Page 91
H16 Auto-restart (OPR command selfhold time) H 1 6 S E L F H O L D
T
Setting range: 0.0 to 30.0 seconds, 999 Since the power to an external operation circuit (relay sequence) and the main power to the drive is generally cut off at a power failure, the operation command issued to the drive is also cut off. This function sets the time an operation command is to be held in the drive. If a power failure lasts beyond the self-hold time, power-off is assumed, automatic restart mode is released, and the drive starts operation at normal mode when power is applied again. (This time can be considered to be the allowable power failure time.) If H16 = 999, an operation command will be held until control power in the drive is established or until the main circuit DC voltage is about 0.
The torque command value is +200% when the voltage at Terminal 12 is +10V and is -200% when the voltage is 10V. Under torque control, the torque command value and motor load determine the speed and direction of rotation. When the torque is controlled, the upper frequency limit refers to the lowest value among the maximum frequency, the frequency limiter (upper limiter), and 120 Hz. Maintain the frequency at min. 1/10 of the base frequency because torque control performance deteriorates at lower frequencies. If the operation command goes off during a torque control operation, the operation is switched to speed control and the motor decelerates-to-stop. At this time, the torque control function will not operate.
H19 Active drive
H18 Torque control
H 1 9 A U T
H 1 8 T RQ
Set value
C T R L
This function controls motor torque according to a command value. Note: PG Option Card is required for this function Value 0 1
2
Operation [Related Functions: E01 – E09 = 23] Inactive (operation by frequency command) Torque control active A 0 to +10 V analog voltage input to Terminal 12 and the direction of rotation (FWD or REV) are used for the torque command value. 0 is used for 0 to -10V. Torque control active A -10 to +10V analog voltage input to Terminal 12 and the direction of rotation (FWD or REV) are used for the torque command value.
R E D
0: Inactive 1: Active
This function automatically extends accelerating time by 60 seconds or longer to prevent an inverter trip resulting from a temperature rise in the inverter due to overcurrent. (If the active drive function is activated, the acceleration time will be three times the selected time.)
H20 PID control (mode select) H 2 0 P I D
Set value
MO D E
0: No operation 1: Normal operation 2: Inverse operation
PID control detects the amount of feedback from a sensor and compares it with the target value (e.g., reference temperature). If the values differ, this function produces an output to eliminate the deviation. In other words, this control matches the feedback amount with the target value. This function can be used for flow control, pressure control, temperature control, and other process controls.
Forward or reverse operations can be selected for PID controller output. This enables motor revolutions to be faster or slower according to PID controller output.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-37
Page 92
The target value can be entered using F01, Frequency setting 1, or directly from the keypad panel. For entry from F01, Frequency setting 1, input a signal to the selected terminal. For direct entry from the keypad panel, turn on keypad operation. Select any of the digital Terminals X1 (E01) to X9 (E09) and assign a value of 11 (frequency setting switching).
Only positive values can be input for this feedback amount of PID control. Negative values (e.g., 0 to -10V, 10 to 0V) cannot be input, thereby the function cannot be used for a reverse operation by an analog signal. Feedback signal setting (H21) must be different from the type of setpoint value.
NOTE: For the target value and feedback amount, the process amount can be displayed according to the values set in E40 Display coefficient A, and E41 Display coefficient B.
H21 PID control (feedback signal) H 2 1 F B
S I G N A L
This function selects the terminal, direction of operation, and feedback input. Select a value from the table below according to sensor specifications. Value 0 1 2 3
Description Terminal 12, forward operation, 0 to 10V voltage input Terminal C1, forward operation, 4 to 20mA current input Terminal 12, reverse operation, 10 to 0V voltage input Terminal C1, reverse operation, 20 to 4mA current input
5-38
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 93
H22 PID control (P-gain) H23 PID control (I-gain) H24 PID control (D-gain) These functions are not generally used alone but are combined like P control, PI control, PD control, and PID control. P operation An operation using an output frequency proportional to deviation is called P operation, which outputs an operation amount proportional to deviation, though it cannot eliminate deviation alone.
I operation An operation where the change speed of the output frequency is proportional to the deviation is called an I operation. An I operation outputs an operation amount as the integral of deviation and, therefore, has the effect of matching the feedback control amount to the target value (e.g., set frequency), though it deteriorates response for significant changes in deviation.
H 2 2 P – G A I N
Setting range: 0.01 to 10.0 times P (gain) is the parameter that determines the response level for the deviation of P operation. Although an increase in gain speeds up response, an excessive gain causes vibration, and a decrease in gain delays response.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-39
Page 94
PID control PID control combines the P operation, the I operation which removes deviation, and the D operation which suppresses vibration. This control achieves deviationfree, accurate, and stable responses.
H 2 3 I – G A I N
Setting range: 0.0 (Inactive), 0.1 to 3600 seconds H23 I-gain is used as a parameter to determine the effect of I operation. A longer integration time delays response and weakens resistance to external elements. A shorter integration time speeds up response, but an integration time that is too short causes vibration.
Adjusting PID value Adjust the PID value while monitoring the response waveform on an oscilloscope or other instrument, if possible. Proceed as follows:
D operation An operation where the output frequency is proportional to the deviation differential is called a D operation. It outputs an operation amount as the deviation differential and, therefore, is capable of responding to sudden changes.
Increase the value of H22 P-gain without generating vibration. Decrease the value of H23 I-gain without generating vibration. Increase the value of H24 D-gain without generating vibration. Adjust the response waveform as follows: To remove the overshoot, increase the value of H23 I-gain, then decrease the value of H24 D-gain.
H 2 4 D – G A I N
Setting range: 0.00 (Inactive), 0.01 to 10.0 seconds H24 D-gain is used as a parameter to determine the effect of a D operation. A longer differentiation time causes vibration by P operation quickly attenuating at the occurrence of deviation. Excessive differentiation time could cause vibration. Shortening the differentiation time reduces attenuation at the occurrence of deviation.
To stabilize response quickly, allowing for min. overshoot, : decrease the value of H23 I-gain or increase the value of H24 D-gain.
PI control P operation alone does not remove deviation completely. P + I control (where I operation is added to P operation) is normally used to remove the remaining deviation. PI control always operates to eliminate deviation, even when the target value is changed or there is a constant disturbance. When I operation is strengthened, however, the response for rapidly changing deviation deteriorates. P operation can also be used individually for loads containing an integral element.
To suppress vibration with a period longer than the value of H23 I-gain, increase the value of H23.
PD control If deviation occurs under PD control, an output frequency larger than that of D operation alone occurs rapidly and prevents the deviation from expanding. For a small deviation, P operation is restricted. When the load contains an integral element, P operation alone may allow responses to vibrate due to the effect of the integral element, in which case PD control is used to attenuate the vibration of P operation and stabilize responses. In other words, this control is applied to loads in processes without a braking function.
5-40
To suppress vibration with a frequency roughly equivalent to the value H24 D-gain, decrease the value of H24. If there is residual vibration with 0.0, decrease the value of H22 P-gain.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 95
H25 PID control (Feedback filter) H 2 5 F B
F I L T E R
The figure above for H26 PTC thermistor (Mode select) shows that a 250W resistor and the thermistor (resistance value Rp) are connected in parallel. Hence, voltage Vc1 at Terminal C1 can be calculated using the following formula:
Setting range: 0.0 to 60.0 seconds This filter is for feedback signal input from Terminals 12 or C1. This filter stabilizes operation of the PID control system. A set value that is too large, however, deteriorates response.
H26 PTC thermistor (mode select) H 2 6 P T C
Set value
MO D E
250 • Rp 250 + Rp Vc1 X 10 [V] 250 • Rp 1000+ 250 + Rp The operation level can be set by bringing Rp in the Vc1 calculation formula into the following range. Rp1 < Rp < Rp2
0: Inactive 1: Active
To calculate Rp, use the following formula:
Set this function active when the motor has a PTC thermistor for overheat protection
Rp
Connect the PTC thermistor as shown in the figure below. Turn on switch PTC on the control PCB. The trip mode is activated by OH2: External thermal relay tripped.
Rp1 + Rp2 [Ohm] 2
H28 Droop operation H 2 8 D RO OP
Set value : -9.9Hz to 0.0Hz When two or more drive motors operate a single machine, a higher load is placed on the motor that is rotating the fastest. Droop operation achieves a good load balance by applying drooping characteristics to speed against load variations. Calculate the droop amount using the following formula: Note: Must be 0 setting when using 4-20mA reference or feedback signal and the PTC switch is off.
Droop amount = Base frequency X
H27 PTC thermistor (level select) H 2 7 P T C
Speed droop at rated torque [r/min.] Synchronous speed [r/min.]
L E V E L
Setting range: 0.00 to 5.00V The voltage input to Terminal C1 is compared to the set voltage level. If the input voltage is equal to or greater than the set voltage, H26 PTC thermistor (Mode select) starts. The PTC thermistor has its own alarm temperature. The internal resistance value of the thermistor largely changes at the alarm temperature. The operation voltage level is set using this change in the resistance value.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-41
[Hz]
Page 96
H30 Serial link (Function select) H 3 0 L I N K
Value 0
F U N C
Setting range: 0 to 3
1
Processing at Communication Error Immediate Er 8 trip (forced stop) Continue operation within timer time, Er 8 trip after time expires
2 3
Continue operation and retry within timer time, then invoke an Er 8 trip if a communication error occurs. If an error does not occur, continue operation. Continue operation.
The link function (communication) provides a standard RS485 serial interface and optional fieldbus connections. The serial link function includes: 1) 2) 3)
Monitoring (data monitoring, function data check) Frequency setting Operation command (FWD, REV, and other commands for digital input) 4) Write function data Communication can be enabled and disabled by a digital input. This function sets the serial link function when communication is enabled. Value 0 1 2 3
Frequency Command Disabled Enabled Disabled Enabled
Operation Command Disabled Disabled Enabled Enabled
H 3 3 T I M E R
Setting range: 0 to 60.0 sec. This function sets the error processing timer value. H 3 4 B AU D
R A T E
Setting range: 0 to 3 This function sets the baud rate.
The data monitoring and write functions are always enabled. Disabling communication by a digital input produces the same results as if this function were set to 0. If the bus option is installed, this setting selects the bus function, and the RS485 interface is restricted to monitoring and writing function data. If the bus option is not installed, this setting selects the RS485 function.
Value
Baud Rate
0
19200 bits/s
1
9600 bits/s
2
4800 bits/s
3
2400 bits/s
H 3 5 L E N G T H
This function sets data length.
H31 RS485 (Address) H39 RS485 (Response interval)
Value 0
These functions set the conditions for RS485 RTU serial communication. Set the conditions according to the host device.
Data Length 8 bit
. H 3 6 P AR I T Y
H 3 1 A D D R E S S
This function sets the parity bit
Setting range: 1 to 247
Value
This function sets the station address of RTU. Maximum connected devices is 31 for an RS-485 network. H 3 2 MOD E
O N
E R
Setting range: 0 to 3
Parity Bit
0
None
1
Even
2
Odd
.
These functions configure the drive behavior in the event of a communication error.
H 3 7 S T O P
B I T S
This function sets the stop bit Value
Stop Bit
0
2 bits
1
1 bit
The stop bit is automatically configured by the value of the parity bit. For parity “NONE” the stop bit is 2 bits. For parity “EVEN” or “ODD” the stop bit is 1 bit. 5-42
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 97
H 3 8 N O
R E S
T
Setting range:
0 (no detection) 1 to 60 seconds
In a system where the drive is continuously polled within a specific time, this function detects that access was stopped due to an open circuit or other network fault and results in an Er 8 trip. H 3 9 I N T E R V A L
Setting range: 0.00 to 1.00 second This function sets the time from when a request is issued from the host device to when a response is returned.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-43
Page 98
A: Alternative Motor Parameters ( Motor 2 ) A06 Electronic thermal relay 2 (select)
A01 Maximum frequency 2 A 0 1 M A X
A07 Electronic thermal relay 2 (level)
H z – 2
A08 Electronic thermal relay 2 (Thermal time constant)
This function sets the maximum frequency for Motor 2 output by the drive. It operates the same as F03 Maximum frequency 1. For details, see the explanation for F03.
A 0 6 E L C T R N O L 2 A 0 7 O L L E V E L 2 A 0 8 T I M E C N S T 2
A02 Base frequency 2 A 0 2 B A S E
H z – 2
This function sets the maximum output frequency in the constant torque area for Motor 2 (i.e., output frequency at rated output voltage). It operates the same as F04 Base frequency 1. For details, see the explanation for F04.
V 2
This function sets the rated voltage output to Motor 2. It operates the same as F05 Rated voltage 1. For details, see the explanation for F05.
V – 2
This function sets the maximum drive output voltage for Motor 2. It operates the same as F06 Maximum voltage 1. For details, see the explanation for F06.
A10 Number of motor-2 poles PO L E S
This function sets the number of poles to be driven by Motor 2. It operates the same as P01 Number of Motor 1 poles. For details, see the explanation for P01.
A11 Motor 2 (capacity) A 1 1 M 2 – CA P
A05 Torque boost 2 A 0 5 T RQ
This function sets the torque vector function for Motor 2. It operates the same as F42 Torque vector control 1. For details, see the explanation for F42.
A 1 0 M 2
A04 Maximum Voltage 2 A 0 4 M A X
A09 Torque vector control 2 A 0 9 T RQ V E C T O R 2
A03 Rated Voltage 2 A 0 3 R A T E D
These functions set the function of the electronic thermal overload relay for Motor 2. They operate the same as F10 to F12 Electronic thermal overload relay 1. For details, see the explanations for F10 to F12.
B OO S T 2
This function sets the torque boost function for Motor 2. It operates the same as F09 Torque boost 1. For details, see the explanation for F09.
This function sets the capacity of Motor 2. It operates the same as P02 Motor 1 (Capacity). For details, see the explanation for P02. However, the related motor data functions change to A12 Motor 2 (Rated current), A15 Motor 2 (No-load current), A16 Motor 2 (%R1 setting), and A17 Motor 2 (%X setting).
A12 Motor 2 (Rated current) A 1 2 M 2 – L R
This function sets the rated current for Motor 2. It operates the same as P03 Motor 1 (Rated current). For details, see the explanation for P03.
5-44
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 99
A13 Motor 2 (Tuning) A 1 3 M 2
T U N 1
This function sets online tuning for Motor 2. It operates the same as for P04 Motor 1 (Tuning). For details, see the explanation for P04.
A14 Motor 2 (On-line tuning) A 1 4 M 2
T U N 2
This function sets online tuning for Motor 2. It operates the same as P05 Motor 1 (On-line tuning). For details, see the explanation for P05.
A15 Motor 2 (No-load current) A 1 5 M 2
I O
This function sets the no-load current for Motor 2. It operates the same as P06 Motor 1 (No-load current). For details, see the explanation for P06.
A16 Motor 2 (%R1 setting) A17 Motor 2 (%X setting) A 1 6 M 2 – %R 1 A 1 7 M 2 – %X
These functions set %R1 and %X for Motor 2. It operates the same as P07 Motor 1 (%R1 setting) and P08 Motor 1 (%X setting). For details, see the explanations for P07 and P08.
A18 Slip compensation control 2 A 1 8 S L I P
C OM P 2
This function sets the amount of slip compensation for Motor 2. It operates the same as P09 Slip compensation control. For details, see the explanation for P09.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-45
Page 100