Manual · GE
AF-300 G11 User's Guide
Manual160 pagesPDF 2.8 MB
User's guide for the GE Fuji AF-300 G11 AC drive: installation, wiring, keypad operation, function settings, troubleshooting and specs.
Covers · 3 models
The models it covers
Summary
What is in it
User's guide from GE Fuji Drives USA for the AF-300 G11 drive, made to run 3-phase induction motors on 230V and 460V systems. It covers receiving and handling, installation and wiring of the main circuit and control terminals, the keypad panel and its menus, the full function list with explanations, protective functions and troubleshooting, maintenance and inspection, replacement parts, specifications and outline dimensions, RS485 Modbus RTU serial communication, options and EMC installation.
Its parts
- Before Using This Product
- Installation Environment and Connection
- Operation
- Keypad Panel
- Function Selection
- Protective Operations
- Troubleshooting
- Maintenance and Inspection
- Warranty Parts and Service
- Replacement Parts
- Specifications
- RS485 Modbus RTU Serial Communications
- Options
- Electromagnetic Compatibility (EMC)
From the manual
Key facts from this manual
Each line names its page in the PDF.
GE Fuji Drives USA user's guide (data dated 9/00) for the AF-300 G11 AC drive. It takes the reader through receiving and wiring the drive, using the keypad panel, reading alarm codes and troubleshooting trips, ordering replacement parts, setting up RS485 Modbus RTU communication and choosing option cards.
- Overcurrent codes
- OC1, OC2, OC3: overcurrent during acceleration, deceleration, constant speed; OU1, OU2, OU3: overvoltage in the same phases p. 101
- Thermal fault codes
- OH1 heat sink overheating, OH2 external alarm, OH3 internal overheating, dbH braking resistor overheating, OL1/OL2 motor 1/2 overload, OLU inverter overload p. 101
- Other fault codes
- LU undervoltage, Lin input phase loss, EF ground fault, FUS DC fuse open, Er1 memory error, Er2 keypad communication error, Er8 RS485 (Modbus RTU) error p. 101
- Serial link
- EIA/RS485, Modbus RTU slave; 19200, 9600, 4800, 2400 bits/s; half duplex; terminals DX+, DX-, SD p. 137
- Modbus functions
- 03 Read Holding Registers, 06 Preset Single Register, 16 Preset Multiple Registers (16 registers maximum) p. 137
- Terminating resistor
- 1/2 W, 120 ohm, needed for RS485 RTU; packed separately for 30 Hp or less, internal (jumper J2 ON) for 40HP or more p. 15
- Keypad panel
- 30 Hp and below: TPAG11S (NEMA 1) or TPAG11S4 (NEMA 4, 12); 40 Hp and above: TPAG11S4 p. 119, 120, 121, 122
- Main control card
- G11CPCBB1 for 30 Hp and below; EP4113B1 for 40 Hp and above p. 119, 120, 121, 122
- Option cards
- OPCG11SRY relay output, OPCG11SDIO digital interface, OPCG11SAIO analog interface, OPCG11SPG and OPCG11SPG2 PG feedback, OPCG11SSY synchronized operation, OPCG11SCIO interface p. 145
- Network cards
- Serial communication cards for LonWorks, Profibus-DP, Device Net, CAN, Modbus plus, Interbus-S and Genius p. 145
- Option mounting
- Two internal cards: location A under the main cover, location B under the keypad; one per location p. 145
- Main terminals
- L1/R, L2/S, L3/T power; U, V, W motor; R0, T0 auxiliary control power; P1, P(+) DC reactor; P(+), DB braking resistor; P(+), N(-) DC link; G ground p. 26
- DC reactor
- Supplied as a separately mounted component with drives rated 100 Hp and larger p. 15, 27
- Braking
- 10 Hp or less: built-in braking resistor on P(+) and DB; 15 Hp or more: external braking unit and resistor (options) p. 27
What this manual walks you through
- Checking the delivery against the ratings nameplate p. 15
- Connecting the main circuit and ground terminals p. 26
- Motor cable length limits by motor insulation level p. 26
- Wiring a DC reactor, braking resistor or braking unit p. 27
- Using the keypad panel keys and displays p. 39
- Alarm codes and their causes p. 101
- Resetting a trip p. 102
- Troubleshooting overcurrent, ground fault, overvoltage, low voltage, overheating and overload trips p. 103, 104, 105
- Ordering replacement parts for 230 VAC and 460 VAC drives p. 119, 120, 121, 122, 123
- Connecting the RS485 Modbus RTU link p. 137
Good to know
- Main circuit power should start or stop the drive only if absolutely necessary, and not more than once an hour. p. 26
- Do not connect a power factor correction capacitor or surge absorber to the drive output. p. 26
- Resetting an alarm with the run command ON restarts the drive suddenly; turn the run command off first. p. 102
- Ground fault detection works only on drives of 40 Hp or more; a separate ground-fault relay or breaker is needed where protection of people or property is required. p. 101
- Connecting P(+) to N(-), or connecting the braking resistor directly, burns up the resistor. p. 27
Questions this manual answers
What does alarm OC1 mean on an AF-300 G11?
OC1 is overcurrent during acceleration. The troubleshooting chart checks for a shorted or grounded motor output, excessive load, torque boost and a too-short acceleration time. p. 101, 103
How do I reset a trip on the AF-300 G11?
Remove the cause, then press RESET on the keypad or pulse the RST terminal OFF-ON-OFF, with the run command set to OFF. p. 102
How is Modbus RTU set up on the AF-300 G11?
Wire shielded cable to DX+, DX- and SD and set the address, baud rate and error response with function codes H30 to H39. p. 137
Does the AF-300 G11 need a terminating resistor for RS485?
Yes, a 1/2 W, 120 ohm resistor. It is packed separately for 30 Hp or less and built in on 40HP or more, connected with jumper J2. p. 15
Contents
Chapters and sections
Each line opens the PDF at its page.
- AF-300 G11User's Guide1
- 1. Before Using This Product15
- 2. Installation Environment and Connection19
- 3. Operation37
- 4. Keypad Panel39
- 5. Function Selection55
- 6. Protective Operations101
- 7. Troubleshooting103
- 8. Maintenance and Inspection111
- 9. Warranty Parts and Service117
- 10. Replacement Parts119
- 11. Specifications125
- 12. RS485 Modbus RTU Serial Communications137
- 13. Options145
- 14. Electromagnetic Compatibility (EMC)153
The whole text · 16 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 150141-150
- Pages 151 to 160151-160
The file