Fieldbus Direct Key features

The system Extremely compact and spacesaving design Low-cost solution for the connection of a small number of valves to a fieldbus Extremely safe, protection class up to IP65 depending on the series

The Fieldbus Direct product range is the most compact way of connecting valves to a fieldbus. The fieldbus node is directly integrated in the electrical actuation of the valve terminal and therefore takes up only a minimal amount of space.

The Fieldbus Direct system comprises the following valve terminal series: CPV

Fieldbus Direct is a system for the connection of one valve terminal. The most important systems are supported.

The CP string extension option allows the functions and components of the CPI installation system to be used. The optional string extension allows additional valve terminals and I/O modules to be connected to the fieldbus node of the Fieldbus Direct system.

The maximum length of the CP string extension is 10 metres, which means that the extension modules can be mounted directly on-site. All of the required electrical signals are transmitted via the CPI cable, which means that no further installation is needed on the extension module.

The I/O modules and cables for the CP string extension are ordered using the order code for the CPI installation system.

Online via: è www.festo.com

Valve terminal configurator A valve terminal configurator is avail­ able online to help you select a suit­ able Fieldbus Direct valve terminal. Like all valve terminals, Fieldbus Di­ rect is ordered using an ident. code.

This ident. code specifies the valve functions, the number of valves, va­ cant positions as well as the addi­ tional functions and the type of compressed air supply.

2

è Internet: www.festo.com/catalogue/...

As is the case with all Festo products, all Fieldbus Direct valve terminals are supplied: fully pre-assembled fitted with fittings on request tested for electrical function tested for pneumatic function securely packaged manuals can be downloaded free of charge

Subject to change – 2018/06

Page 3

Fieldbus Direct Key features Switch module for CPV Direct The bus parameters and the device configuration of CPV Direct are set using the removable switch module.

The integrated DIL switches are easy to set and check, even if the mounting position is difficult to access.

In the case of the valve terminals with the CP system according to Specifica­ tion “B”, the DIL switches for para­ meterisation/configuration are integrated in the basic electrical unit.

The maximum length of the CP string extension is 10 metres, which means that the extension modules can be mounted directly on-site. All of the required electrical signals are trans­ mitted via the CP cable, which in turn means that no further installation is needed on the extension module.

The CP string interface offers: 16 input signals 16 output signals for output modules 24 V DC or solenoid coils Logic and sensor supply for the input modules Load voltage supply for the valve terminals Logic supply for the output modules

The variant according to Specification “B” supports the connection of 32 inputs 32 outputs 24 V DC or solenoid coils. It goes without saying that the CP modules without Specification “B” can also be connected to the CPI string extension of valve terminals.

CP string extension The optional string extension allows an additional valve terminal and I/O modules to be connected to the field­ bus nodes of the Fieldbus Direct sys­ tem. A CP string of the CP installation system is integrated in the fieldbus node as an extension. Different input and output modules as well as CPV, MPA-S and CPV-SC valve terminals can be connected. CPV Direct with fieldbus node Fieldbus

8 valve slices 16 solenoid coils 16 3/2-way valves

CPV Direct with input module 24 V DC for detecting the cylinder end positions Fieldbus

2018/06 – Subject to change

8 valve slices with up to 16 solenoid coils 16 inputs M8 or M12, each with sensor supply

è Internet: www.festo.com/catalogue/...

Variant according to Specification “B” 32 input signals 32 output signals/solenoid coils

3

Page 4

Fieldbus Direct Key features – Bus connection Fieldbus Direct system diagnostics The fieldbus node together with the modules connected to the CP string offer several diagnostic options.

Diagnostic LEDs on the Fieldbus Direct node The fieldbus-specific LEDs display the communication status and the fieldbus function. Further LEDs display the power supply status of all connected modules as a common message. Undervoltage Short circuit Interruption of voltage

Diagnostic LEDs on the CP extension modules LEDs on the individual CP/CPI modules display the current status of the switching signals of the inputs or outputs. Additional LEDs display short circuits or overload of the power supply and communication faults on the CP connection.

Diagnostic messages via the fieldbus All available diagnostic information is transferred to the fieldbus node by means of the CP connection. This means that the diagnostic information for the entire device can be transferred to the fieldbus master. Configuration errors Short circuit/overload of an output module Short circuit/undervoltage of the sensor supply Undervoltage/load voltage of the valves Interruption of a CP string to one of the CP modules

Fieldbus 1

4

2

4

4

6

è Internet: www.festo.com/catalogue/...

3

5

1 Diagnostics via fieldbus 2 Bus-specific LED 3 Diagnostics via LED on the CP/CPI module 4 Diagnostics via CP string 5 Status display on the CP/CPI module 6 Status display on the valve terminal

Subject to change – 2018/06

Page 5

Fieldbus Direct Overview of examples Valve terminals with CP interface CPV valve terminal CPV10 CPV14 CPV18

Max. 16 valves in 8 valve slices Highly compact and space-saving Width 10, 14, 18 mm Nominal flow rate 400/800/1600 l/min CPV10, CPV14 and CPV18 with CPI functionality

Further information è Internet: cpv

MPA1 MPA2

Max. 32 valves Modular and versatile Width 10, 20 mm Nominal flow rate 360/700 l/min CPI functionality

Further information è Internet: mpa-s

MPA-S valve terminal

2018/06 – Subject to change

è Internet: www.festo.com/catalogue/...

5

Page 6

Fieldbus Direct Peripherals overview CP/CPI installation system input/output modules CP-E16-M12x2-5POL

16 inputs 24 V DC Signal status display via 16 LEDs Operating status display

M12 socket, double allocation 1x M9 CP/CPI connection PNP/NPN, IP65

CP-E16-M8

16 inputs 24 V DC Signal status display via 16 LEDs Operating status display

M8 socket, single allocation 1x M9 CP connection PNP/NPN, IP65

CP-E16-M8-Z

16 inputs 24 V DC Signal status display via 16 LEDs Operating status display

Electrical isolation through additional power supply M8 socket, single allocation 1x M9 CP connection Separate sensor supply PNP/NPN, IP65

CP-A08-M12-5POL

8 outputs 24 V DC Output signal display via 8 LEDs Operating status display M12 socket, single allocation

2x M9 CP connection Separate load voltage Outputs resistant to overloads and short circuits PNP/NPN, IP65

Detailed description of input and output modules è Internet: ctec

6

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/06

Page 7

Fieldbus Direct Peripherals overview CP/CPI Compact Line input/output modules CP-E08-M12x2-CL

8 inputs 24 V DC Signal status display via 8 LEDs Operating status display

4x M12 socket, 5-pin, double allocation 2x M9 CP connection PNP, IP65/67

CP-E08-M8-CL

8 inputs 24 V DC Signal status display via 8 LEDs Operating status display

8x M8 socket, 3-pin, single allocation 2x M9 CP connection PNP, IP65/67

CP-E16-KL-CL

16 inputs 24 V DC Indirect signal status display via LEDs in the connection set of the tension-spring socket Operating status display

Screw terminal or tension-spring sockets 2x M9 CP connection PNP, IP20

CP-A04-M12x2-CL

4 outputs 24 V DC Signal status display via 4 LEDs Operating status display

4x M12 socket, 5-pin, double allocation 2x M9 CP connection Outputs resistant to overloads and short circuits PNP, IP65/67

In

Out

1

3

5

7

In

Out 0

2

4

1

3

5

6 7

Detailed description of input and output modules è Internet: ctec

2018/06 – Subject to change

è Internet: www.festo.com/catalogue/...

7

Page 8

Fieldbus Direct Peripherals overview CP/CPI Eco Line input/output modules CP-E16-M8-EL

16 inputs 24 V DC Signal status display via LEDs Operating status display

16x M8 socket, 3-pin, double allocation 2x M9 CP connection PNP

CP-E16-M12-EL

16 inputs 24 V DC Signal status display via LEDs Operating status display

8x M8 socket, 5-pin, single allocation 2x M9 CP connection PNP

CP-A08-M12-EL-Z

8 outputs 24 V DC Signal status display via LEDs Operating status display

4x M12 socket, 5-pin, double allocation 2x M9 CP connection Outputs resistant to overloads and short circuits PNP

Detailed description of input and output modules è Internet: ctec

CP connecting cable The CP string is connected using preassembled CP cables, which are sup­ plied in lengths from 0.5 to 8 metres.

8

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/06

Page 9

Fieldbus Direct Peripherals overview Fieldbus systems for CPV Direct

Fieldbus variants Of the more than 20 different fieldbus systems (protocols) available on the market, some have emerged as the most important variants. Festo supports these by means of various fieldbus nodes (FBxx) on its valve terminals. Fieldbus systems require a powerful, central PLC and a master interface adapted to that particular fieldbus. Fieldbus systems are generally used when several devices with many inputs/outputs, complex functions or high communication levels must be controlled. In this case, the advan­ tages of simple cabling, easy diagnos­ tics and maintenance outweigh the extra outlay for a fieldbus master in­ terface and the necessary know-how.

2018/06 – Subject to change

Festo fieldbus A fieldbus developed by Festo with simple prompting, supported by the controllers of the FPC, SF and IPC series (Festo FB5). A maximum of 98 bus stations can be connected to the Festo fieldbus. The bus can oper­ ate with 4 different baud rates (31.25, 62.5, 187.75 and 375 kbps). PROFIBUS DP An open fieldbus standard, originally developed by Siemens and in worldwide use. The bus can operate with baud rates from 9.6 kBaud to 12 MBaud.

DeviceNet An open fieldbus system based on CAN technology originally developed for the automotive sector. DeviceNet was originally developed by Rockwell (Allen Bradley) and is now an open standard.

ABB CS31 The fieldbus from ABB connects a maximum of 63 fieldbus stations to the fieldbus master. The data is transferred at a constant baud rate of 187.5 kbps. The protocol is suitable for use in all areas of automation technology.

Moeller SUCONET K A maximum of 98 bus stations can be connected to the SUCONET K fieldbus. The bus operates with a baud rate of 187.5 or 375 kbps, depending on the design, bus length, etc. The bus interface is based on RS 485 with a master/slave structure.

è Internet: www.festo.com/catalogue/...

9

Page 10

Fieldbus Direct Peripherals overview Fieldbus systems Valve terminal type

CPV-…-GE-DI01-8

CPV-…-GE-DI02-8

10

Fieldbus protocol

PROFIBUS DP (12 MBaud) Festo ABB CS31 Moeller SUCONET K PROFIBUS DP (12 MBaud)

Plug type, bus connection

è Page/ Internet

16

Sub-D fieldbus plug 2xM12, 5-pin, B-coded

12

32

Screw terminal strip, 5-pin Sub-D socket, 9-pin Socket and plug, M12x1, 5-pin, B-coded

16

Valve terminal Number of solenoid coils

CP string extension Number of solenoid coils/outputs

Number of inputs

16

16 / 8

16

32 / 32

è Internet: www.festo.com/catalogue/...