Page 8
TM
AF-300 G11 Specifications Relay Output Alarm Relay Output
Item 30A, 30B, 30C
Programmable Relay Output Options
Y5A, Y5C Item LAN LAN LAN LAN LAN LAN
Description Activates when a protective function is activated, programmable with the default state function code settable Selectable the same as Y1-Y4 Description GENIUS Profibus DP N2 - Metasys Interbus-S Modbus Plus DeviceNet
Tachometer KEYPAD Extension Cable
Adaptor for RJ45 cable, up to 100'
Input/Output Specifications Three-phase 230V series Type designation
6KG1123_ _ _X1A1 (NEMA Type1) 6KG1123_ _ _ X2A1 (NEMA Type12) 6KG1123_ _ _ X4A1 (NEMA Type4) 6KG1123_ _ _ X8A1 (Open, Type 12 Heatsink) 6KG1123_ _ _ X9A1 (Open) Nominal 230V system pplied motor Output Rated Capacity *1) ratings Rated Voltage *2) Rated Current *3) Overload Capability
Input ratings
Rated Frequency Phases, Voltage, Frequency
F25
007
010
015
020
025
030
040
050
060
075
100
125
HP 1/4 1/2 1 2 3 5 7.5 kVA 0.59 1.1 1.9 3.1 4.3 6.7 9.9 V 3-phase, 200V /50Hz , 200V ,220V ,230V /60Hz A 1.5 3.0 5.0 8.0 11 17 25 150% of rated current for 1min , 200% of rated current for 0.5s
10 13
15 18
20 23
25 29
30 34
40 45
50 57
60 71
75 85
100 112
125 137
33
46
59
74
87
115 145 180 215 150% of rated current for 1min , 180% of rated current for 0.5s
283
346
Hz
F50
001
002
003
005
50, 60Hz 3-phase, 200 to 230V , 50/60Hz
3-phase, 200 to 220V /50Hz , 200 to 230V /60Hz * 220 to 230V /50Hz *4), -Voltage : +10 to -15% ( Voltage unbalance *5) : 2% or less ) -Frequency :+5 to -5% When the input voltage is 165V or more, the inverter can be operated continuously. When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . (within 85% load of nominal applied motors) The smooth recovery method is selectable.
Voltage / frequency variations Momentary voltage dip capability *6)
1) Drive output capacity [kVA] at 230V 2) Output voltage is proportional to the power supply and can’t exceed the power supply voltage. 3) Current derating may be required in case of low impedence load such as high frequency motor. 4) 220 to 230 V/50 Hz: Order individually 5) Reference to the IEC 61800-3 (5.2.3) 6) Input power: 85%
Three-phase 460V series Type designation
6KG1143_ _ _X1A1 (NEMA Type1) 6KG1143_ _ _ X2A1 (NEMA Type12) 6KG1143_ _ _ X4A1 (NEMA Type 4) 6KG1143_ _ _ X8A1 (Open, Type 12 Heatsink) 6KG1143_ _ _ X9A1 (Open) Norminal 460V system applied mot Output Rated Capacity *1) ratings Rated Voltage *2) Rated Current *3) Overload Capability
Input ratings
F50
001
002
003
005
007
010
015
020
025
030
040
050
060
075
100
125
150
200
250
300
350
400
450
450
HP
1/2
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400 kVA
1.1
1.9
2.9
4.3
7.1
10
14
19
23
31
35
47
59
72
89
119
140
167
201
242
300
330
414
39
45
60 75 91 112 150% of rated current for 1min , 180% of rated current for 0.5s
150
176
210
253
304
377
415
520
Rated Frequency Phases, Voltage, Frequency
V 3-phase, 380V , 400V , 415V /50Hz , 380V , 400V , 440V , 460V /60Hz A 1.5 2.5 3.7 5.5 9.0 13 18 24 30 150% of rated current for 1min , 200% of rated current for 0.5s Hz 50, 60Hz 3-phase, 380 to 480V , 50/60Hz
Voltage / frequency variations Momentary voltage dip capability *6)
3-phase, 380 to 440V /50Hz , 380 to 480V /60Hz * 380V/50Hz and 380 to 415V/60Hz *4) -Voltage : +10 to -15% ( Voltage unbalance *5) : 2% or less ) When the input voltage is 310V or more, the inverter can be operated continuously. When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms . (less than 85% load of nominal applied motors) The smooth recovery method is selectable.
1) Drive output capacity [kVA] at 460V 2) Output voltage is proportional to the power supply and can’t exceed the power supply voltage. 3) Current derating may be required in case of low impedence load such as high frequency motor. 4) Change the tap of auxiliary transformer 380/50 Hz: Change over CN UX connector from U1 part to U2 part (reference to the instruction manual) Input Voltage 400 to 440V/50 Hz, 440 to 480V/60 Hz
CN UX connector U4 (factory setting)
380V/50 Hz (398V or smaller) 380 to 415V/60 Hz (430V or smaller)
U2
5) Reference to the IEC 61800-3 (5.2.3) 6) Input power: 85%
8
-Frequency :+5 to -5%
Page 9
TM
AF-300 G11 Specifications Dimensions .25 - 30 Hp 4.34(110)
0.28(7)
Fig. 2
D
3.78(96)
D1 0.24(6)
0.28(7)
0.28(7) 2-ø”0.24(ø”6)
0.28(7)
5.91(150) 0.28(7)
2.42 (61.5)
2-ø”0.24(ø”6)
Auxiliary control power supply terminals (M3, 5)
0.28(7)
D2
Main circuit terminals (M4)
D3
0.61(15.5)
NP
0.61(15.5) 1.56(39.5)
9.69(246) 10.25(260)
Control circuit terminals (M3) NP
0.24(6)
0.24(6)
3.43(87) 0.28(6)
0.31(8)
3-ø”0.87(ø”22) Wire inlet knock out hole
1.22(31) 1.73(44)
D1
D2
D3
D4
1/4, 1/2 HP
1.44 (36.5)
3.15 (80)
3.70 (94)
2.81 (71.5)
1 HP
5.71 (145)
2.03 (51.5)
3.74 (95)
4.29 (109)
3.41 (86.5)
0.31(8) 3-ø”0.87(ø”22) Wire inlet Knock out hole
3.92(99.5)
D 5.12 (130)
4.29(109)
1.22(31)
1.06(27) D4 Type
3.74(95)
0.28(7)
9.69(246)
Main circuit terminals (M3, 5)
10.25(260)
Control circuit terminals M3
5.71(145)
5.35(136) 0.28(7)
Fig. 1
2 to 5 Hp
0.47(12)
Fig. 4
0.47(12)
8.66(220)
7.68(195) 4.09(104) 0.44(11)
7.72(196)
2-ø”0.39(ø”10)
9.84(250) 8.90(226)
0.47(12)
2-ø”0.39(ø”10)
0.39(10)
0.47(12) 7.68(195) 4.17(106) 0.44(11)
Fig. 3
0.39(10)
Control circuit terminals
5.49(139.5) 0.44(11)
1.81(46)
5.67(144)
Main circuit terminals (M5)
NP
0.39(10)
14.88(378) 15.76(400)
Auxiliary control power supply terminals (M3, 5)
6.26(159) 0.31(8)
2-ø”1.34(ø”34) Wire inlet knock out hole
2.17(55) 2.42(61.5)
2.54(64.5)
7 to 10 Hp
6.26(159) 0.31(8)
ø”1.34(ø”34) Wire inlet knock out hole
2-ø”1.65(ø”42) Wire inlet knock out hole
5.75(146)
5.51(140)
ø”1.06(ø”27) Wire inlet knock out hole
5.06(128.5) 5.12(130)
0.39(10)
2.07(52.5)
0.44(11)
Main circuit terminals (M5)
2.28(58)
Control circuit terminals (M3) NP
Auxiliary control power supply terminals (M3, 5)
10.25(260)
9.37(238)
(M3)
15 to 30 Hp
9
Page 10
TM
AF-300 G11 Specifications Dimensions NEMA 1 Surface Mount
230V SERIES NEMA 1 HP 40 HP 50 HP
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
16.9 (430) 22.8 (580)
20.01 (510) 26 (660)
W3 –
W4 13.5 (342) 14.9 (377)
60 HP
H1 20.9 (530) 23.4 (595) 28.3 (720)
DIMENSIONS inches (mm) H2 H3 H6 H7 H9 19.7 20.2 0.4 7.1 3 (500) (512) (9) (180) (75) 22.2 22.7 7.9 (565) (577) (200) 27.2 27.6 (690) (702)
H10 29.7 (755) 33.1 (840) 38 (965)
D 10 (255) 10.6 (270)
33.5 (850)
27 (685) 32.1 (815)
41.3 (1050) 50.4 (1280)
11.2 (285) 14.2 (360)
H1 20.9 (530)
DIMENSIONS inches (mm) H2 H3 H6 H7 H9 19.7 20.2 0.4 7.1 3 (500) (512) (9) (180) (75)
H10 29.7 (755)
D 10 (255) 10.6 (270)
25.8 (655)
24.6 (625)
25.1 (637)
34.6 (880)
28.3 (720) 28 (710) 38 (970)
27.2 (690) 26.6 (675) 37 (935)
27.6 (702) 27 (685) 37 (945)
D2 0.2 (4)
D3 5.7 (145)
D4 4.1 (105)
8.7 (220)
3.6 (91) 6.5 (166)
D3 5.7 (145)
D4 4.1 (105)
6.9 (175) 9 (220)
4.7 (121) 7 (166)
Mtg. Bolts M8
75 HP 100 HP 125 HP
11.4 (290)
21 (533) 26.9 (683)
27.4 (695) 32.5 (825)
0.5 (13)
11.1 (283) 15.1 (383)
3.3 (83)
M12
Wt. Lb (kg) 70 (32) 86 (39) 106 (48) 110 (50) 172 (78) 282 (128)
460V SERIES NEMA 1 HP 40 HP 50 HP
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
W3 –
W4 13.5 (342) 14.9 (377)
60 HP
D2 0.2 (4)
Mtg. Bolts M8
75 HP 100 HP 125 HP 150 HP 200 HP 250 HP 300 HP 350 HP 400 HP 450 HP
10
16.9 (430)
22.8 (580)
20.0 (510)
26 (660)
21 (533)
11.4 (290)
26.9 (683)
0.5 (13)
7.9 (200) 8.2 (208) 13 (333) 15.1 (383)
38 (965) 3.3 (83) 53.1 (1350) 55.1 (1400)
12.4 (315) 14.2 (360)
M12
Wt. Lb (kg) 70 (32) 82 (37) 95 (43) 97 (44) 115 (52) 174 (79) 245 (111) 337 (153)
Page 11
TM
AF-300 G11 Specifications Dimensions Open Type Surface Mount
[230V SERIES] HP 230V W 40 HP 13.4 (340) 50 HP 14.8 (375) 60 HP
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
16.9 (430) 22.8 (580)
20.1 (510) 26 (660)
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
W3
H 21.7 (550) 24.2 (615) 29.1 (740)
H1 20.9 (530) 23.4 (595) 28.3 (720)
Through Panel Mount
DIMENSION Inch (mm) H2 H3 H4 19.7 20.2 0.5 (500) (512) (12) 22.2 22.7 (565) (577) 27.2 27.6 (690) (702)
H5 1 (25)
H6 0.4 (9)
D 10 (255) 10.6 (270)
1.3 (33)
0.5 (13)
11.2 (285) 14.2 (360)
D1 5.7 (145)
D2 0.2 (4)
C 0.4 (10)
Mtg. Bolts M8
75 HP 100 HP
20.9 (530) 125 HP 26.8 (680) [460V SERIES] HP 460V W 40 HP 13.4 (340) 50 HP 14.8 (375) 60 HP
W3
29.5 (750) 34.6 (880)
27 (685) 32.1 (815)
27.4 (695) 32.5 (825)
33.5 (850)
H 21.7 (550)
H1 20.9 (530)
26.6 (675)
25.8 (655)
24.6 (625)
25.1 (637)
29.1 (740)
28.3 (720) 28 (710) 38.2 (970)
27.2 (690) 26.6 (675) 36.8 (935)
27.6 (702) 27 (682) 37.2 (945)
0.6 (16)
DIMENSION Inch (mm) H2 H3 H4 19.7 20.2 0.5 (500) (512) (12)
0.6 (15)
M12
8.7 (220)
H5 1 (25)
H6 0.4 (9)
D 10 (255) 10.6 (270)
D1 5.7 (145)
1.3 (33)
0.5 (13)
12.4 (315) 14.2 (360)
6.9 (175) 8.7 (220)
D2 0.2 (4)
C 0.4 (10)
Mtg. Bolts M8
75 HP 100 HP 125 HP 150 HP 200 HP 250 HP 300 HP 350 HP 400 HP 450 HP
20.9 (530)
16.9 (430)
20.1 (510) 39.4 (1000)
26.8 (680)
22.8 (580)
26 (660)
11.4 (290)
0.6 (16)
0.6 (15)
M12
Weight Lb (kg) 64 (29) 79 (36) 97 (44) 101 (46) 154 (70) 253 (115) Weight Lb (kg) 64 (29) 75 (34) 86 (39) 88 (40) 106 (48) 154 (70) 220 (100) 308 (140)
11
Page 12
TM
AF-300 G11 Specifications Plug-in Terminal Strip Assignments
30A Y5A CMY Y3 Y1 C1 FMA FMP PLC X1 X2 X3 X4 X5 X6 X7 X8 X9 30C 30B Y5C Y4 Y2 11 12 13 V2 CM CM FWD REV P24 P24 DX DX SD
Classification
Terminal Symbol
Terminal Name
Function
Analog input
13
Potentiometer power supply
Used for +10V DC power supply for frequency setting POT (resistance of 1 to 5k Ohm)
12
Voltage input
① Frequency is set according to the analog input voltage supplied from an external circuit. - 0 to +10V DC / 0 to 100% - Reversible operation using positive and negative signals: 0 to +/- 10V DC / 0 to 100% - Reverse operation: +10 to 0V DC / 0 to 100% ② The feedback signal for PID control is input. ③ The analog input value from the external circuit is used for torque control * Input resistance: 22 k Ohm
V2
Voltage input supplied from an external circuit.
¨ Frequency is set according to the analog input voltage - 0 to +10V DC/0 to 100% - Reverse operation: +10 to 0V DC/0 to 100% * Use only one terminal - V2 or C1 alternatively. * Input resistance: 22 k Ohm
C1
Current input
① Frequency is set according to the analog input current supplied from an external circuit. - 4 to 20mA DC / 0 to 100% - Reverse operation: 20 to 4mA DC / 0 to 100% ② The feedback signal for PID control is input. ③ PTC thermistor input
* Use only one terminal - V2 or C1 alternatively * Input resistance: 250 Ohm 11
12
Analog input common
Common terminal for analog input signals
Page 13
TM
AF-300 G11 Specifications
Digital input
FWD
Forward operation / Stop command
Used for forward operation (when FWD-CM is on) or deceleration and stop (when FWD-CM is off)
REV
Reverse operation / Stop command
Used for reverse operation (when REV-CM is on) or deceleration and stop (when REV-CM is off)
X1
Digital input 1
The coast-to-stop command, external alarm, alarm reset, multistep frequency selection, and other functions (from an external circuit) can be assigned to terminals X1 to X9. For details, see "Setting the Terminal Functions E01 to E09" in Section 5.2 Function Explanation in the Instruction Manual. <Specifications of digital input circuit> Item Operating voltage
Analog output min. 0V 22V typ. 24V 3.2mA max. 2V 27V 4.5mA 0.5mA
X2 X3 X4 X5 X6 X7 X8 X9
Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital input 6 Digital input 7 Digital input 8 Digital input 9
P24 PLC
Control Unit power Supply PLC signal power
+24VDC power supply for control input. Maximum output current = 100mA Used to connect power supply for PLC output signals; rated voltage = 24 VDC (22 to 27) at sink logic operation.
CM
Digital input common
Common terminal for digital input signals and P24
FMA
Analog monitor
Outputs monitor signal using analog DC voltage 0 to +10V DC. The signal indicates one of the following: - Output frequency (before slip compensation) - Load factor - Output frequency (after slip compensation) - Power consumption - Output current - PID feedback value - Output voltage - PG feedback value - Output torque - DC link circuit voltage * Connectable impedance: min. 5kW
Frequency monitor (pulse waveform output)
Outputs a monitor signal using the pulse waveform. This signal has the same function as the FMA signal.
(11: common terminal)
Pulse output
ON OFF ON OFF
FMP (CM: Common terminal)
Operating current Allowable leakage current
13
Page 14
TM
AF-300 G11 Specifications Transistor
Relay output
Communication
Y1
A running signal, frequency equivalence signal, overload early warning output signal, and other signals from the drive are output (as transistor output) to arbitrary ports. For details, see "Setting the Terminal Functions E20 to E23" in Section 5.2 Function Explanation In the Instruction Manual. * <Specifications of transistor output circuit>
Item Operating voltage
ON OFF ON OFF min. – – – – typ. 1V 24V – – max. 2V 27V 50 mA 0.1 mA
Y2 Y3 Y4
Transistor output 2 Transistor output 3 Transistor output 4
CME
Transistor output common
30A,30B,30C
Alarm outputs for any fault.
Y5A,Y5C
Multi-purpose signal relay outputs
These signals can be output similar to the Y1 to Y4 signals above. The contact rating for any fault is the same as that of the alarm output above.
DX+,DX–
RTU communication
Input / output signal terminals for RTU communication input / output Up to 31 inverters can be connected using the daisy chain method.
SD
Communication cable shield connection terminal
Terminal for connecting the cable shield. The terminal is electrically floating.-
14
Transistor output 1
GET-AF-300 G11 tech
Maximum load current Leakage current
Common terminal for transistor output signals. This terminal is isolated from terminals (CM) and [11]. If the drive is stopped by an alarm (protective function), the alarm signal is output from the relay contact output terminal (1SPDT). Contact rating: 250 VAC, 0.3A,cosØ = 0.3, 48 VDC, 0.5A for CE Marking An excitation mode (excitation at alarm occurrence or at normal operation) can be selected.