For the Foxboro 760CSA

Page 1

Product Specifications

PSS 2C-1A1 B

760 Series SINGLE STATION MICRO Controller

This powerful, new single-station controller is a self-contained, stand-alone, microprocessor-based instrument that permits control of a wide range of processes. It has a host of advanced features including the revolutionary and exclusive EXACT control. FEATURE HIGHLIGHTS • EXACT Control

• Passcode Security

• Brilliant Fully-Interactive Display

• Nonvolatile Memory

• Familiar Operating Procedures

• Transportable Configuration

• Computer Compatible

• Power Failure Recovery Logic

• Housing or Shelf Mounting

• Common Keypad for Configuration and Operator Interface

• Ideal Physical Retrofit into Existing Shelves

®

Page 2

PSS 2C-1A1 B Page 2 EXACT CONTROL

COPY FEATURE

The EXACT tuning method does not use an arbitrary process model. Instead it uses micro-processor technology to make controller adjustments based on the actual, current process dynamics. Thus, while continuously scanning the process variables, if it senses a process upset, it immediately takes corrective action. The user can choose the degree of response by specifying the desired damping and overshoot-to-load change, such as quarter-amplitude damping.

The copy feature permits the controller configura-tion to be duplicated for use in another controller. This is accomplished by using two NOVRAMS (nonvolatile, random access memory modules) and a configuration copy accessory. Briefly, after turning off power, the procedure is as follows. First remove the first NOVRAM (in controller and already configured); then install (plug in) the copy accessory; next plug the first NOVRAM and second NOVRAM (memory to be configured) into the copy accessory; and then turn on the power and the second NOVRAM is now copied for use in another controller. With minimum effort, any number of controllers can thus be configured to the same parameters as the original controller. Each controller, as configured, can then have any of its individual parameters changed to any desired value.

This new, exciting tool is on the job 24 hours a day, and it can be turned on or off from the keypad. Process upsets do occur, but with EXACT control, the product need not suffer. CHOICE OF HOUSING OR SHELF MOUNTING The 760CNA has an integral housing that can be mounted directly to a panel. The 760CSA can be installed in most Foxboro shelves with only little additional hardware. The controller is a physical substitute for H-Line, E27 Series, and even pneumatic 100-Line controllers. SIMPLIFIED CONFIGURATION AND OPERATION Because of the controller’s flexibility, it can be easily configured to meet the most exacting process requirements. All operating functions can be examined and/or changed by pushbutton. Interactive prompting simplifies setting of adjustable functions. From the operator’s standpoint there is very little new to learn. The same familiar control concepts and terminology are used. What is new is the ease with which the various controller operations can be implemented or changed, and the ease with which complete information about the process and the controller is made available, literally at the push of a button.

READY FOR COMPUTER TIE-IN The controller is equipped with an RS485 serial port to connect to certain personal computers through an RS232C-RS485 converter. This simple converter provides the proper electrical and mechanical interface between these serial communication standards. COMPLETE SECURITY FOR PROCESS SETTINGS The operator has keypad access to read the value of inputs, alarm and limit settings, as well as the operating configuration. However, the operator can adjust only those settings which were specified as operator-changeable when the controller was configured. The remaining parameters can only be accessed for change by first entering a passcode from the keypad. This passcode is chosen by an authorized person at the time the controller is configured. Thus, only those who have been given this passcode can change any of the configuration parameters, including the passcode.

Page 3

PSS 2C-1A1 B Page 3 FULL-FUNCTION DISPLAY The front of the controller has a clear, bright, easy-toread, anti-glare display consisting of graphics and alphanumeric characters.This enables the operator to keep track of every parameter that is received or generated by the controller. Measure-ment and setpoint displays have applicable engineering units electronically displayed. See Figure 1.

Figure 1. Front-of-Panel Functions FUNCTIONAL SPECIFICATIONS Proportional Input Signals Any combination of the following proportional inputs with total of all types not to exceed four. All signals Proportional Type Maximum Input Signal Number can be characterized or combined in a variety of calculations.See table below.

Details

4 to 20 mA dc Current Input

4

4 to 20 mA dc input is standard for all shelf-mounted controllers, and for housing-mounted controllers that have 32-position terminal blocks on the rear of the housing. Inputs are across 250 Ω resistors. Housing-mounted controllers that have a 30-pin socket on the rear of the housing will accept 4 to 20 mA inputs by the addition of 250 Ω resistors across the input terminations. Includes 25 V dc source for powering one or two field transmitters.

10 to 50 mA dc Current Input

4

10 to 50 mA dc input is optionally available; refer to Optional Features section. 10 to 50 mA input/output is also available for shelf-mounted controllers (760CSA); refer to Model Code.

1 to 5 V dc Voltage Input

4

1 to 5 V dc input is standard on all housing-mounted controllers that have a 30-pin plug socket on the rear of the housing. All other controllers will accept 1 to 5 V dc by removing the input resistors.

Thermocouple Input (requires E93 Temperature Transmitter, or equivalent)

1

Linearization of displayed value is provided as follows:

1 to 9999 Hz Frequency Input

2

Input pulse rates, voltage levels, and field power are compatible with Foxboro E83 Series Vortex Flowmeter, and with Foxboro 81 or 82 Series Turbine Flowmeter having a preamplifier input.

Resistance Temperature Detector (RTD) Input

1

Platinum, per IEC 100 or SAMA* 100 (RC 21-4) temperature curves. Linearization of displayed value is provided, as follows:

Thermocouple Type J Type K Type E

*Scientific Apparatus Makers Association

Temperature Range -20 to +760°C (-4 to +1400°F) -20 to +1380°C (-4 to +2500°F) -130 to +540°C (-200 to +1000°F)

IEC 100

SAMA 100

Range

–200 to +850°C (–330 to +1562°F)

–200 to + 600°C (–330 to +1100°F)

Span

110 to 1000°C (200 to 1800°F)

110 to 800°C (200 to 1440°F)

Page 4

PSS 2C-1A1 B Page 4 FUNCTIONAL SPECIFICATIONS (Cont.) Discrete Input Signals One or two contact or transistor switch inputs, 5 V dc nominal open circuit voltage, 1 mA maximum current. For remote status changes such as A/M, R/L, W/P, EXT ACK, and tracking functions. Output Signals TWO NONISOLATED ANALOG OUTPUTS Control output (can be conditioned) and auxiliary output. • Control: 4 to 20 mA into 500Ω maximum.10 to 50 mA input/output into 660Ω maximum is optionally available for shelf-mounted controllers. Isolated output option is also available. • Auxiliary Output: 1 to 5 V dc into 2 kΩ minimum. Can be used for measurement, set point, control, or conditional input signals. TWO DISCRETE OUTPUTS Two nonisolated open collector transistor (NPN) switch outputs. For status indication of A/M, R/L, W/P, and alarms. Contact ratings are 50 V dc maximum, 250 mA maximum. Leakage current is 100 µA maximum. Transmitter Power Supply Standard controller provides 25 V dc field power for two 4 to 20 mA transmitters. Each transmitter connection has a 250Ω limiting resistor. Controller with optional 10 to 50 mA output provides 65 V dc field power for one transmitter. Output is currentlimited to 55 mA. Alarms Up to three absolute, and one deviation, high-low alarms are available. • Two absolute alarms are configurable for the measurement signal, and one absolute alarm for the output signal. • Deviation alarm senses the difference between the set point and measurement (error signal). • Alarm status is indicated by a combination of alphanumeric display, the bar graphs, and the contact outputs. • Alarm dead band is adjustable between 0 and 10% of span. Supply Voltage (As specified; fused.) ac SUPPLY VOLTAGE 24, 100, 120, 220, or 240 V; all +10, -15% 47 to 63 Hz, at 30 VA maximum dc SUPPLY VOLTAGE 24 V +20%, -10%; at 1 A maximum Input Filter Adjustment time, 0 to 10 min. Second order Butterworth filter.

Front Panel The controller can be configured and operated entirely from the front panel with no external equipment required. By using the keypad and the display, complete process information can be read, and all controller settings can be changed (see Figure 1). The front panel consists of the following parts: • Alphanumeric display consisting of two lines of 9 characters each, graphics display of three 50segment bar graphs, and status indicators. • The displays are highly-visible fluorescent. The numerical quantities have a resolution of ±0.1% of upper range value.The bar graphs have a resolution of ±2% of span. • Keypad of 8 keys. Keys must be pressed for a minimum of 0.2 seconds. Switches are normallyopen contacts, closing to a common lead. Environmental Operating Limits TEMPERATURE 5 and 50°C (40 and 120°F) HUMIDITY 5 and 95% Execution Rate 10 times per second. Memory All configuration and operating parameters are stored in a nonvolatile memory. Should a power failure occur, essential control settings and last operating conditions are saved indefinitely. No batteries are used. Control Adjustments PROPORTIONAL BAND 1 to 8000%. INTEGRAL 0.014 to 200 minutes/repeat. DERIVATIVE 0 to 100 minutes. Other Control Adjustments • Non-Linear Extender to PID • EXACT Control • Ratio: 0 to 5 • Calculations (each input can have a gain and/or bias, and can be combined together in a variety of mathematical equations). • Characterizer (available on two signals at 20 segments each, including non-linear extender, assignable). • Logic (AND, NAND, OR, XOR, NOR, and NOT on two contact inputs) • Signal Conditioning (square, square root, characterizer, RTD and thermocouple (TC) linearizing).

Page 5

PSS 2C-1A1 B Page 5 PERFORMANCE SPECIFICATIONS Accuracy at Numeric Display In percent of span, unless otherwise noted. Refer to table below. Parameter

Accuracy

Set Point Local Remote Ratio

±0.1% ±0.1% ±0.1%

Input Analog Frequency RTD

Ambient Temperature Effect Maximum error, in percent of span, for a 30°C (55°F) change in temperature within normal operating limits. See table below. Parameter

Maximum Error in % of Span

Set Point Local Remote

±0.1% ±0.5%

±0.1% ±0.1% ±0.5 °C

Output Valve Retransmitted (linear)

Input Analog Frequency RTD

±0.5% ±0.2% ±0.5%

±0.5% ±0.25%

Linearization RTD Thermocouple

Output Valve Retransmitted

±0.5% ±0.5%

±0.5 °C ±0.5 °C

Control Modes Prop. Band Integral Derivative

±5% of setting ±5% of setting > 0.1 min ±5 s for < 0.1 min

Alarm Settings Absolute Deviation

±0.1% ±0.1%

Calculations

±0.1%

Humidity Effect Maximum error, in percent of span, from reference conditions to 95% R.H., measured at a wet-bulb temperature of 30°C (80°F) is ±0.1% for all conversions, calculations and settings. Frequency Response Analog input to output conversion flat to 3 Hz. Output Noise 0.25% peak to peak

Supply Voltage Effect ±0.1% of span (maximum) for a +10% or -15% change in ac voltage within normal operating conditions; or a +20% or -10% change in dc voltage within normal operating conditions. PHYSICAL SPECIFICATIONS Signal Connections (on rear panel) 760CNA (HOUSING MOUNTING) • 32-position terminal block, with compression terminals, for wire sizes up to 2.5 mm2 (14 AWG), or, • 30-pin socket for use with a 2AK or 2AKQ SPEC 200 cable. 760CSA (SHELF MOUNTING) • 30-pin socket for use in 202S Shelf with 32position terminal block and cord set. Terminal block has compression terminals for wire sizes up to 2.5 mm2 (14 AWG). • 20-pin socket for retrofit use in all Foxboro shelves using 20-position terminal block and cord set.

Power Connections (on rear panel) 760CNA (HOUSING MOUNTING) 3-position terminal strip with 8-32 screw connections. 760CSA (SHELF MOUNTING) 3-position power cord connector. Mounting 760CNA Controller with integral housing is mounted to panel. Refer to “Dimensions--Nominal” section. 760CSA Mounts in a 202S Series Shelf; or with retrofit installations, in EH, 101, or 102 Series Shelves. Approximate Mass 4.5 kg (10 lb)

Page 6

PSS 2C-1A1 B Page 6

MODEL CODE - 760CNA Description

Model

SINGLE STATION MICRO Controller, Housing Mounting

760CNA

Nominal Supply Voltage and Frequency

120 V ac, 50/60 Hz 220 V ac, 50/60 Hz 240 V ac, 50/60 Hz 24 V dc 24 V ac, 50/60 Hz 100 V ac, 50/60 Hz

–A –B –C –D –E –J

Housing and Signal Connections

32-Position Terminal Block on Rear of Housing. Standard 4 to 20 mA dc input(a,b) 30-Pin Plug Socket on Rear of Housing. Standard 1 to 5 V dc Input(c) Controller Chassis without Housing Optional Features

T C W

Isolated Output Signal (Output Number 1 only) RTD Input (Input Number 1 only)

1 2

(a)Available 10 to 50 mA dc input. Specify AS Code SIG. (b)Will accept 1 to 5 V dc input by removing input resistor. (c)Will accept 4 to 20 mA dc or 10 to 50 mA dc, respectively, by addition of 250 Ù or 100 Ù voltage dropping resistors at input terminations.

MODEL CODE - 760CSA Description

Model

SINGLE STATION MICRO Controller, Shelf Mounting - Standard 4 to 20 mA dc Input(a) Signal Connector 20-Pin Signal Connector, Quick Disconnect 30-Pin Signal Connector, Quick Disconnect Nominal Supply Voltage and Frequency

760CSA –2 –3

120 V ac, 50/60 Hz 220 V ac, 50/60 Hz 240 V ac, 50/60 Hz 24 V dc 24 V ac, 50/60 Hz 100 V ac, 50/60 Hz Optional Features

–A –B –C –D –E –J

Isolated 4 to 20 mA Control Output Signal (Output Number 1 only) RTD Input (Input Number 1 only). Not available with 20-pin Signal Connector, Code –2. 0 to 50 mA dc Input Signals and 10 to 50 mA dc Control Output Signal. Not available with 24 V Supply (Code –D or Code –E).

1 2 3

(a)Will accept 1 to 5 V dc input by removing input resistor.