The text of a manual · part 9 of 18
CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Commissioning, pages 65 to 74
Pages 65 to 74 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Festo CPX-FB-32
Page 65
2. Commissioning
2.3.1
Methods of parameterisation You can parameterise a CPX terminal with CPX-FB32 various methods. The following table and the following sections provide an overview of the methods.
Methods and description
Advantages
Disadvantages
1. Parameterisation via configuration data (“Configuration Assembly”) Depending on the control software, parameters can be entered manually or conveniently via the menus.
– Parameters are loaded automatically after Power On and are therefore retained if the CPX terminal is replaced
– Parameters must be entered individually 1)
2a. Parameterisation via software 2b. Parameterisation with the Handheld Parameterisation is carried out with entries via the menus
– User-friendly parameterisation via the menus (plain text)
– Parameterisation is saved locally in the CPX terminal and is lost if the terminal is replaced. 1)
3. Parameterisation via the PLC application program Parameterisation is carried out within the user program in the PLC/IPC via “Explicit Message”.
– Parameterisation is saved in the PLC – Parameters are loaded automatically after Power On and are therefore retained if the CPX terminal is replaced
– Explicit Message programming required
4. Parameterisation with EDS files via configuration program The parameters are set via the configuration program and transmitted directly to the EtherNet/IP station.
– Fast, simple parameterisation during commissioning for testing the parameters
– Not available with all Ethernet/IP masters – Parameterisation is saved locally in the CPX terminal and is lost if the terminal is replaced. 2)
1) With the help of the CPX-FMT and the function L5K Export, the complete configuration of a
CPX terminal for RSLogix5000 can also be prepared automatically. 2) The current parameter settings can be copied with the help of the Handheld.
Tab. 2/14: Methods of parameterisation
Festo P.BE-CPX-FB32-EN en 1111a
2-31
Page 66
2. Commissioning
2.3.2
Parameterisation via Configuration Assembly (method 1) With parameterisation via the Configuration Assembly, the parameters must be entered individually in the control program or generated via software. Parameterisation via the Configuration Assembly is available only for revision statuses later than Rev. 1.10. Further information on creation of the Configuration Assembly can be found at www.festo.com/fieldbus.
Simplified parameterisation in RSLogix5000 With the help of the CPX Festo Maintenance Tool (CPX-FMT), it is possible to export the configuration of a CPX terminal with EtherNet/IP bus node into an RSLogix5000 project. The CPX-FMT is available in the internet at www.festo.com/fieldbus. 1. Establish a connection between CPX-FMT and the CPX terminal through the Ethernet. 2. Manually configure the CPX terminal with the CPX-FMT or use the online function to download the configuration automatically. 3. Change the parameters to the extent needed (all parameters can also still be changed after export/import into RSLogix).
2-32
Festo P.BE-CPX-FB32-EN en 1111a
Page 67
2. Commissioning
4. Export the configuration via File } Export } RSLogix (.L5K) and select a storage location for the L5K file.
Fig. 2/8: Export of the L5K file 5. Open the L5K file as a new project in RSLogix5000. This project contains the just configured CPX terminal.
Festo P.BE-CPX-FB32-EN en 1111a
2-33
Page 68
2. Commissioning
6. To integrate the CPX terminal into existing RSLogix projects, copy the module with a right click } Copy.
Fig. 2/9: Copying the CPX module
2-34
Festo P.BE-CPX-FB32-EN en 1111a
Page 69
2. Commissioning
7. Insert the module with a right click } Paste onto the Ethernet connection in the existing RSLogix project.
Fig. 2/10: Inserting the CPX module All necessary settings from CPX-FMT are taken over into the RSLogix project. This includes, among others, the I/O data lengths, the IP configuration and all module and system parameters.
Festo P.BE-CPX-FB32-EN en 1111a
2-35
Page 70
2. Commissioning
2.3.3
Parameterisation via software (method 2a) With the CPX Maintenance Tool (CPX-FMT), you can parameterise the CPX terminal with a PC via Ethernet. The CPX-FMT is available in the internet at: –
2.3.4 www.festo.com/fieldbus.
Parameterisation with the Handheld (method 2b) The Handheld offers menu-orientated access to parameterisation without configuration software. Information on operating the Handheld can be found in the relevant description.
Note The last parameterisation received in the CPX terminal is always valid. The CPX terminal can only be parameterised if the system parameter “System start” has the setting “System start with default parameterisation and current CPX expansion”. In this case, the standard parameter settings are valid in the CPX terminal after Power On.
Note If the system parameter “System start” has the setting “System start with saved parameterisation and saved CPX expansion”, modified parameter settings in the CPX terminal will become valid immediately after Power On.
2-36
Festo P.BE-CPX-FB32-EN en 1111a
Page 71
2. Commissioning
2.3.5
Parameterisation via the PLC user program (method 3) Program-controlled access to parameters is made via the “Explicit Message” programming. The addresses of the EtherNet/IP Object Model required for this can be found in Appendix B. Information on programming this data transmission can be found in the manual for your controller. In order to address the CPX terminal with FB32 you will require the following Object descriptions: Detailed Object descriptions can be found in Appendix B.1.
Object classes
Instances (dec.)
Attributes (dec.)
Name
4d
100 ... 102
-
Assembly Object
102d
1 ... 48
1, 2
Modification digital inputs, Object
103d
1 ... 48
1 ... 6
Modification digital outputs, Object
104d
1 ... 48
1, 2
Modification analogue inputs, Object
105d
1 ... 48
1 ... 6
Modification analogue outputs, Object
106d
1 ... 48
1, 2
Modification input words of technology module, Object
107d
1 ... 48
1 ... 6
Modification output words of technology module, Object
132d
1
1 ... 37
System Object (Global System Object)
133d
1
1 ... 3
Status and Diagnostic Object
134d
1 ... 40
1 ... 12
Diagnostic Trace Object
135d
1
1 ... 13
Diagnostic Trace Status Object
Tab. 2/15: Overview of Object classes for EtherNet/IP (operating mode Remote I/O)
Festo P.BE-CPX-FB32-EN en 1111a
2-37
Page 72
2. Commissioning
Object classes
Instances (dec.)
Attributes (dec.)
Name
Type
136d
1
1, 2
Slave Size Object (only Remote Controller)
SINT
Tab. 2/16: Object class for EtherNet/IP in operating mode Remote Controller
2.3.6
Parameterisation with EDS files (method 4) This method of parameterisation is only possible if your configuration program supports parameterisation via EDS. The EDS files of the CPX terminal must be contained in the EDS library. The CPX-EDS Version 1.2 is used only for identification of the CPX-FB32 in the network.
2-38
Festo P.BE-CPX-FB32-EN en 1111a
Page 73
2. Commissioning
2.4
Notes on parameters for Idle mode and Fault mode Reaction of the outputs in Idle mode or Fault mode The Idle mode is assumed by the stations after request by the master. The Fault mode defines the status the relevant channel is to assume in the event of fieldbus communication faults. In this status, the following applies: –
Inputs are transmitted.
–
Output channels of the stations are no longer updated.
In the Idle mode or Fault mode, outputs can assume one of the following states: Digital outputs/valves
Analogue outputs
Freeze current status
Freeze current status
Reset output
Desired analogue value
Set output
Tab. 2/17: Possible states in the Idle or Fault mode You can determine the status to be assumed for each output channel (output or solenoid coil) separately. The standard setting is “Reset of the output channel”. Further information can be found in the CPX system description.
Festo P.BE-CPX-FB32-EN en 1111a
2-39
Page 74
2. Commissioning
2.5
2-40
Check list for commissioning the CPX terminal with FB32 •
Please observe the general commissioning instructions in the CPX system description.
•
Check the DIL switch settings and the network configuration before using and replacing CPX terminals.
•
Check the configured address range. If necessary, test the I/Os.
•
Check the address assignment of the I/Os on the CPX terminal. For this purpose you can, if necessary, force the I/Os (see CPX system description).
•
Make sure that the desired parameterisation of the CPX terminal in the start-up phase or after fieldbus interruptions is restored by the plug-in module. This is to ensure that if the CPX terminal is replaced, the new terminal will also be operated with the desired parameter settings.
•
Use spot checks if necessary to check the parameterisation, e.g. with the configuration program or with the Handheld.
Festo P.BE-CPX-FB32-EN en 1111a