760 Series SINGLE STATION MICRO Controller Product Specifications, pages 7 to 12

Pages 7 to 12 of 12

The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Foxboro 760CSA

Page 7

PSS 2C-1A1 B Page 7 PRODUCT SAFETY SPECIFICATIONS Electrical Classification Testing Laboratory, Types of Protection, and Area Classification

Conditions of Certification

Electrical Safety Design Code

CSA certified for use in Ordinary Locations.

Panel-mounted controllers without a housing are not approved.

CS-E/CG-A

CSA certified for Class I, Groups A, B, C, and D, Division 2.

10 to 50 mA options and panel-mounted controllers without a housing are not approved. Temperature Class T6.

CS-E/CN-A

FM certified for use in Ordinary Locations.

10 to 50 mA options are Foxboro certified only. See below.

CS-E/FG-A

FM certified for Class I, Groups A, B, C, and D, Division 2.

10 to 50 mA options are not approved. Temperature Class T6.

CS-E/FN-A

Foxboro certified for use in Ordinary Locations.

Controllers with 10 to 50 mA input and output options.

CS-E/XG-F

OPTIONAL FEATURES 10 to 50 mA dc Current Input A 10 to 50 mA dc current input is optionally available for housing-mounted controllers with a 32-position terminal block on the rear of the housing (760CNA- T). Specify Auxiliary Specification (AS) Code SIG.

o

Surge Suppressor A surge suppressor is optionally available for use with serial communication input when external wiring is located near transient producing sources such as meters, solenoids, high voltages, etc. Specify AS Code SURSUP.

Page 8

PSS 2C-1A1 B Page 8 ACCESSORIES Configuration Copy Accessory All of the operating configuration is stored in a nonvolatile, random access memory module (NOVRAM). The copy accessory permits the entire contents of the memory module to be quickly copied into another NOVRAM, either a spare or one from another controller. Specify part number K0143DV for the copy accessory, and part number K0143SA for a spare NOVRAM. Panel Cutout Adapter Bezels For 760CNA Controllers only. Used when replacing E Series Housing-Mounted Electronic CONSOTROL Control Stations and 54 Series Pneumatic CONSOTROL Control Stations with 760CNA Controllers. Two bezels are required for each panel cutout. See table below. Bezel Part Number

Quantity Required

E-3 Single Unit Electronic Housing with one 760CNA

K0143DG

2

E-6 Double Unit Electronic Housing or 54 Series Pneumatic CONSOTROL Control Station with two 760CNA’s

K0143DH

2

E-9 Triple Unit Electronic Housing with two 760CNA’s

K0143DJ

E-9 Triple Unit Electronic Housing with three 760CNA’s. Width of existing cutout must be increased by 13 mm (0.5 in)

K0143DK

To Replace

Replacement Shelf Signal Connector Assembly For installing 760CSA-3 Shelf-Mounted Controller (with 30-pin receptacles) into existing 101, 102, 202, and EH Series Shelves. Connector set assembly for 102, 202, and EH Shelves includes plug, cable, and terminal block. Specify part number K0143CG for 4 to 20 mA inputs. And specify part number K0143EF for 10 to 50 mA inputs. Assembly for 101 Shelf cable with quick-disconnect plug on one end and screw-in plug on other end. Input range is 1 to 5 V dc. Convertible to 4 to 20 or 10 to 50 mA dc input by addition of 250 or 100 Ù resistor, respectively. Specify cable Model 2AKQ. When ordering this accessory, a replacement power cord is also required (see Replacement Power Cord section). Replacement Power Cord Required when ordering a Replacement Shelf Signal Connector Assembly. Available with power plug at each end (plug type), with power plug on one end with a long extension, or power plug on one end with a short extension type. See table below. Power Cord Type

Approximate Length

Plug Type (Plug at each 1.2 m (4 ft) end) 2

2

Shelf Conversion Parts To convert 101, 102, 202, and EH Shelves to accept a 760CSA Controller replacing an electronic or pneumatic instrument. Specify model of both shelf and instrument being replaced.

Part Number N0139CA

Long Extension Type (Plug on one end)

5.6 m (18.5 ft) N0139CB

Short Extension Type (Plug on one end)

1.2 m (4 ft)

N0139TZ

Computer Based Training Package Consists of a software program that operates on any IBM-compatible personal computer that has a 256K RAM (minimum) and MS-DOS 2.0 release. The package includes a keyboard overlay so that designated keys on the computer clone the functions of the controller front panel keyboard. Specify part number L0121AA.

Page 9 read from a scan by OCR; it may hold reading errors

PSS 2C-1A1 B Page 9

DIMENSIONS, NOMINAL m in

761CNA CONTROLLER--HOUSING MOUNTING

MOUNTING PANEL 3 TO 22 mm MOUNTING RECESSED 30-PIN POWER TERMINALS (0.12 TO 0.90 in) THICK BRACKET HOUSING CONNECTOR PLUG, OR (24, 100, 120, 220, 32-POSITION TERMINAL 240 V ac,OR 24 Vdc FRONT STRIP, AS SPECIFIED. AS “ee ‘ PANEL :, - - fig :eces $0.5 G2e aoe 144 57 188 3 G) & 29 ey a - 2 = = OY 6.3 OIA. | 025 ; al | |g19.2 a 6.3 31 ia DIA 26 0.38 = , 0.4 0.25 12 17.6 l TO 45 | a 72 455, a 28 173 ! + - i - PANEL CUTOUT DIMENSIONS 68.0 TO 695 (N X 72.0], 4.0 = WIOTH (mm); TOLERANCE = +1.5,-0 ere, - ____» 268 To 2.74 (N X 2.84], 0.16 = WIDTH (in); TOLERANCE = +0.06,-0 ry 1 | ! . . | t 138.0 TO 139.0 SINGLE a 4 ! 5.43 To 547 |CUTOUT cL ! CUTOUT FOR MULTIPLE 760 CONTROLLERS * } | | OF : c + 760CNA u . § RIETEOGLER ! MAXIMUM

3.0 TO 3.3

0.12 TO 0.13

76 To 79 0.30 To 0.31

IF PANEL THICKNESS IS GREATER THAN 13 mm (0.5 in), ACLEARANCE SLOT FOR =, - - - LATCH ON BOTTOM OF CONTROLLER IS REQUIRED.

FRONT SURFACE OF PANEL

PANEL THICKNESS

*1F PANEL HAS MORE THAN ONE CUTOUT, ALLOW 45 mm (1.78 in) VERTICAL DISTANCE BETWEEN CUTOUTS AS SHOWN BELOW. THIS PROVIDES 36 mm (1.4 in) SPACING BETWEEN CONTROLLERS.

UPPER CUTOUT

LOWER CUTOUT

Fs ™e

Page 10

PSS 2C-1A1 B Page 10 DIMENSIONS – NOMINAL (Cont.) 760CSA CONTROLLER--SHELF MOUNTING FOR 760CSA SHELF DIMENSIONS, REFER TO APPLICABLE DIMENSIONAL PRINT IN TABLE BELOW.

For Shelf Model

Use Dimensional Print

EH 101 102 202S

DP 018-510 DP 017-441 DP 017-410 DP 202-100

ORDERING INSTRUCTIONS 1. 2. 3. 4.

Model Number Optional Features Accessories Customer Tag Data NOTE

For 760CSA (Shelf-Mounted Controller), refer to GS 2A-12A1 A, GS 2B-12B1 B, GS 2B-12B1 A, and PSS 2E-2A1 C for shelves and cord sets for the EH, 101, 102, and 202S Shelves, respectively.

Page 11

PSS 2C-1A1 B Page 11

Page 12

PSS 2C-1A1 B Page 12

The Foxboro Company 33 Commercial Street Foxboro, MA 02035-2099 United States of America http://www.foxboro.com Inside U.S.: 1-888-FOXBORO (1-888-369-2676) Outside U.S.: Contact your local Foxboro representative. Facsimile (508) 549-4492

Foxboro, EXACT, SINGLE STATION MICRO, and SPEC 200 are trademarks of The Foxboro Company. Invensys is a trademark of Invensys plc. All other brand names may be trademarks of their respective companies.

An Invensys company

MB 010

Copyright 1988-1996 The Foxboro Company All rights reserved Printed in U.S.A.

1296