CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP: Diagnostics, pages 75 to 84

Pages 75 to 84 of 146, from CPX terminal Manual Electronics: CPX field bus node Type CPX-FB32, Fieldbus protocol EtherNet/IP

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-FB-32

Page 75

Diagnostics

Chapter 3

Diagnostics

Festo P.BE-CPX-FB32-EN en 1111a

3-1

Page 76

3. Diagnostics

Table of contents

3.

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1 3.2

Overview of diagnostics options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnostics via LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.1 CPX-specific LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnostics via status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnosis via I/O diagnostic interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnosis via EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-3 3-5 3-7 3-14 3-15 3-16 3-19

3.3 3.4 3.5 3.6

3-2

Festo P.BE-CPX-FB32-EN en 1111a

Page 77

3. Diagnostics

3.1

Overview of diagnostics options The CPX terminal provides extensive and user-friendly possibilities for diagnostics and error handling. The following possibilities are available depending on the configuration:

Diagnostics option

Brief description

Advantages

Detailed description

LED display

The LEDs show directly configuration errors, hardware errors, bus errors, etc.

Fast “on-the-spot” recognition of errors

Section 3.2

Status bits

Internal inputs that supply coded common diagnostic messages.

Fast access to error messages, irrespective of the module and master.

Section 3.3 and CPX system description

I/O diagnostic interface

The I/O diagnostic interface is a bus-independent diagnostic interface at I/O level which permits access to internal data of the CPX terminal (16 inputs and 16 outputs).

Detailed error recognition irrespective of the fieldbus type used.

Section 3.4 and CPX system manual

Diagnostics via EtherNet/ IP

Access to all system data of the CPX terminal via the fieldbus.

Detailed module-related and channel-related error recognition as well as access to the diagnostic memory in the online mode of the programming/configuration software and in the PLC user program.

Appendix B (Ethernet/IP Objects)

Diagnostics via the Handheld

Diagnostic information can be shown on the CPX Handheld in a user-friendly manner by means of menus.

Fast “on site” error detection

Description for the Handheld

Tab. 3/1: Diagnostics options

Festo P.BE-CPX-FB32-EN en 1111a

3-3

Page 78

3. Diagnostics

Note Observe that the diagnostic information displayed depends on the parameterisation of the CPX terminal.

3-4

Festo P.BE-CPX-FB32-EN en 1111a

Page 79

3. Diagnostics

3.2

Diagnostics via LEDs LEDs for diagnosing the CPX terminal are available on the fieldbus node as well as on the individual modules. The meaning of the LEDs on the electric modules can be found in the description for the relevant module.

LEDs on the fieldbus node CPX-FB32 The LEDs on the cover indicate the operating status of the CPX fieldbus node.

1 CPX-specific LEDs PS: Power System PL: Power Load SF: System Fault

MS

PS

NS

PL

IO

SF

TP

M

MS

PS

NS

PL

IO

SF

TP

M

1

M: Modify

2 EtherNet/ IP-specific LEDs MS: Module Status NS: Network Status

2

IO: I/O Status TP: Link/Traffic Fig. 3/1: LEDs on the CPX fieldbus node

Festo P.BE-CPX-FB32-EN en 1111a

3-5

Page 80

3. Diagnostics

The LEDs are shown in their various states as follows: lit;

flashing;

off;

Normal operating status In normal operating status the following LEDs light up green. The SF LED does not light up. The M-LED lights up only with the setting “System start with stored parameterisation and stored CPX expansion” (see function number 4402). LED display

MS

PS

NS

PL

IO

SF

TP

M

Operating status The following LEDs light green: – PS – PL – MS – NS – IO 1) – TP 2) The SF LED does not light up. – SF M LED see function number 4402

Standard

1) Lights up only when inputs/outputs are controlled via

EtherNet/IP. 2) Steady light: Ready for data transmission

Flashing: Data transmission ongoing

Tab. 3/2: Normal operating status

3-6

Festo P.BE-CPX-FB32-EN en 1111a

Page 81

3. Diagnostics

3.2.1

CPX-specific LEDs

PS (power system) – power sensor/logic supply LED (green)

Sequence ON OFF

LED lights up ON OFF

LED flashes ON OFF

ON OFF

LED is off

Status

Meaning / error handling

No error. Operating voltage/sensor supply applied

–

Operating voltage/sensor supply outside the tolerance range

Eliminate undervoltage

Internal fuse for the operating voltage/sensor supply has responded.

1. Eliminate short circuit/overload on module side. 2. Depends on the parameterisation of the module (module parameter): • The sensor supply voltage will be switched on again automatically after the short circuit has been eliminated (default) • Power Off/On is necessary

The operating voltage/ sensor supply is not applied

Check the operating voltage connection of the electronics

PL (power load) – power load supply (outputs/valves) LED (green)

Sequence

Status

Meaning / error handling

ON

No error. Load voltage applied

None

Load voltage at the system supply or additional supply outside the tolerance range

Eliminate undervoltage

OFF

LED lights up ON OFF

LED flashes

Festo P.BE-CPX-FB32-EN en 1111a

3-7

Page 82

3. Diagnostics

SF (system failure) – system fault LED (red)

Sequence 1)

Status

Meaning / error handling

ON

No error.

–

Simple error/information (error class 1)

See description of error numbers in the CPX system manual

OFF

LED is off ON OFF

LED flashes

ON OFF

Error (error class 2)

LED flashes

ON OFF

Serious error (error class 3)

LED flashes

1) The System Failure LED flashes dependent on the applicable error class.

Error class 1 (simple error): Error class 2 (error): Error class 3 (serious error):

3-8

1 * flashing, pause time 2 * flashing, pause time 3 * flashing, pause time

Festo P.BE-CPX-FB32-EN en 1111a

Page 83

3. Diagnostics

M (modify) – parameterisation modified or forcing active LED (yellow)

Sequence

Status

Meaning / error handling

ON

System start with default parameterisation (factory setting) and current CPX expansion set; external parameterisation is possible (pre-setting)

None

System start with saved parameterisation and saved CPX expansion has been set; Parameters and CPX expansion are saved remanently; external parameterisation is blocked 1)

Be careful when replacing CPX valve terminals with saved parameterisation. With these CPX valve terminals, parameterisation is not carried out automatically by the higher-order PLC/IPC when the terminal is replaced. In these cases, check which settings are required before the replacement and make these settings if necessary.

– Force is active 1)

– The Force function is enabled (see system parameter Force mode; function no. 4402). – CPX-FB32 Restart (Power OFF/ON), see also section 1.3.3)

OFF

LED is off

ON OFF

LED lights up

ON OFF

LED flashes

– Network settings have been modified

1) The display of the Force function (LED flashes) has precedence over the display of the setting for System start (LED lights up).

Festo P.BE-CPX-FB32-EN en 1111a

3-9

Page 84

3. Diagnostics

EtherNet/IP-specific LEDs MS – module status LED

Sequence

Status

Meaning / error handling

ON

Logic supply for bus interface not applied

• Check logic supply

Operating status normal

None

CPX terminal must be placed in operation as the configuration is missing, incomplete or incorrect.

Carry out, complete or correct the configuration

Error can be rectified

Complete or correct the configuration

Error cannot be rectified

Check CPX expansion as well as other LEDs and, if necessary, request service

CPX terminal is in self-test

None

OFF

Is off ON

Lights up green

OFF

ON OFF

Flashes green ON OFF

Flashes red ON OFF

Lights up red ON OFF

Flashes red-green

3-10