Page 151

Name Type Function Specifications

Relay Output Card Card type OPCG11SRY Unit type • Includes 4 relay output circuits • Converts transistor output signals from drive control output terminals Y1 to Y4 to relay (1SPDT) output signals. Input None Output Four-channel contact (12 terminals from Y1A to Y4C) 250 VAC, 0.3A, ocs dia. = 0.3 Power source The power source to drive the relay card is supplied from the drive.

Connection diagram

+ 13Vdc

+ 24Vdc

Y1A

RY Y1B 5G

CM +13Vdc

Y1C

+24Vdc

Y2A Connector

RY Y2B CM

5G +13Vdc

Y2C

+24Vdc

Y3A

RY Y3B 5G

CM +13Vdc

Y3C

+24Vdc

Y4A

RY Y4B 5G CM

Remarks

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

13-7

Y4C

Page 152

Notes

13-8

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 153

14. Electromagnetic Compatibility (EMC) 14.1 General In accordance with the provisions described in the European Commission Guidelines Document on Council Directive 89/336/EEC, GE Fuji has chosen to classify the AF-300 G11 range of Drives as “Complex Components”. Classification as a “Complex Components” allows a product to be treated as an “apparatus”, and thus permits compliance with the essential requirements of the EMC Directive to be demonstrated to both an integrator of AF-300 G11 drives and to his customer or the installer and the user. AF-300 G11 drive is supplied ‘CE-marked’, signifying compliance with EC Directive 89/336/EEC when fitted with specified filter units installed and earthed in accordance with this sheet. This Specification requires the following performance criteria to be met. EMC product standard EN61800-/13/1997 Immunity: Second environment (Industrial environment) Emision: First environment (Domestic environment) Finally, it is the customer’s responsibility to check whether the equipment conforms to EMC directive. 14.2 Recommended Installation Instructions It is necessary that to conform to the EMC Directive, these instructions must be followed. Follow the usual safety procedures when working with electrical equipment. All electrical connections to the filter, Drive and motor must be made by a qualified electrical technician. 1) Use the correct filter according to Table on page 6-39. 2) Install the Drive and filter in the electrically shielded metal wiring cabinet. 3) The back panel of the wiring cabinet should be prepared for the mounting dimensions of the filter. Care should be taken to remove any paint etc. from the mounting holes and face area of the panel. This will ensure the best possible grounding of the filter. 4) Use the shield cable for the control , motor and other main wiring which are connected to the Drive. These shields should be securely grounded. 5) It is important that all wire lengths are kept as short as possible and that incoming mains and outgoing motor cables are kept well separated. “ To minimize the conducted radio disturbance in the power distribution systems, the length of the motor-cable should be as short as possible. “ 6) In the case where a ferrite ring is provided with the filter, fit the ferrite ring so the conductors pass through the center of the ferrite. Wire the cable according to Fig.6 or Fig.7 , paying attention to the applied Drive type.

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

14-1

Page 154

Applied Drive AF-300G11 / AF-300 P11 [Hp] Max. rated voltage 3 Phase 230 VAC Tested Motor Filter Type Cable Length G11 (Fuji model #) Rated EN55011 EN55011 Current Class B Class A 0.25 EFL075SP2 0.5 6A (EFL-0.75SP-2) 1 2 EFL370SP2 3 164 ft 25A (EFL-3.7SP-2) 5, (50m) 7.5 EFL750SP2 50A 10 (EFL-7.5SP-2) 15 EFL150SP2 100A 20 (EFL-15SP-2) 25 EFL220SP2 150A 30 (EFL-22SP-2) 40 50 60 75 100 125

RF3180F11 (RF3180-F11) RF3280F11 (RF3280-F11)

180A

400A, RF3400F11 (RF3400-F11)

15 20 25 30

EFL150G114 (EFL-15G11-4) EFL220G114 (EFL-22G11-4)

50A

40

RF3100F11 (RF3100-F11)

100A

400 450 500 600

328 Ft (100m)

164 ft (50m)

72A

RF3180F11 (RF3180-F11)

180A

RF3280F11 (RF3280-F11)

280A

RF3400F11 (RF3400-F11)

400A

RF3880F11 (RF3880-F11)

Dimensions L x W x H (mm)

Mount. Dim. Y x X (mm)

Ferrite Total Ring (Qty) Wt. (lb)

9.57 x3.35x3.66 (243x85x93)

8.98x2.32 (228x59)

OF1 [1]

3.3

9.17x4.13x5.35 (233x105x136)

8.46x 3.15 (215x80)

OF2 [1]

5.5

10.75x4.72x6.22 (273x120x158)

10x3.74 (254x95)

OF2 [1]

11.0

20.2x8.07x7.6 (513x205x193)

19.17x6.30 (487x160)

OF3 [1]

44.1

19.49x7.87x6.3 (495x200x160)

18.4x6.53 (468x166), 48.7

60, 48.7

120 220

280A

[HP] Max. rated voltage 3 Phase 480 VAC 0.5 EFL075G114 5A 1 (EFL-0.75G11-4) 2 EFL400G114 3 12A (EFL-4.0G11-4) 5 7.5 33 ft EFL750G114 10 (10m) 35A (EFL-7.5G11-4)

50 60 75 100 125 150 200 250 300 350

RFI Filter Data

800A

23.11x9.84x8.07 (587x250x205)

22.05x3.35 (560x85), 110

12.6x4.56x1.65 (320x116x42)

11.54x3.54 (293x90), 2.0

12.6x6.1x1.77 (320x155x45)

11.54x4.13 (293x105), 2.6

13.43x8.86x1.87 (341x225x47.5)

12.24x6.57 (311x167), 4.0

19.69x9.84x2.76 (500x250x70)

17.68x7.28 (449x185), 7.9, 8.8

17.13x7.87x5.19 (435x200x130)

16.06x6.54 (408x166), 28.6

19.49x7.87x6.3 (495x200x160), 328 ft (100m)

23.11x9.84x8.07 (587x250x205)

27.09x14.33x7.09 (688x364x180)

14-2

18.4x6.53 (468x166)

22.05x3.35 (560x85)

25.51x5.91 (648x150)

Watt loss [W] 0.4 1.4 5.1 3.9 8.2 21 24 40 42 68 74 99

0.8 3.1 3.1 6.9 18 10 17 24 29 49 47 62

48.7

60, 84.8

120, 110

220, 130

180

142

Fig. 1 Separate Type

Fig. 3 Separate Type

Fig. 4 Separate Type

Fig. 2 Separate/ Integral Type

21, F200 160 [3]

Note

180

Fig. 3 Separate Type

Fig. 4 Separate Type

Fig. 5 Separate Type

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 155

Ferrite Ring Dimensions : Inches (mm) Part No. D H T OF1 0.98 (25) 2.01 (51) 0.67 (17) OF2 1.61 (41) 2.80 (71) 0.71 (18) OF3 2.83 (72) 3.94 (100) 1.06 (27)

Figure 1

Figure 2

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

14-3

Page 156

W

W1

Dimensions : Inches (mm) H

H1

D

RF3100-F11

7.87 (200)

6.54 (166)

17.1 (435)

16.1 (408)

5.12 (130)

RF3180-F11

7.87 (200)

6.54 (166)

19.5 (495)

18.4 (468)

6.30 (160)

Filter Type

Figure 3 Outline Dimensions (RF3100-F11, RF3180-F11)

Figure 4 Outline Dimensions (RF3280-F11, RF3400-F11)

14-4

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 157

Figure 5 Outline Dimensions (RF3880-F11)

Figure 6

230V all Hp 460V less than 350 Hp

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

14-5

Page 158

Figure 7

AF-300 G11 460V 400 Hp and higher

14-6

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 159

This page is a scan with no text; see it in the PDF.

Page 160

GE Fuji Drives USA

GEI-100363C 000914 FERGADV

GE Fuji Drives USA, Inc. 1501 Roanoke Blvd. Suite 435 Salem, VA 24153 1-800-543-6196 www.GEindustrial.com

GE Fuji Drives America, S.A. de C.V. Ave. La Sierra 1401 Parque Industrial La Silla Guadalupe, N.L. Mexico 67190