For the GE AF-300G11, Fanuc AF-300G11 and GE Fanuc AF-300G11

Page 1

TM

AF-300 G11 Specifications

GE Industrial Systems

Product Specifications

AF-300 G11

TM

1

Page 2

TM

AF-300 G11 Specifications Category Nominal Motor Braking Torque (Standard)

Braking Torque (Optional) Enclosure, Standard Cooling Method Standards

Input

Condition Altitude Temperature Vibration Humidity Output

Accuracy (Stability) Setting Resolution

2

Item Description 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3 Phase 1/2 Hp to 450 Hp 1/4 Hp to 1 Hp 150% 2 Hp to 10 Hp 100% 15 Hp to 30 Hp 20% 40 Hp and Higher 10% - 15% 1 Hp to 30 Hp 150% 40Hp and Higher 100% 1/4 Hp to 30 Hp NEMA 1 Standard, NEMA 4 Optional to 10 Hp, NEMA 12 Optional all ratings 40 Hp and Up NEMA 1 Standard, IP00 Optional 40Hp and above Convection 1 Hp and below Fan Cooled Above 1 Hp UL/cUL No input fuses required CE EN61800-3 for EMC EN61800-2 for Low Voltage Item Description Up to 30 Hp, 230 VAC 200V - 230V (+10%, -15%), 50 or 60 Hz (+/- 5%) Up to 30 Hp, 460 VAC 380V - 480V (+10%, -15%), 50 or 60 Hz (+/- 5%) 40 Hp & Above, 230 200V - 220V (+10%, -15%), 50 Hz (+/- 5%) / 220V - 230V (+10%, -15%), 60 Hz VAC (+/- 5%) 40 Hp & Above, 460 380V - 440V (+10%, -15%), 50 Hz (+/- 5%) / 380V - 480V (+10%, -15%), 60 Hz VAC (+/- 5%) Unbalance Voltage Unbalance within 3% Power Dip For input voltage greater than Vmin, the drive will operate at rated output continuously. For input voltage less than Vmin, the drive will operate at 85% of rated output for 15 Msec. Vmin (230V Series) = 165V, Vmin (460V Series) = 310V. Smooth recovery method is selectable Item Description 1000 meters or less. Derate at 1% for each 100 meters from 1000 to 3000 meters (Above 3000 meters, consult factory) Ambient -10 to 50°C (units less than and equal to 30Hp must have ventilation covers removed for 40°C and above) Storage -20 to 65°C IEC61200-2 5 - 95% Relative Humidity (Non-condensing) Item Description 230V, 3 Phase 3 Phase, 200V, 50Hz or 3 Phase, 200V, 220V, 230V, 60Hz 460V, 3 Phase 3 Phase, 380V, 400V, 415V, 440V, 50Hz or 3 Phase, 380V, 400V, 440V, 460V, 60Hz Frequency 50 / 60 Hz Overload 150% of rated current for 1 min 180% of rated current for 0.5 sec => 30Hp 200% of rated current for 0.5 sec =< 30Hp Max Freq. 50 - 400 Hz Base Freq. 25 - 400 Hz Starting Freq. 0.1 - 60 Hz Carrier Freq. 0.75 - 15 kHz up to 100 Hp. 0.75 - 10 kHz 125 Hp and above. Minimum carrier frequency changes dependent on maximum output frequency Analog +/- 0.2% of maximum frequency (speed) at 25 +/- 10°C Digital +/- 0.01% of maximum frequency (speed) between -10 and 50°C Analog 1/3000 of maximum frequency (speed) Digital 0.01 Hz for frequency up to 99.9 Hz (0.1 Hz for frequency > 100 Hz)

Page 3

TM

AF-300 G11 Specifications Control Control Method

Item Sinusoidal PWM

Operation Frequency Setting

Methods Keypad Potentiometer Analog

Digital

Acceleration Setting

Serial Networks Four Modes Automatic

Frequency Limiter Bias Frequency Frequency Gain Jump Frequency Catch Spinning Motor Auto-Restart Switching Operation Slip Compensation Torque Limiting Torque Control PID Control Automatic Deceleration 2nd Motor Settings Fan Stop Operation Motor Autotune Energy Saving Keypad

Offline Tuning Online Tuning

Item

Description V/Hz Dynamic Torque Vector Control (Sensorless) Flux-vector Control with Pulse Tachometer Keypad, Digital Input, Bus Communication (UP or DOWN) 1-5KW (1/2 W) Optional 0 - 5 VDC 0 to +/– 10 VDC Bi-polar (Reversible operation by signal polarity) 0 - 10 VDC (10 - 0 VDC selectable) 4 - 20 MA (20 - 4 MA selectable) Up/Down Control (Increases with UP, decreases with DOWN) Multi-step (4 different frequencies via SS1 and SS2) Multi-step (8 different frequencies via SS1, SS2, and SS4) Multi-step (16 different frequencies via SS1, SS2, SS4, and SS8) Programmed pattern operation - 8 stages RS485 with Modbus RTU - Standard Optional network cards 0.01 - 3600 seconds (Independent Acc/Dec, four times, three modes - Linear, SCurve, Non-linear) When the motor acc.(dec.) torque reaches a preset value, the acc. (dec.) time is automatically extended for tripless operation. High and low values are presettable -400.0 to +400.0 Hz Adjustable from 0 - 200 % Jump frequency setting (3 points), jump hysteresis width (1 setting) Smoothly pick up a rotating motor without stopping (speed search method) No DB required Autorestart is available after a momentary power failure (speed search method) Continuous operation mode is selectable Control terminals are provided for smooth switching operation from line power to drive Related to load torque and magnified for negative slips frequencies Automatic overcurrent adjustments 2 torque limiting functions can be preset Output torque or load factor can be controlled by analog input signal with PG option Process controller - standard Automatic extension of deceleration time when braking torque limit is reached for tripless operation without a DB resistor Settings for a second motor: base freq., rated voltage, rated current, no load current, impedances Automatically manage cooling fan operation to extend life - up to 30Hp operation is preset, above 30Hp signal is preset Selectable with motor rotating and without motor rotating Dynamically compensates regulator for changes in motor temperature Reduces losses at light loads Description Backlit LCD Display Smart Keypad to copy parameters from one drive to another Extension cable adapter for RJ45 connector

3

Page 4

TM

AF-300 G11 Specifications Indication Operation Mode

Item LED

LCD

Program Mode Trip Mode

Diagnostics

4

Other Feature Languages OC1 OC2 OC3 FUS OU1 OU2 OU3 LV OH1 OH2 OH3 dBH OL1, OL2 OUV EF LIM FUS Er1 Er2 Er3 Er4 Er5 Er6 Er7 Er8 History

Description Output frequency Output current, Output voltage Motor synchronous speed (RPM) Line speed (M/min) Load shaft speed (RPM) Output torque (%) Frequency setting PID (Set 1 value, Set 2 value, Feedback value) Power consumption Motor load factor Heatsink temperature Drive internal temperature I/O Test - indicates signal existence or absence of digital I/O and signal value of analog I/O RMS current - 1 cycle %DB - 1 cycle DC Link power charge display Function Code and Function Name, Data or Data Code English, French, German, Italian, Japanese, Spanish Overcurrent during acceleration Overcurrent during deceleration Overcurrent running at constant speed Fuse blown Overvoltage during acceleration Overvoltage during deceleration Overvoltage running at constant speed Low voltage Overheating of heatsink External thermal relay tripped Overtemperature of inside air Overheating of DB circuit Motor overload Drive unit overload Ground fault Input Phase Loss DC Fuse open (40 Hp and above) Memory error KEYPAD communication error CPU error Option card error, detected by the control card Option card error, detected by the option card Operations procedure error. Output wiring error - impedance unbalance RS485 communications error Trip history - passed four events (Trip and Warning)

Page 5

TM

AF-300 G11 Specifications Protection Overload Overvoltage

Item

Incoming Surge Undervoltage Overheating Short Circuit Ground Fault Motor Overload

DB Resistor Overheating Motor Overheating Phase Loss

Signal Loss Auto-reset Terminal Functions Main Circuit Power Input Drive Output DC Reactor

L1/R, L2/S, L3/T U, V, W P1, P(+)

Braking Unit Ext. Braking Resistor Unit Ground Aux. Control Power

P(+), N(-) P(+). DB G R0, T0

Analog Inputs Potentiometer Power Voltage Input

Item 13 12

Common Current Input

11 C1

Analog Input 1

V2

Item

Description Detection of electronic thermal overload relay Detection of DC link circuit overvoltage (230V series - 400V, 460V series 800V) Drive protection from surge voltage input (Max. 1.2 x 50 usec 7KV peak) Detection of DC link circuit undervoltage (230V series - 200V, 460V series 400V) Drive overheating protection by temperature detection Short circuit protection for drive output circuit Ground fault protection for drive output circuit - 3 phase circuit detection method Zero phase current detection method - 40 Hp and above Electronic thermal overload relay can be selected for general purpose motor or dedicated drive motor Calculation of thermal time constant can be preset 2nd motor electronic thermal overload relay Internal electronic thermal overload relay - up to 10 Hp Overheating detection thermal overload relay installed in braking resistor unit 15 Hp and above (option) Overheating detection PTC thermistor can be connected to terminals 13-C1-11 Drive protection for line side phase loss Drive protection for motor side phase loss during tuning Detection of output impedance unbalance during tuning Detection of loss of C1 current signal Auto reset times and reset interval can be preset Description Connect a three phase power source Connect to a three phase induction motor Connect the DC reactor for power factor correcting or harmonic current reduction Shipped in same carton with drive Connect the braking unit - optional for 15 Hp and above Connect the external braking resistor - 230V/460V series up to 10 Hp Ground terminal for drive chassis (housing) Connect the same AC power source used for Power Input as backup for control circuit power supply - 2 Hp and above Description +10V DC power supply, maximum allowable output current 10ma 0-10V / 0-100%, 22K ohm input impedance 0-5V / 0-100% can be selected by signal gain setting Inverse mode operation by polarity Reversible operation can be selected by function code Frequency command, torque control, Tach feedback, or PID control Common for analog signal 4-20ma / 0-100 % (input impedance 250 ohm) Inverse mode operation Frequency command, PID feedback 0 - +/- 10V / 0 - +/- 100% (input impedance 22K ohm)

5

Page 6

TM

AF-300 G11 Specifications Digital Inputs Forward Operation Reverse Operation Digital Input 1

Item FWD REV X1

Digital Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Input 6 Digital Input 7 Digital Input 8 Digital Input 9 3 Wire Stop

X2 X3 X4 X5 X6 X7 X8 X9 HLD

Coast Stop Trip Command Alarm Reset Multistep Frequency

BX THR RST SS1 / SS2 SS4 SS8

6

ACC/DEC Time Select

RT1 RT2

JOG 2nd Frequency Select 2nd Motor Select DC Brake Command 2nd Torque Limiter Line/drive Switching

JOG HZ2/HZ1 M2/M1 DCBRK TL2/TL1 SW50 / SW60

UP Command DOWN Command Write Enable PID Control Cancel Inverse Mode Changeover Interlock Signal (52-2) TRQ Control Cancel Link Enable (RS485) Universal Digital Input Sync/Tach Enable Zero Speed Command Timed Alarm Command Pre-exciting Command RS485 I/O Terminal

UP DOWN WE-KP HZ/PID IVS IL HZ/TRQ LE U-DI PG/HZ ZERO STP EXITE DXA, DXB, SD

PLC Terminal

PLC

Common

CM

Description ON - Motor runs in the forward direction, OFF - Motor decelerates and stops ON - Motor runs in the reverse direction, OFF - Motor decelerates and stops Functions selected via function codes - Sink type terminal specification default with source type hardware selectable ON state - maximum input voltage 2V, maximum source current 5ma OFF state - maximum voltage 27V, maximum leakage current 0.5ma Selectable from the following

ON - the drive latches the FWD or REV signal, OFF - the drive releases the latch ON - motor will coast to a stop, no alarm signal will be issued OFF - OH2 trip is issued and latched, motor will coast to a stop ON - Momentary on for > 0.1 sec will reset faults 4 different frequencies can be selected by ON/OFF pattern on terminals SS1 and SS2 8 different frequencies can be selected by ON/OFF pattern on terminals SS1, SS2, and SS4 16 different frequencies can be selected by ON/OFF pattern on terminals SS1, SS2, SS4, and SS8 Second ACC/DEC time can be selected by terminal RT1 4 different ACC/DEC times can be selected by ON/OFF pattern on terminals RT1 and RT2 ON - JOG frequency is activated ON - drive will stop and the 2nd frequency command becomes effective ON - drive will stop and Motor 1 values are changed to Motor 2 values ON - DC injection braking is active during deceleration ON - Torque Limiter 2 is active ON - Motor is changed from drive operation to line operation (Main circuit signal output via Y1-Y5) ON - drive output frequency increases (change rate determined by ACC time) ON - drive output frequency decreases (change rate determined by DEC time) ON - data can be changed by KEYPAD operation ON - PID control is canceled ON - Operation mode is toggled from Normal to Inverse or Inverse to Normal Connection for auxiliary contact 52-2 ON - Torque control is canceled ON - Bus link or RS485 link is active ON - Enables input from RS485 or LAN option ON - Synchronize operation or Tach feedback operation is active ON - Enables stall torque function OFF -The drive decelerates and stops ON - The motor eneters into a pre-exciting state during flux vector control Connections for RS485 serial port communications Modbus RTU standard protocol Connection for PLC power supply that avoids drive current loops on Sink type inputs when PLC power supply is off. Common for digital inputs

Page 7

TM

AF-300 G11 Specifications Analog Outputs Analog Monitor

Item FMA / 11

Universal Analog Output Pulse Rate Monitor

FMP / CM

Transistor Outputs Power Supply Transistor Output 1 Transistor Output 2 Transistor Output 3 Transistor Output 4 Drive Running Frequency Equivalence

Item P24 Y1 Y2 Y3 Y4 RUN FAR

Description Output DC voltage is proportional to selected function's value. Functions are selected by FC31 Slip frequency (0 - max frequency) Output frequency (0 - max frequency) Output current (0 - 200 %) Output voltage (0 - 200 %) Output torque (0 - 200 %) Load factor (0 - 200 %) Input power (0 - 200 %) PID feedback value (0 - 100 %) Tach feedback value (0 - max speed) Analog output pass through for process control Pulse rate is proportional to selected function's value. maximum output current: 2ma The average value of the pulse train is proportional to the selected function's value, output functions same as for FMA Description DC power supply - +24V, 100ma ON state maximum output voltage 2V, sink current 50ma OFF state maximum allowable voltage 27V, leakage current 0.1ma Select from the following

ON - output frequency is larger than starting frequency ON - difference between output frequency and setting frequency is smaller than FAR hysteresis width Frequency Level Detection FDT ON - output frequency is larger than preset detection level Undervoltage Detection LV ON - drive undervoltage stops and operation command is ON Torque Polarity B/D ON - drive is in braking mode Torque Limiting TL2/TL1 ON - drive is in torque limiting mode Auto-restarting IPF ON - drive auto restarting mode active or restart waiting mode is active KEYPAD Operation Mode TP ON - drive is in KEYPAD operation mode Drive Stopping STOP ON - drive is in stopping mode or DC braking mode Overload Early Warning OL ON - electronic thermal calculated value is larger than preset protection level (Selectable) ON - output current is larger than preset detection level Line/drive Changeover SW88 Outputs signal 88 for line/drive changeover SW52-2 Outputs signal 52-2 for line/drive changeover SW52-1 Outputs signal 52-1 for line/drive changeover Motor 2 / Motor 1 SWM2 Outputs motor changeover control switch for switching between motor 1 and motor 2 Auxiliary Terminal AX ON - drive is running Times UP TU Outputs a 100ms ON pulse for time up for pattern operation Cycle Complete TO Outputs a 100ms ON pulse for cycle complete for pattern operation Stage 1 Indicator STG-1, STG-2, STG-3 Pattern operation stage indicator (binary encoded) Alarm 1 Indicator AL-1, AL-2, AL-4 Trip alarm number (binary encoded) Fan Control FAN Outputs the drive fan control signal for 40 Hp and larger drives Auto-resetting 1-TRY ON - auto resetting mode or reset waiting mode active Universal Digital Output U-DO ON - Enables output from RS485 or LAN option Overheating Early Warning OH ON - heatsink temperature is larger than preset detection level Synchronization Complete SY Synchronization signal for synchronize operation option Loss of C1 Current Input C1-OFF ON - When C1 current input is smaller than 2mA Signal Common CM Common terminal for transistor output signals

7