Page 101
6. Protective Operations 6.1 List of Protective Functions In the event of an abnormality in the inverter’s operation, the protective function will activate immediately to trip the inverter and display the alarm name on the LED monitor while the motor coasts to a stop. A list of the alarms with their explanations is included in the table below, and troubleshooting charts in Section 7. Table 6.1.1 List of Alarms and Causes Keypad Panel Display Alarm Name LED LCD OC1 OC DURING ACC OC2 OC DURING DEC Overcurrent OC3 OC AT SET SPD
Ground fault
Cause of Activation During acceleration If the inverter output current momentarily exceeds the overcurrent detection During deceleration level, due to an overcurrent in the motor, or a short-circuit or ground fault in the Running at constant output circuit, the protective function is activated during heavy load. speed If a ground fault in the inverter output circuit is detected, the protective function is activated (for 40 Hp or more only). If a ground fault occurs in an inverter rated at 30 Hp or less, the inverter is protected by the overcurrent protection. If protection against personal injury or property damage is required, install a separate ground-fault protective relay or ground leakage circuit breaker.
EF
GROUND FAULT
OU1
OV DURING ACC
During acceleration
OU2
OV DURING DEC
During deceleration
OU3
OV AT SET SPD
Running at constant speed
Undervoltage
LU
UNDERVOLTAGE
If the DC link voltage in the main circuit falls below the undervoltage detection level (230V series: 400V DC, 460V series: 800V DC) due to a lowered power supply, the output is shut down. If function F14 Restart after momentary power failure was selected, an alarm is not displayed. In addition, if the supply voltage falls to a level unable to maintain control power, an alarm may not be displayed.
Input phase loss
Lin
PHASE LOSS
If input power L1/R, L2/S and L3/T has any phase of the 3 phase power "OPEN" or if there is a significant disparity between the phases, the retifying diodes or smoothing capacitors may be damaged. An Alarm is displayed and the protective function is activated during heavy load.
Overheating of heat sink
OH1
FIN OVERHEAT
If the temperature of the heat sink rises due to a cooling fan failure, or the temperature of the heatsink is too low, the protective function is activated.
External alarm
OH2
EXT ALARM
If the external alarm contacts on the braking unit, braking resistor, or external thermal O/L relay are connected to the control circuit terminals (THR), the contacts will be actuated according to contact signals.
Overheating internally
OH3
HIGH AMB TEMP
Overheating of braking resistor dbH
DBR OVERHEAT
Motor 1 overload
OL1
MOTOR1 OL
Motor 2 overload
OL2
MOTOR2 OL
If the second motor current exceeds the preset level when the operation is switched to drive the second motor, the protective function is activated, provided that electronic thermal O/L relay 2 of function A04 was selected.
Inverter overload
OLU
INVERTER OL
If the output current exceeds the rated overload current, the protective function is activated to provide thermal protection against overheating of the semiconductor elements in the inverter’s main circuit.
Blown fuse
FUS
DC FUSE OPEN
If the fuse in the inverter is blown out following a short-circuit or damage to the internal circuit, the protective function is activated (for 40 Hp or more only).
Memory error
Er1
MEMORY ERROR
If a memory error occurs, such as missing or invalid data, the protective function is activated.
Er2
KEYPD COM ERR
If a communication error or interrupt between the keypad panel and control circuit is detected, the protective function is activated.
Er3 Er4 Er5
CPU ERROR OPTN COM ERR OPTION ERROR
Operating error
Er6
OPR PROCD ERR
Output wiring error
Er7
TUNING ERROR
Modbus RTU error
Er8
RS485 COM ERR
Overvoltage
Keypad panel communication error CPU error Option error
If the DC link voltage in the main circuit exceeds the overvoltage detection level (230V series: 460V DC, 400V series: 800V DC), due to an increase in the regenerating current from the motor, the output is shut down. However, protection against inadvertent overvoltage (e.g., high-voltage line) may not be provided
If the temperature inside the inverter rises due to poor ventilation, etc., the protective function is activated. If electronic thermal O/L relay (for braking resistor) function F13 is selected, the protective function is activated to prevent the resistor from burning due to overheating caused by frequent use of the braking resistor. The protective function is activated if the motor current exceeds the preset level, provided that electronic thermal O/L relay 1 function F10 has been selected.
If a CPU error occurs due to noise, etc., the protective function is activated. Error occurred while using an optional unit. Detects drive operating procedure error during drive startup. FWD or REV connected to terminal CM when Main power is applied to drive (F02 setting 3 or 4). Stop key on keypad is pressed in terminal operation (F02 setting 1 or 3). Detected timed alarm stop command. If there is an open circuit or connection error in the inverter output wiring during an auto-tuning procedure, the protective function is activated. If an error occurs while using Modbus-RTU, the protective function is activated.
Note: Number in fron of Alarm Code indicates multiple alarms. See page 4-15. Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
6-1
Page 102
6.2 Alarm Reset
10ms or more
To release the trip status, enter the reset command by pressing the RESET key on the keypad panel or sending the appropriate signal to the RST terminal after removing the cause of the trip. Since the reset command is an edge operation, input a command sequence such as OFF-ON-OFF as shown in Fig.6-2-1.
Reset command Keypad panel display Alarm output
When releasing the trip status, set the operation command to OFF. If the operation command is set to ON, inverter will start operation after resetting.
OFF
ON
OFF
Normal display Alarm display (Operable) OFF ON OFF
Trip Fig. 6-2-1
WARNING If the alarm reset is activated with the operation signal ON, the inverter will restart suddenly, which may be dangerous. To ensure safety, disable the operating signal when releasing the trip status, as accident may result.
6-2
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 103
7. Troubleshooting 7.1 Activation of Protective Function (1) Overcurrent Overcurrent during acceleration OC1
YES
Remove the short-circuit and ground fault.
Are the motor connecting terminals (U, V, W) short-circuited or grounded? NO
NO
NO
YES
Reduce the load or increase the drive capacity?
Is the load excessive? NO
NO
Overcurrent running at constant speed OC3
Overcurrent during deceleration OC2
NO
Can the torque boost amount be reduced?
NO
Overcurrent during acceleration OC1 YES
YES Reduce the torque boost.
NO
Is the acceleration time setting too short compared with the load? YES
NO
Faulty drive or error due to noise. Consult with GE Fuji.
Is the deceleration time setting too short compared with the load? YES
YES
NO
Has the load changed suddenly? YES
Can the acceleration time setting be prolonged? NO
YES
Prolong time settings.
Can the deceleration time setting be prolonged? NO The braking method requires inspection. Contact GE Fuji.
Reduce the load or increase the drive capacity.
Reduce the load or increase the drive capacity.
(2) Ground fault Remove the grounded part. YES Ground fault EF
Note:
Is a part in the drive output circuit (cable, motor) grounded?
NO
Faulty drive or error due to noise. Contact GE Fuji.
The ground fault protective function is provided only for drive for nominal applied motors rated at 40 HP or more.
(3) Fuse brown Fuse brown FUS
Possible short-circuit within the drive. Contact GE Fuji.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
7-1
Page 104
(4) Overvoltage Overvoltage during deceleration OU2
Overvoltage during acceleration OU1
Reduce the supply voltage to less than the specified upper limit.
NO
Overvoltage running at constant speed OU3
Is the power supply voltage within the specified value? YES
YES
YES
Does OU activate when the load is suddenly removed? NO NO Faulty drive or error due to noise. Contact GE Fuji.
NO
YES
NO
Does the main circuit DC link voltage exceed the protection level? YES
YES Does OU alarm activate when acceleration is completed?
YES YES
Can the acceleration time be prolonged? NO
YES
NO
YES
Can the deceleration time be prolonged?
Prolong.
NO Reduce.
YES Can the amount of load inertia be reduced? NO
NO
NO NO
Is the braking device or DC brake function in use? YES
YES
YES
Consider using a braking system or DC brake function.
Inspect the braking method. Contact GE Fuji.
(5) Low voltage Low voltage LU
Is the power supply voltage within the specified value?
Has a (momentary) power failure occurred?
Reset and restart operation.
Faulty parts or loose connection in the power circuit?
Replace the faulty part and repair the connection.
Is there a load requiring a large starting current within the same power distribution group?
Does LU activate when the circuit breaker or magnetic contactor is switched on?
Is the main circuit DC voltage (between P-N) higher than the detection level specified in Section 6.1.1?
Is power transformer capacity adequate?
The drive may be faulty. Contact GE Fuji.
Modify power distribution system to satisfy the specified value.
7-2
Faulty drive control circuit or error due to noise, etc. Contact GE Fuji.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 105
(6) Overheating internally and overheating of heat sink Over temperature at inside air OH3
(7) External thermal relay tripped External thermal relay tripped OH2
Overheating at heatsink OH1
Check the temperature of the heatsink using the alarm information displayed on the keypad panel.
NO
IIncrease ambient temperature
YES Is PTC operating?
YES Does the heatsink temperature indicate 50°C or lower?
Is the ambient temperature -10°C or lower?
YES
NO
Reduce the load.
Is the external circuit (including constants regular?
NO
NO Set to correct value.
YES
NO
Change to regular external circuit.
YES
Replace the cooling fan.
Faulty drive or error due to noise, etc. Contact GE Fuji.
YES Is the cooling air passage blocked?
Incorrect motor load or inadequate cooling. Check the motor side.
YES
YES
NO Is the cooling fan rotating?
YES
NO Is PTC level H27 set correctly?
NO Is the load excessive?
Is PTC MODE H26 enabled?
Remove obstacles.
NO Is the ambient temperature within the specification?
Faulty drive or error due to noise, etc. Contact GE Fuji.
YES
Is data input to the control terminals THR-X1 to X9? Are alarm signals from external equipment input to the terminals and the CM?
NO Arrange peripheral conditions to meet the specification.
NO
Connect the alarm signal contact.
NO
Remove the cause of alarm function activation.
YES
(8) Drive overload and motor overload Drive overload OLU
Is the alarm function of the external equipment operating correctly?
Motor overload OL1, OL2
YES Do the characteristics of the electronic thermal O/L relay and motor overload match?
NO
Connect a thermal O/L relay externally.
YES Is the electronic thermal O/L relay setting correct?
NO
Set to the correct level.
YES Is the load excessive?
NO
YES
Faulty drive or error due to noise, etc. Contact GE Fuji.
Reduce the load or increase drive capacity.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
7-3
Faulty drive or error due to noise, etc. Contact GE Fuji.
Page 106
(9) Memory error Er1, Keypad panel communication error Er2, CPU error Er3
Er1, 2, 3 indicated. Abnormal display or indication goes out.
(10) Output wiring error
Output wiring error Er7
Remedy faulty parts.
NO Turn the power off then on again after the CHARGE lamp (CRG) goes off.
Are the connectors, plugs, and ICs inserted correctly? Is there noise generating source nearby? YES
Is data displayed on the LED monitor correctly?
NO
Did the error occur during tuning? NO Are the braking unit and braking resistor connected incorrectly?
YES
Connect correctly or replace the cable.
NO
Drive may be faulty. Contact GE Fuji.
YES
YES
Faulty drive or error due to noise, etc. Contact GE Fuji.
Drive is normal. Continue operation.
(11) Input Phase/Loss Is the U, V, W terminal wiring not connected or is there an open circuit?
Input phase loss Lin
YES
Connect correctly or replace the cable.
NO Are all main circuit power supply terminals L1/R, L2/S and L3/T connected to the power supply?
NO
Connect all three phases.
The keypad panel connector is loose.
YES
Secure the connector.
YES
Disable the connection.
NO
YES Are there loose screws on the terminal block?
YES
Tighten the screws on the terminal block.
NO Is there a significant imbalance voltage between phases?
Is connection between control terminals FWD, REV - CM enabled? NO
YES
Faulty drive or error due to noise, etc. Contact GE Fuji.
Faulty drive or error due to noise, etc. Contact GE Fuji.
NO
Faulty drive or error due to noise, etc. Contact GE Fuji.
7-4
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 107
7.2 Abnormal Motor Rotation (1) If motor does not rotate Charge lamp (CRG) lights and LCD moniotr lights up?
Motor does not rotate.
NO
YES Remove the cause of alarm function activation and reset the alarm, then run the motor.
Is the LCD monitor displaying an alarm mode screen? NO
YES
Keyad panel
YES
Does the motor run if FWD or REV is pressed?
NO
NO Press the UP key and set the frequency.
NO
YES Does the motor start when the key UP is pressed? NO
Was the forward or reverse operation command given? YES YES
Has the frequency been set? YES
YES Set the frequency correctly.
NO
Turn on.
NO
Connect.
Drive may be faulty. Contact GE Fuji.
Is external wiring between YES Replace the faulty switch control circuit terminals FWD, or relay. REV - CM connected correctly? NO
NO
YES
Are the frequency limiter (High) and the frequency setting lower than the starting frequency? NO Are the drive output terminals (U, V, W) provided with the proper voltage?
Faulty motor.
Is a jumper or DC reactor connected between terminals P1 and P(+)? YES
Control terminals
NO
Check for problems (low NO voltage, an open phase, a loose connection, poor contact) and remedy accordingly.
Are the voltages at the power terminals (R/L1, S/L2, T/L3) normal?
Is input method from keypad panel or control terminal? If no error is detected, continue operation. YES
Are the circuit breaker and magnetic contactor on the power supply side switched on? YES
Is the external wiring between control terminals 13, 12, 11, and C1 or between X1-X9 and CM for the multi-step frequency selection connected correctly? YES
NO
Correct the wiring error. NO
Replace the faulty frequency setting POT, (VR), signal converter, switch, or relay contacts as required.
Drive may be faulty. Contact GE Fuji.
YES
NO
YES
Excessive load?
Are the cables to the motor connected correctly?
NO
Correct the wiring error.
YES Is the torque boost set correctly? NO
YES
The load is excessive, resulting in motor lock. Reduce the load and check that the brake is released (if a mechanical brake is used.)
Raise the torque boost.
Note: Monitor the operation command or frequency setting values, etc., on the LED or LCD monitor after selecting the respective functions.
The motor does not rotate if the following commands are issued. An operation command is issued while the coast-to-stop or DC braking command is output. A reverse operation command is issued with the • H08 Rev. phase sequence lock• value set ot 1.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
7-5
Page 108
(2) If the motor rotates but the speed does not change
Is the maximum frequency setting too low?
The motor rotates but the speed does not change.
YES
Increase the setting.
NO
YES
Change the setting.
Is the higher or lower frequency limiter activating?
Set the frequency. Keypad panel operation
NO
YES
Pattern operation
Is the timer timing too long? NO YES
Is the pattern operation competed?
Which frequency setting methods used: keypad panel, analog signal, multi-step frequency, or UP/DOWN control? Is the pattern operation activated?
Analog signal
YES Does the speed change when the UP or DOWN is pressed?
Can the frequency setting signal (0 to 10 V, 4 to 20 mA) be changed?
Multi-step frequency UP/DOWN
NO
YES
NO
NO YES
Are the external connections between X1-X9 and CM correct?
Are all acceleration and deceleration times identical?
NO
Correct the connection error.
YES
NO
Are the external connections between control terminals 13, 12, 11 and C1 correct? YES
NO
Are the frequencies for each multi-step frequency different?
NO
Change the frequency setting.
Replace the faulty frequency setting POT (VR) or signal converter as required.
YES
Faulty drive or error due to noise, etc. Contact GE Fuji.
NO
Is the acceleration or deceleration time set too long? YES
Change the time setting to conform to load values.
In the following cases, changing the motor speed is also restricted. Signals are input from control terminals both 12 and C1 when “F01 Frequency command 1” and “C30 Frequency command 2” are set to 3, and there is no significant change in the added value. The load is excessive, and the torque limiting and current limiting functions are activated.
7-6
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 109
(3) If the motor stalls during acceleration
The motor stalls during acceleration.
Is the acceleration time too short?
YES
Prolong the time.
NO Is the inertia moment of the YES motor or the load excessive?
Is a special motor used?
YES
Contact GE Fuji.
NO NO Use a thicker cable between the drive and the motor or shorten the cable length.
YES
Reduce the inertia moment of the load or increase the drive capacity.
Has the motor terminal voltage dropped? NO
Reduce the torque of the load or increase the drive capacity.
YES
Is the torque of the load excessive? NO
Is the torque boost set correctly?
YES
Faulty drive or error due to noise, etc. Contact GE Fuji.
NO
Increase the torque boost.
The motor generates abnormal heat.
Is the torque boost excessive?
YES
Reduce the torque boost.
NO Has the motor been operating continuously at a very low speed?
YES
Use a motor exclusive to the drive.
YES
Reduce the load or increase motor capacity.
NO
Is the load excessive? NO
Is the drive output voltage. Terminals (U, V, W) balanced?
YES
Faulty motor.
NO
Note: Motor overheating following a higher frequency setting is likely the result of the current wave form. Contact GE Fuji.
Faulty drive or error due to noise, etc. Contact GE Fuji.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
7-7
Page 110
Notes
7-8
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA