P.BE-CPX-FB32-EN en 1111a
2-15
Page 50
2. Commissioning
Module no.
Module
Input address
Output address
0
Fieldbus node CPX-FB32 with status bits
I0 ... I15 1)
–
1
Digital 8-input module CPX-8DE
I16 ... I23
–
2
Digital 8-input module CPX-8DE
I24 ... I31
–
3
Digital 4-output module CPX-4DA
–
O32 ... O39 2)
4
Digital multi I/O module CPX-8DE-8DA
I32 ... I39
O40 ... O47
5
Analogue 2-output module CPX-2AA
–
O0 ... O31
6
VTSA pneumatic interface set with DIL switch to 1 ... 8 valve coils
–
O48 ... O55
1) 16 bits occupied, 8 bits used 2) 8 bits occupied, 4 bits used
Tab. 2/10: Addressing the example terminal 3 (see Fig. 2/3)
2-16
Festo P.BE-CPX-FB32-EN en 1111a
Page 51
2. Commissioning
2.1.3
Address assignment after extension/conversion A speciality of the CPX terminal is its flexibility. If the demands placed on the machine change, the equipment fitted on the CPX terminal can also be modified.
Caution If the CPX terminal is extended or converted at a later stage, the input/output addresses may be shifted. This applies in the following cases: – Additional modules are inserted between existing modules. – Existing modules are removed or replaced by other modules which have more or fewer input/output addresses. – Interlinking blocks (CPA) or pneumatic manifold blocks (Midi/Maxi) for single-solenoid valves are replaced by interlinking blocks/manifold blocks for double-solenoid valves or vice versa (see Pneumatics description). – Additional interlinking blocks (CPA) of manifold blocks (Midi/Maxi) are inserted between existing ones. – Status bits or the I/O diagnostic interface are activated/deactivated.
Festo P.BE-CPX-FB32-EN en 1111a
2-17
Page 52
2. Commissioning
Example terminal 3 modified
The next diagram shows with terminal 3 as an example (see Fig. 2/3) the effects of modifications to the address assignment. The following has been changed:
Module no.: 0
–
The status bits have been deactivated.
–
In the case of module no. 1 an 8-input module has been replaced by a 16-input module.
–
The pneumatic interface has been set to 16 O in order to reserve addresses for an extension to the pneumatics.
1
2
3
16DI
8DI
4DO
4
5
8DI 8DO
6
2AO
16 O
1
2
1 Modified status bits deactivated 2 Modified: 8DI module replaced by
3 3 Modified: Pneumatic interface (set with DIL switch to 1 ... 16 valve coils)
16DI module Fig. 2/4: Example terminal 3 after extension/modification(compare with Fig. 2/3)
2-18
Festo P.BE-CPX-FB32-EN en 1111a
Page 53
2. Commissioning
Module no.
Module
Input address
Output address
0
Fieldbus node CPX-FB32 with deactivated status bits
Dependent on DIL switch settings (see Tab. 1/2)
1
Digital 16-input module CPX-16DE
I0 ... I15
–
2
Digital 8-input module CPX-8DE
I16 ... I23
–
3
Digital 4-output module CPX-4DA
–
O32 ... O39 1)
4
Digital multi I/O module CPX-8DE-8DA
I24 ... I31
O40 ... O47
5
Analogue 2-output module CPX-2AA
–
O0 ... O31
6
VTSA pneumatic interface set with DIL switch to 1 ... 16 valve coils
–
O48 ... O63 bold = modified module 1) 8 bits occupied, 4 bits used
Tab. 2/11: Addressing the example terminal 3 after extension/modification (see Fig. 2/4)
Festo P.BE-CPX-FB32-EN en 1111a
2-19
Page 54
2. Commissioning
2.2
Bus configuration General instructions on commissioning Configuration of the CPX terminal demands a very accurate procedure, as different configuration specifications are sometimes necessary for each station on the EtherNet/IP due to the modular structure. Note here the specifications in the sections which follow.
2.2.1 Registering station properties in the configuration program When you place a new EtherNet/IP station into operation for the first time, you must inform your configuration program about certain features of the station. The properties of the various stations are managed by the configuration program usually in a list or library, e.g. “EDS library” (EDS for electronic data sheets). The following options are available for expanding an EDS library: –
Installing EDS files The EDS file is used only for identification of the CPX-FB32 in the network.
–
Enter station properties manually (only by using the parameter settings set at the factory).
Source of supply for EDS files Source of supply
Current EDS files, icon files and information on the EDS files can be found at the following internet address: –
2-20 www.festo.com/fieldbus