Summary
What is in it
Festo catalog pages for Fieldbus Direct, which builds the fieldbus node straight into the electrical actuation of a CPV valve terminal. It describes the key features, switch module, CP string extension and diagnostics, gives an overview of compatible valve terminals, CP/CPI I/O modules and supported fieldbus systems, then technical data and accessories for the CPV-DI01 and CPV-DI02-8 fieldbus nodes, including the FBA-2-M12-5POL-RK Micro Style 2xM12 bus connection.
Its parts
- Key features
- Peripherals overview
- Technical data, Fieldbus node CPV-DI01
- Technical data, Fieldbus node CPV-DI02-8
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Festo catalog pages (2018/06) for the Fieldbus Direct system, covering the CPV-DI01 and CPV-DI02-8 fieldbus nodes for CPV valve terminals and their accessories. The FBA-2-M12-5POL appears as the 2xM12 bus connection adapter for the CPV-DI02-8 node. The pages give technical data, connection details and ordering data.
- What it is
- M12 adapter for the bus connection of the CPV-DI02-8 fieldbus node, part number 525632 p. 19
- Connector
- Plug connector 2xM12, installed with IP65 protection; the alternative to the 9-pin Sub-D socket p. 16
- Fieldbus
- CPV-DI02-8: PROFIBUS DP, 9.6 to 12,000 kbps with automatic detection, addresses 1 to 125 set with a switch module p. 17
- For CPV-DI01
- CPV-DI01 nodes use the FBA-2-M12-5POL-RK, part number 533118, for a 2xM12 bus connection p. 15
- CPV-DI02-8 node
- CPV-DI02-8: drives a CPV valve terminal with 8 valve slices and 16 solenoid coils; 32 inputs and 32 outputs via CP string extension p. 16, 17
- Node supply
- CPV-DI01 and CPV-DI02-8: 24 V DC, reverse polarity protected, 20.4 to 26.4 V; max. 100 mA plus sensor supply p. 13, 17
- Power connector
- CPV Direct: operating and load voltage through a 4-pin M12 plug (A-coded) p. 11, 18
- Sensor supply
- Up to 500 mA via the CP string to the connected input module p. 11
- CP string extension
- Up to 10 metres; CP cables from 0.5 to 8 metres p. 2, 8
- Switch module
- CPV10/14/18-GE-DI-SM, part number 165814, sets bus parameters and device configuration p. 19
- Other bus connectors
- CPV-DI02-8: FBS-SUB-9-GS-DP-B Sub-D socket (532216); FBA-1-SL-5POL open style adapter (525634); FBSD-KL-2x5POL terminal strip (525635) p. 19
- Protection class
- CPV-DI02-8: IP20 with the 5-pin screw terminal strip, IP65 with Sub-D or M12x1 socket/plug p. 17
- Temperature
- Ambient -5 to +50 °C; storage -20 to +70 °C p. 17
- Diagnostics
- Short circuit/overload of outputs; undervoltage of valves, outputs and sensor supply; missing module on the CP string p. 17
What this sheet walks you through
- Choosing a bus connection for the CPV-DI02-8 node p. 16
- Wiring the operating and load voltage supply p. 11
- Adding valve terminals and I/O modules through the CP string extension p. 2, 3
- Reading the diagnostic LEDs and fieldbus diagnostics p. 4
- Comparing the supported fieldbus systems p. 9
- Fieldbus pin allocation for the CPV-DI01 and CPV-DI02-8 p. 14, 18
- Ordering nodes, connectors, cables and manuals p. 15, 19
- Choosing CP input and output modules p. 6, 7, 8
Good to know
- The valve load supply is fed separately from the electronics supply. p. 11
- The Sub-D bus connector plug is IP65 from Festo but IP20 from other makers. p. 16
- The CP string extension may be no longer than 10 metres. p. 3
Questions this sheet answers
What is the Festo FBA-2-M12-5POL?
It is the M12 adapter, part number 525632, that gives the CPV-DI02-8 fieldbus node a 2xM12 bus connection instead of the Sub-D socket. p. 16, 19
Which M12 adapter fits the CPV-DI01 node?
The ordering data for the CPV-DI01 lists the FBA-2-M12-5POL-RK, part number 533118. p. 15
What supply voltage does a CPV Direct fieldbus node need?
24 V DC, reverse polarity protected, within 20.4 to 26.4 V, fed through a 4-pin M12 plug. p. 11, 17
Which fieldbus protocols does the CPV-DI01 support?
PROFIBUS DP, Moeller SUCOnet K, ABB CS31 and Festo fieldbus, selected with DIL switches. p. 12
How long can the CP string extension be?
Up to 10 metres, so extension modules can be mounted on site. p. 2
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file