CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Commissioning, pages 55 to 64

Pages 55 to 64 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-FB-32

Page 55

2. Commissioning

Installing EDS files You will require the following files for the CPX terminal: File type Filename

Language

Description

EDS cpx_fb32.eds

English

Provides the communication adapter in the configuration program.

ICO cpx_fb32.ico

–

Icon file for representing the CPX terminal or mode in the configuration program.

Tab. 2/12: Configuration files (EDS) for CPX terminal for EtherNet/IP

Installing EDS files

•

Install the files with your configuration program.

Icon files

Depending on the configuration program used, you can assign icon files (.ico format) to the CPX terminal or the CPX modules. The CPX terminal or the modules will then be represented accordingly in the configuration program. Instructions on installing the EDS files and the icon files can be found in the documentation for your configuration program.

Festo P.BE-CPX-FB32-EN en 1111a

2-21

Page 56

2. Commissioning

Entering station properties manually When an EDS file is installed, the following information about the EtherNet/IP station is added to the EDS library. This information can also be entered manually if the CPX terminal is to be operated with the parameter settings preset at the factory. Information

Description

Vendor name

Festo Corporation

Vendor ID

26D

1AH

Device type

12D

CH

Product code (depends on operating mode) – Remote I/O – Remote Controller

13002D 13003D

32CAH 32CBH

Major Revision

21)

Input size / output size

Depends on CPX equipment

Product name

CPX-FB32

Catalogue number

541302

Extended Ethernet/IP station features Request Packet Interval (RPI) Connections: – Total of all connections – Exclusive Owner – Input only – Listen only

≥ 10 ms Max. 32 Max. 1 Max. 32 Max. 31 (There has to be simultaneously at least 1 Excl.Owner or input only connection)

1) From CPX-FB32 Revision 17

Tab. 2/13: Station features

2-22

Festo P.BE-CPX-FB32-EN en 1111a

Page 57

2. Commissioning

Note From CPX-FB32 Revision 17, the “Major Revision” was raised from 1 to 2. For “Major Revision” 2, a new EDS file must be used or the corresponding setting made in the controller. Nodes with “Major Revision” 2 are downward compatible with “Major Revision” 1

The EDS file suitable to your CPX-FB32 can be determined and downloaded at www.festo.com in the Festo Support Portal.

Note If the station features are entered manually, individual parameterisation of the CPX terminal is not possible. When the EDS library has been expanded, the CPX terminal is entered in the station list as a possible EtherNet/IP station. It can now be added to a network.

2.2.2 Overview of configuration on the EtherNet/IP When the station features have been configured (e.g. by installation of the EDS file), the following steps are required for parameterisation (depending on the configuration program): 1. Install your CPX terminal and set the network addressing according to section 1.3.3. 2. Create a connection to an EtherNet/IP station. With RSLogix, use for this the profile “Generic Ethernet Device”.

Festo P.BE-CPX-FB32-EN en 1111a

2-23

Page 58

2. Commissioning

3. Assign the instances of the Assembly Object: Instance 101: Inputs Instance 100: Outputs Instance 102: Configuration data, if used (“Configuration Assembly”) 4. Select the data format SINT. 5. Enter the IP address, if necessary.

2.2.3 Set up a listen-only connection When the station features have been configured (e.g. by installation of the EDS file), the following steps are required for parameterisation (depending on the configuration program): 1. Install your CPX terminal and set the network addressing according to section 1.3.3. 2. Create a connection to an EtherNet/IP station. With RSLogix, use for this the profile “Generic Ethernet Device”. 3. Assign the instances of the Assembly Object: Instance 101: Inputs Instance 1 Outputs Instance 102: Configuration data, if used (“Configuration Assembly”) 4. Select the data format Input Data – SINT. 5. Enter the IP address, if necessary.

2-24

Festo P.BE-CPX-FB32-EN en 1111a

Page 59

2. Commissioning

2.2.4 Configuration with RSLogix5000 With the help of the CPX Festo Maintenance Tool (CPX-FMT), it is also possible to export the configuration of a CPX terminal with EtherNet/IP bus node into an RSLogix5000 project (see section 2.3.2). 1. Click in RSLogix5000 in the “I/O Configuration” on the right on the Ethernet/IP bridge and select “New Module”:

Festo P.BE-CPX-FB32-EN en 1111a

2-25

Page 60

2. Commissioning

1

1 CPX-FB32 – adding as new module in Ethernet/IP Fig. 2/5: Configuration with RSLogix5000 2. Select “ETHERNET MODULE – Generic Ethernet Module” in the window “Select Module Type” and confirm with “OK”:

2-26

Festo P.BE-CPX-FB32-EN en 1111a

Page 61

2. Commissioning

Fig. 2/6: CPX-FB32 – adding as generic module 3. Enter in the window “Module Properties” (Fig. 2/7): – the name for the fieldbus node (freely selectable)

–

Instances for inputs: 101 outputs: 100

–

Instance for Configuration Assembly: 102 The standard setting is “0” (Configuration Assembly not used). Operating mode Remote I/O: If you undertake parameterisation via the Configuration Assembly: Enter the total of the assigned bytes (see section 2.3.1). Operating mode Remote Controller: Leave the standard setting “0” unchanged.

–

Data format SINT

–

IP address

Confirm the entry. Festo P.BE-CPX-FB32-EN en 1111a

2-27

Page 62

2. Commissioning

1 Name

1

(freely selectable)

2

2 Assembly instances

3 Size of the “Configuration Assembly” (see explanation in the text)

4 IP address 5 Data format

5

4

3

Fig. 2/7: Enter values for “Module Properties”

Note For the configuration with RSLogix5000 at least one input must be assigned: • Enter at least 1 for the instances for inputs (2 in Fig. 2/7) or • if your CPX terminal does not contain any input modules, activate the status bits with the DIL switches (see Tab. 1/2).

2-28

Festo P.BE-CPX-FB32-EN en 1111a

Page 63

2. Commissioning

2.3

Parameterisation Caution A different parameterisation will result in different characteristics. Check especially when replacing CPX terminals to see which settings are necessary and make sure that these are restored (e.g. in the start-up phase by the higher-order PLC/IPC).

The CPX terminal is supplied from the factory with preset parameters. The system reaction of the CPX terminal can be adapted to the relevant application. You can set the reaction of the CPX terminal as well as the reaction of individual modules and channels through parameterisation. A distinction is made between the following parameterisations: –

System parameterisation, e.g.: switching off of malfunction messages, setting of reaction times, etc.

–

Module parameterisation (module- and channel-specific), e.g.: monitoring, settings in case of error, settings for Forcing.

–

Parameterisation of the diagnostic memory.

A detailed description of the individual parameters as well as fundamentals for application can be found in the CPX system description (P.BE-CPX-SYS-...) The module parameters that are available for the various modules can be found in the description of the relevant module (e.g. Description of the CPX pneumatic interfaces and CPX I/O modules (P.BE-CPX-EA-...).

Festo P.BE-CPX-FB32-EN en 1111a

2-29

Page 64

2. Commissioning

Requirements for parameterisation You can influence the start characteristics with the system parameter “System start”. If possible, select the setting “System start with default parameterisation and current CPX expansion”. The desired parameterisation can then be carried out in the initialisation phase or user-controlled (depending on the fieldbus used).

Note The CPX terminal can only be parameterised if the system parameter “System start” has the setting “System start with default parameterisation and current CPX expansion”. If the M LED lights up permanently after the system start, then “System start with saved parameterisation and saved CPX expansion” is set. In this case, no other parameterisation can be carried out.

Caution In the case of CPX terminals on which the M LED lights up permanently, parameterisation will not be restored automatically by the higher-order system if the CPX terminal is replaced during servicing. In these cases, check before replacement to see which settings are required and carry out these settings.

2-30

Festo P.BE-CPX-FB32-EN en 1111a