Page 1 of AF-300 G11 User's Guide

Manual · GE

AF-300 G11 User's Guide

Manual160 pagesPDF 2.8 MB

User's guide for the GE Fuji AF-300 G11 AC drive: installation, wiring, keypad operation, function settings, troubleshooting and specs.

Download the PDF2.8 MB

Covers · 3 models

The models it covers

Summary

What is in it

User's guide from GE Fuji Drives USA for the AF-300 G11 drive, made to run 3-phase induction motors on 230V and 460V systems. It covers receiving and handling, installation and wiring of the main circuit and control terminals, the keypad panel and its menus, the full function list with explanations, protective functions and troubleshooting, maintenance and inspection, replacement parts, specifications and outline dimensions, RS485 Modbus RTU serial communication, options and EMC installation.

Its parts

  1. Before Using This Product
  2. Installation Environment and Connection
  3. Operation
  4. Keypad Panel
  5. Function Selection
  6. Protective Operations
  7. Troubleshooting
  8. Maintenance and Inspection
  9. Warranty Parts and Service
  10. Replacement Parts
  11. Specifications
  12. RS485 Modbus RTU Serial Communications
  13. Options
  14. Electromagnetic Compatibility (EMC)

From the manual

Key facts from this manual

Each line names its page in the PDF.

GE Fuji Drives USA user's guide (data dated 9/00) for the AF-300 G11 AC drive. It takes the reader through receiving and wiring the drive, using the keypad panel, reading alarm codes and troubleshooting trips, ordering replacement parts, setting up RS485 Modbus RTU communication and choosing option cards.

Read for this summary: pages 3, 15 to 16, 26 to 27, 39, 101 to 105, 119 to 123, 137 and 145 of 160.

Overcurrent codes
OC1, OC2, OC3: overcurrent during acceleration, deceleration, constant speed; OU1, OU2, OU3: overvoltage in the same phases p. 101
Thermal fault codes
OH1 heat sink overheating, OH2 external alarm, OH3 internal overheating, dbH braking resistor overheating, OL1/OL2 motor 1/2 overload, OLU inverter overload p. 101
Other fault codes
LU undervoltage, Lin input phase loss, EF ground fault, FUS DC fuse open, Er1 memory error, Er2 keypad communication error, Er8 RS485 (Modbus RTU) error p. 101
Serial link
EIA/RS485, Modbus RTU slave; 19200, 9600, 4800, 2400 bits/s; half duplex; terminals DX+, DX-, SD p. 137
Modbus functions
03 Read Holding Registers, 06 Preset Single Register, 16 Preset Multiple Registers (16 registers maximum) p. 137
Terminating resistor
1/2 W, 120 ohm, needed for RS485 RTU; packed separately for 30 Hp or less, internal (jumper J2 ON) for 40HP or more p. 15
Keypad panel
30 Hp and below: TPAG11S (NEMA 1) or TPAG11S4 (NEMA 4, 12); 40 Hp and above: TPAG11S4 p. 119, 120, 121, 122
Main control card
G11CPCBB1 for 30 Hp and below; EP4113B1 for 40 Hp and above p. 119, 120, 121, 122
Option cards
OPCG11SRY relay output, OPCG11SDIO digital interface, OPCG11SAIO analog interface, OPCG11SPG and OPCG11SPG2 PG feedback, OPCG11SSY synchronized operation, OPCG11SCIO interface p. 145
Network cards
Serial communication cards for LonWorks, Profibus-DP, Device Net, CAN, Modbus plus, Interbus-S and Genius p. 145
Option mounting
Two internal cards: location A under the main cover, location B under the keypad; one per location p. 145
Main terminals
L1/R, L2/S, L3/T power; U, V, W motor; R0, T0 auxiliary control power; P1, P(+) DC reactor; P(+), DB braking resistor; P(+), N(-) DC link; G ground p. 26
DC reactor
Supplied as a separately mounted component with drives rated 100 Hp and larger p. 15, 27
Braking
10 Hp or less: built-in braking resistor on P(+) and DB; 15 Hp or more: external braking unit and resistor (options) p. 27

What this manual walks you through

  • Checking the delivery against the ratings nameplate p. 15
  • Connecting the main circuit and ground terminals p. 26
  • Motor cable length limits by motor insulation level p. 26
  • Wiring a DC reactor, braking resistor or braking unit p. 27
  • Using the keypad panel keys and displays p. 39
  • Alarm codes and their causes p. 101
  • Resetting a trip p. 102
  • Troubleshooting overcurrent, ground fault, overvoltage, low voltage, overheating and overload trips p. 103, 104, 105
  • Ordering replacement parts for 230 VAC and 460 VAC drives p. 119, 120, 121, 122, 123
  • Connecting the RS485 Modbus RTU link p. 137

Good to know

  • Main circuit power should start or stop the drive only if absolutely necessary, and not more than once an hour. p. 26
  • Do not connect a power factor correction capacitor or surge absorber to the drive output. p. 26
  • Resetting an alarm with the run command ON restarts the drive suddenly; turn the run command off first. p. 102
  • Ground fault detection works only on drives of 40 Hp or more; a separate ground-fault relay or breaker is needed where protection of people or property is required. p. 101
  • Connecting P(+) to N(-), or connecting the braking resistor directly, burns up the resistor. p. 27

Questions this manual answers

What does alarm OC1 mean on an AF-300 G11?

OC1 is overcurrent during acceleration. The troubleshooting chart checks for a shorted or grounded motor output, excessive load, torque boost and a too-short acceleration time. p. 101, 103

How do I reset a trip on the AF-300 G11?

Remove the cause, then press RESET on the keypad or pulse the RST terminal OFF-ON-OFF, with the run command set to OFF. p. 102

How is Modbus RTU set up on the AF-300 G11?

Wire shielded cable to DX+, DX- and SD and set the address, baud rate and error response with function codes H30 to H39. p. 137

Does the AF-300 G11 need a terminating resistor for RS485?

Yes, a 1/2 W, 120 ohm resistor. It is packed separately for 30 Hp or less and built in on 40HP or more, connected with jumper J2. p. 15

What is the AF-300 G11 keypad part number?

TPAG11S (NEMA 1) or TPAG11S4 (NEMA 4, 12) for drives of 30 Hp and below; TPAG11S4 for 40 Hp and above. p. 119, 120, 121, 122

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. AF-300 G11User's Guide1
    1. 1. Before Using This Product15
    2. 2. Installation Environment and Connection19
    3. 3. Operation37
    4. 4. Keypad Panel39
    5. 5. Function Selection55
    6. 6. Protective Operations101
    7. 7. Troubleshooting103
    8. 8. Maintenance and Inspection111
    9. 9. Warranty Parts and Service117
    10. 10. Replacement Parts119
    11. 11. Specifications125
    12. 12. RS485 Modbus RTU Serial Communications137
    13. 13. Options145
    14. 14. Electromagnetic Compatibility (EMC)153

From the PDF’s own bookmarks.

The whole text · 16 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160

The file

Revision and size

Part no.GEI-100363C
Revision9/00
PublisherGE Fuji Drives USA
Pages160
PDF2.8 MB
TextText from the PDF itself; pages 1 and 67 are scans, read by OCR, which may hold reading errors.
GEI-100363C

The first pages · 3 of 160

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 160
Page 2
Page 2of 160
Page 3
Page 3of 160

More documents · 1

For the same models