Page 81
E45 LCD monitor (display selection)
E46 LCD monitor (language)
E 4 5 L CD
E 4 6 L AN GU A G E
MN T R
This function selects the items to be displayed on the LCD monitor in operation mode. Value
Display Items
0
Operation status, direction of rotation, operation guide
1
Output frequency before slip compensation, output current, calculated torque in bar graph
Set value: 0 During running
When stopping
This function selects the language for data display on the ELCD4monitor. 6
E
Value 40 7 1 2
Language Japanese English German
Value 3 4 5
Language French Spanish Italian
Note: English language is used for all LCD screens in this manual.
E47 LCD monitor (contrast adjustment) E 4 7 C ON T R A S T
60.00
60.00
RUN
STOP
This function adjusts the LCD contrast. Increase the set value to raise contrast and decrease to lower contrast. FWD
PRG PRG MENU F/D LED SHIFT
Value Screen
Set value: 1 60.00 Hz A % Fout/Iout/TRQ
Full scale value of bar graph Display item Full scale Output frequency Maximum frequency Output current 200% of drive rated value Calculated torque value 200% of motor rated value Note: The scale cannot be adjusted.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-27
0, 1, 2 • • • • • • 8, 9, 10 Low High
Page 82
C: Control Functions of Frequency C01 Jump frequency 1 C02 Jump frequency 2 C03 Jump frequency 3 C04 Jump frequency hysteresis C 0 1 J UM P C 0 2 J UM P C 0 3 J UM P
H z H z H z
C05-C19 Multi-step frequency 1 to 15 C 0 5 M U L T I C 0 6 M U L T I C 0 7 M U L T I C 0 8 M U L T I C 0 9 M U L T I C 1 0 M U L T I C 1 1 M U L T I C 1 2 M U L T I C 1 3 M U L T I C 1 4 M U L T I C 1 5 M U L T I C 1 6 M U L T I C 1 7 M U L T I C 1 8 M U L T I C 1 9 M U L T I
1 2 3
Set value 0 to 400 Hz in 1Hz increments (min.) C 0 4 J UM P
H Y S T R
Set value 0 to 30 Hz in 1Hz increments (min.) This function makes the set frequency jump so that the drive’s output frequency does not match the mechanical resonance point of the load. Up to three jump points can be set.
H z – 1 H z – 2 H z – 3 H z – 4 H z – 5 H z – 6 H z – 7 H z – 8 H z – 9 H z 1 0 H z 1 1 H z 1 2 H z 1 3 H z 1 4 H z 1 5
Set value 0 to 400 Hz In 0.01 Hz increments (min.)
This function is ineffective if jump frequencies 1 to 3 are set to 0 Hz.
Multistep frequencies 1 to 15 can be switched by turning terminal functions SS1, SS2, SS4, and SS8 on and off. (See E01 to E09 for terminal function definitions.)
A jump does not occur during acceleration or deceleration.
OFF is the default value any undefined SS1, SS2, SS4, and SS8 terminals.
➝
Output Frequency (Hz) C13 C12
➝
➝
➝
Related functions: E01 to E09 (Set value: 0 to 3)
C14
➝
C11
➝
➝ ➝
➝
C15
C10
➝
Jump frequency 3
C16
C09
➝
➝ ➝
➝
➝
➝
➝
➝
Jump frequency width Jump frequency width Jump frequency width
➝ ➝
Output frequency (Hz)
➝
If a jump frequency setting range overlaps another range, both ranges are added to determine the actual jump area.
C17 C18
C08
Jump frequency 2
C07
➝
C19
C06
Jump frequency 1 ➝
➝
➝
C05
➝ Set frequency (Hz)
FWD-CM
ON
➝
Output frequency (Hz)
➝
➝
➝
➝
➝
➝ ➝
SS4-CM
Jump frequency 2
SS8-CM
➝
➝
SS2-CM
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
➝ ➝
Actual jump width Jump frequency width
➝ ➝
➝
SS1-CM
ON
ON
ON
Jump frequency 1 ➝
➝
➝ Set frequency (Hz)
5-28
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 83
C20 Jog frequency C 2 0 J OG
H z
Setting range: 0.00 to 400.00 Hz This function sets a frequency for the motor jogging operation, which is different from the normal operation. The jogging frequency is used for operation when the jogging mode signal is received from the keypad panel or control terminal. For details, see the explanations of E01 Terminal X1 to E09 Terminal X9.
C21 Pattern operation (operation selection) C 2 1 P A T T E R N
Pattern operation is an automatic operation according to a preset operation time, direction of rotation, acceleration and deceleration time, and frequency. When using this function, set F01 Frequency setting to 10 (pattern operation). [Related Functions: F01, C30 = 10] The following operation patterns can be selected. Value 0 1 2
Operation Pattern Perform a pattern operation cycle, then stop operation. Perform pattern operation repeatedly. Operation is stopped by the STOP operation. Perform a pattern operation cycle, then continue operation at the last set frequency.
C22-C28 Pattern operation (stage 1 to 7) C 2 2 S T A GE C 2 3 S T A GE C 2 4 S T A GE C 2 5 S T A GE C 2 6 S T A GE C 2 7 S T A GE C 2 8 S T A GE
1 2 3 4 5 6 7
Seven stages are operated in order of function codes, according to the values set in C22 Pattern operation (stage 1) to C28 Pattern operation (stage 7). Each function sets the operation time and the direction of rotation for each stage and assigns values to acceleration and deceleration time. Set or assign item Operation time Rotation direction Acceleration and deceleration time
Value range 0. 00 to 6000s F: Forward (counterclockwise) R: Reverse (clockwise) 1: Acceleration time 1 (F07) Deceleration time 1 (F08) 2: Acceleration time 2 (E10) Deceleration time 2 (E11) 3: Acceleration time 3 (E12) Deceleration time 3 (E13) 4: Acceleration time 4 (E14) Deceleration time 4 (E15) Note: The operation time is represented by the three most significant digits, hence, can be set with only three high-order digits.
Setting example
100
F
3 Acceleration and deceleration time (code): 3 Motor rotating direction: Forward (counterclockwise) Operation time: 100s
Set the operation time to 0.00 for any unused stages, which are skipped during operation. In regard to the set frequency value, the multi-step frequency function is assigned according to the table below. Seven frequencies can be set for C05 Multi-step frequency 1 to C11 Multi-step frequency 7.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-29
Stage No.
Operation Frequency
Stage 1
Multi-step frequency 1 (C05)
Stage 2
Multi-step frequency 2 (C06)
Stage 3
Multi-step frequency 3 (C07)
Stage 4
Multi-step frequency 4 (C08)
Stage 5
Multi-step frequency 5 (C09)
Stage 6
Multi-step frequency 6 (C10)
Stage 7
Multi-step frequency 7 (C11)
Page 84
Pattern operation example Function Value / Operation Frequency
Notes: 1.
C21
1
Selects function
C22 (stage 1)
60.0F2
Multi-step frequency 1 (C05)
C23 (stage 2)
100F1
Multi-step frequency 2 (C06)
C24 (stage 3)
65.5R4
Multi-step frequency 3 (C07)
C25 (stage 4)
55.0R3
Multi-step frequency 4 (C08)
C26 (stage 5)
50.0F2
Multi-step frequency 5 (C09)
C27 (stage 6)
72.0F4
Multi-step frequency 6 (C10)
C28 (stage 7)
35.0F2
Multi-step frequency 7 (C11)
2.
The direction of rotation cannot be reversed by a command issued from the REV key on the keypad panel or Terminal REV. Any reverse rotation commands entered will be canceled. Select forward or reverse rotation by the data in each stage. If the control terminals are used for operation, the self-hold function will not work. Select an alternate type switch when using control terminals. At the end of a cycle, the motor decelerates to stop according to the value set in F08 Deceleration time 1.
C30 Frequency setting 2 C 3 0 F R E Q
The following diagram shows this operation.
CMD
2
For the setting method, see the explanation for F01. Notes: Setting 2, 3, and 7 are inactive. (C1 signals) This function determines the frequency setting method.
C31 Analog input bias adjustment The setting range is -100.0 to +100.0% (in 0.1% increments) of the maximum output frequency.
C32 Analog input gain adjustment The gain adjustment range is 0.0 to 200%. C 3 1 B I A S C 3 2 G A I N
These functions set the gain and bias for analog input Terminals 12 and C1, in conjunction with functions F17 (freq. gain) and F18 (freq. bias). Example:
Running and stopping are controlled by pressing the STOP or FWD keys or by opening and closing the control terminals. When using the keypad panel, the FWD key starts operation. The STOP key pauses stage advance. Pressing the FWD key again will restart operation from the stop point according to the stages. If an alarm stop occurs, press the RESET key to release the drive protective function, then press the FWD key to restart stage advance. If operation is to restart from the first stage, C22 Pattern operation (stage 1), enter a STOP command and press the RESET key. If an alarm stop occurs, press the RESET key to release the protective function, then press the RESET key again. 5-30
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 85
C33 Analog setting signal C 3 3 R E F
F I L T E R
Setting range: 0.00 to 5.00 seconds Analog signals input from Terminals 12, V2 or C1 may contain noise which renders the control unstable. This function adjusts the time constant of the input filter to remove the effects of noise. A value that is set too large delays control response although stabilizing the control. A value that is set too small speeds up control response but renders the control unstable. If the optimum value is not known, adjust the setting if the control is unstable or response is delayed. Note: The set value is commonly applied to Terminals 12, V2 and C1. For input of PID feedback, the PID control feedback filter (H25) is used.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-31
Page 86
Motor 1 (P: Motor Parameters) Value 0
P01 Number of motor 1 poles P 0 1 M 1
This function sets the number of poles in Motor 1. If this setting is not made, an incorrect motor speed (synchronous speed) is displayed on the LED.
P02 Motor 1 (capacity) P 0 2 M 1 – CA P
2
Measure the motor’s primary resistance (%R1) and base frequency leakage reactance (%X) when the motor is stopping, measure the no-load current (lo) when the motor is running, and automatically store these values in P06, P07, and P08.
Perform auto tuning if the previously stored data in P06 No-load current, P07 %R1, and P08 %X differs from the actual motor data. Some typical examples are listed below. Auto tuning improves control and calculation accuracy.
Set values for models with nominal motor capacity of 30Hp or less: 0.01 to 60Hp Set values for models with nominal motor capacity of 40Hp or more: 0.01 to 800Hp
When a motor other than the GE standard 3-phase motor is used, and accurate data is required for close control. When output-side impedance cannot be ignored, e.g. when the cable between the drive and the motor is too long or when a reactor is connected. When %R1 or %X is unknown, e.g. when a nonstandard or special motor is used.
The nominal motor capacity is set at the factory. This setting should only be changed when driving a motor with a different capacity. Set the nominal motor capacity listed in 9-1 Standard Specifications. A value in the range from two ratings lower to one rating higher than the nominal motor capacity can be set. If a value outside this range is set, accurate control cannot be guaranteed. If a value between two nominal motor capacities is set, data for the lower capacity is automatically stored for related function data. If this function setting is changed, the following related functions are automatically set to data values for the Fuji 3-phase standard motor.
Tuning Procedure 1.
2., P03 Motor 1 (rated current), P06 Motor 1 (no-load current), P07 Motor 1 (% R1), P08 Motor 1 (% X1)
3.
Note:
4.
The values for the GE 3-phase standard motor are 230V, 60Hz, 4 poles for the 230V series; 460V, 60Hz, 4 poles for the 460V series. 5.
P03 Motor 1 (rated current) P 0 3 M 1 – L R
Set value: 0.00 to 2,000 A This function sets the rated current value for Motor 1.
6.
P04 Motor 1 (Tuning) P 0 4 M 1
1
Measure the motor’s primary resistance (%R1) and base frequency leakage reactance (%X) when the motor is stopping and automatically store both values in P07 and P08.
PO L E S
Set values: 2, 4, 6, 8, 10, 12, 14
Operation Inactive
Adjust the voltage and frequency according to motor data. Adjust functions F03 Maximum output frequency, F04 Base frequency, F05 Rated voltage, and F06 Maximum output voltage. First enter motor constants that cannot be tuned. Set functions P02 Capacity, P03 Rated current, and P06 No-load current (no-load current setting is not required if P04=2). When tuning the no-load current, beware of motor rotation. Set function P04 Auto tuning = 1 (motor stop) or 2 (motor rotation). Press the FUNC/DATA key to store the set value and press the FWD key or REV key. Tuning will start. Tuning may take several seconds. If P04=2, the motor accelerates up to half the base frequency according to acceleration time, is tuned for the no-load current, and decelerates according to the deceleration time. The total tuning time varies depending on the settings for acceleration and deceleration time. Press the STOP key, and the procedure will end.
Note: Use function A13 Motor 2 (auto tuning) to tune Motor 2. In this case, the set values described in (1) and (2) above are for functions A01, etc. corresponding to Motor 2.
T U N 1
This function measures and automatically stores motor data.
WARNING If the auto tuning value is set to 2, the motor rotates at a maximum of half the base frequency. Beware of motor rotation as injury may result. 5-32
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 87
P05 Motor 1 (On-line Tuning)
P09 Slip compensation control
P 0 5 M 1
P 0 9 S L I P
T U N 2
Long-time operation affects motor temperature and motor speed. On-line tuning minimizes speed changes related to these temperature changes. Value
Operation
0
Inactive
1
Active
P06 Motor 1 (no-load current) P 0 6 M 1 – I O
Set value: 0.00 to 2,000 A This function sets the no-load current (exciting current) for Motor 1.
Set value: 0.00 to 15.00 Hz Changes in load torque affect motor slippage, thus causing variations in motor speed. The slip compensation control adds a frequency, proportional to motor torque, to the drive output frequency. This will minimize variations in motor speed due to changes in torque. Calculate the amount of slip compensation using the following formula:
= Base frequency X
%R 1 %X
These functions are used to set data if using a motor other than the GE standard 3-phase motor and when the motor constant and the impedance between the drive and motor are known. Calculate %R1 using the following formula:
R1 + CableR
X 100 [%] V/( 3•I) R1: Primary coil resistance value of the motor [W] Cable R: Output-side cable resistance value [W] V: Rated voltage [V] I: Rated current [A] Rated current %R1 =
%X =
X1 +X2 • XM / (X2+XM) + Cable X
X 100 [%] V/( 3•I) X1: Primary leakage reactance of the motor [W] X2: Secondary leakage reactance (converted to a primary value) of the motor [W] XM: Exciting reactance of the motor [W] Cable X: Output-side cable reactance [W] V: Rated voltage [V] I: Rated current [A] Note: For reactance, use a value from the data stored in F04 Base frequency 1. When connecting a reactor or filter to the output circuit, add its value. Use value 0 for cable values that can be ignored.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Slippage [r/min.] Synchronous speed [r/min.]
Slippage = Synchronous speed - Rated speed
P07 Motor 1 (%R1 setting) P08 Motor 1 (%X setting) P 0 7 M 1 P 0 8 M 1
C OM P 1
5-33
[Hz]
Page 88
H: High Performance function H03 Data initializing H 0 3 D A T A
Set value
WARNING When the retry function is selected, operation will automatically restart, depending on the cause of the stop. (The machine should be designed to ensure safety during a restart.) When the retry function is selected, GE start software (F02 set 3 or 4) does not work.
I N I T
0: Disabled 1: Initializes data
This function returns all function data changed by the customer to the original factory settings (initialization). To perform initialization, press the STOP and ^ keys together to set H03=1, then press the FUNC/DATA key. The values for all functions are initialized. The set value in H03 automatically returns to 0 following the end of initialization.
H04 Auto-reset (Times) H05 Auto-reset (Reset interval) H 0 4 A U T O – R E S E T
H 0 5 R E S E T
I N T
Set the protective function release count and waiting time from its startup to release. Setting range (Count) : 0, 1 to 10 (Waiting time) : 2 to 20 seconds When a drive protective function which invokes the retry operation is activated, these functions release operation of the protective function and restarts operation without issuing an alarm or terminating output. To disable the retry function, set H04 Retry (count) = 0.
H06 Fan stop operation
Drive protective functions that can invoke the retry function: OC1, OC2, OC3:
dBH:
H 0 6 F AN
Overcurrent braking resistor overheating
Set value
OV1, OV2, OV3:
OL1:
Overvoltage
Motor 1 overload
OH1:
OL2:
Heat sink overheating
Motor 2 overload
OH3:
OLU:
Drive overheating
Drive overload
S T O P
0: ON/OFF control disabled 1: ON/OFF control enabled
This function specifies whether ON/OFF control for the cooling fan is automatic. While power is applied to the drive, the automatic fan control detects the temperature of the heatsink and turns the fan on or off. When this control is not selected, the cooling fan rotates continuously. The cooling fan operating status can be monitored from terminals Y1 to Y5.
internally
If the value of H04 Retry (count) is set from 1 to 10, a drive run command is immediately entered following the wait time set in H05 Retry (wait time) and the startup of the retry operation. If the cause of the alarm has been removed at this time, the drive starts without switching to alarm mode. If the cause of the alarm still remains, the protective function is reactivated according to the wait time set in H05 Retry (waiting time). This operation is repeated until the cause of the alarm is removed. The restart operation switches to alarm mode when the retry count exceeds the value set in H04 Retry (count). The operation of the retry function can be monitored from terminals Y1 to Y5. 5-34
H07 ACC/DEC (Mode select) pattern H 0 7 A CC
P T N
Set value 0: Inactive (linear acceleration and deceleration) 1: S-shape acceleration and deceleration (mild) 2: S-shape acceleration and deceleration (sharp) 3: Curvilinear acceleration and deceleration This function selects the acceleration and deceleration pattern. Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 89
S-shape Acceleration and Deceleration
H09 Start mode
This pattern reduces shock by mitigating output frequency changes at the beginning and end of acceleration and deceleration.
H 0 9 S T A R T
MO D E
Setting range 0, 1, 2 This function smoothly catches a spinning motor which is coasting after a momentary power failure or after the motor has been subject to external force, without stopping the motor, i.e. windmilling fan. At startup, this function detects the motor speed and outputs the corresponding frequency, thereby enabling a shock-free motor startup. The normal startup method is used if the coasting speed of the motor is 120 Hz or more as a drive frequency and if the value of F03 Maximum frequency exceeds the value of F15 Frequency limiter (upper limit). Pattern constants> When 1 is selcted in H07 (mid S-shape pattern) Range of 0.05 x maximum S-shaped output frequency (Hz) 0.10 x Time for acceleration S-shaped at acceleration time (s) 0.10 x Time for deceleration (s) S-shaped at deceleration
When 2 is selcted in H07 (mid S-shape pattern)
Value
Normal startup
0.10 x maximum output frequency (Hz)
0 1 2
Inactive Inactive Active
0.20 x acceleration time (s)
*
0.20 x deceleration (s)
When acceleration and deceleration times are very long or short, acceleration and deceleration are almost linear. Curvilinear Acceleration and Deceleration This function is used to minimize motor acceleration and deceleration times in the range that includes a constant output range. Output frequency acceleration
Maximum output deceleration
Restart after a momentary power failure Inactive Active Active
Line-to-drive switching Inactive Active Active
Explanation 1.
This function is effective if F14 Restart after momentary power failure (operation selection) is set to 3, 4, or 5. This function is also effective when operation is switched from the line to the drive. The motor is started with the same frequency as the current coasting speed (speed search). 2. In addition to restarting following a momentary power failure and switching between the line and the drive, this function detects the coasting speed of the motor and starts the motor at the same frequency as all startups (including when an ON operation command is entered). By assigning 26 (start characteristics selection) to terminals X1 to X9, this function can be externally selected as the normal startup method whenever an ON operation command is entered.
Set frequency Base frequency
0 t [sec]
H08 Rev. phase sequence lock H 0 8 R E V
Set value
L O C K
0: Inactive 1: Active
If accidental reversing could result in a malfunction, this function can be set to prevent reversal. This function prevents a reversing operation resulting from a connection between the REV and CM terminals, inadvertent activation of the REV key, or negative analog input from Terminals 12 or V1. Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Note: The dotted-dashed line indicates motor speed. 5-35
Page 90
H10 Energy-saving operation
H13 Auto-restart (Restart time)
H 1 0 E N E RG Y
H 1 3 R E S T A R T
Set value 0: Inactive
S A V
1: Active
T
Setting range: 0.1 to 10.0 seconds
With constant-speed operation at light loads (fixed output frequency), this function automatically reduces the output voltage while minimizing the product of voltage and current (power). [Exception: If F09 Torque boost 1 = 0.0] Notes: Use this function for variable torque loads (e.g., fans, pumps). If used for a constant torque load or rapidly changing load, this function causes a delay in control response.
Instantaneous switching to another power line (when the power of an operating motor is cut off or power failure occurs) creates a large phase difference between the line voltage and the voltage remaining in the motor, which may cause electrical or mechanical failure. To rapidly switch power lines, store the remaining voltage attenuation time to wait for the voltage remaining in the motor to attenuate. This function operates at restart after a momentary power failure.
The energy-saving operation automatically stops during acceleration and deceleration or when the torque limiting function is activated.
If the momentary power failure time is shorter than the wait time value, a restart occurs following the wait time. If the power failure time is longer than the wait time value, a restart occurs when the drive is ready to operate (after about 0.2 to 0.5 seconds).
H11 DEC mode
H14 Auto-restart (freq. fall rate)
H 1 1 D E C
H 1 4 F A L L
MO D E
Set value
0: Deceleration-to-stop based on data set with H07 Non-linear acceleration and deceleration 1: Coasting-to-stop This function determines the drive stopping method when a STOP command is entered. Note: This function is effective only when a STOP command is entered and, therefore, is ineffective if the motor is stopped by lowering the set frequency.
H12 Instantaneous overcurrent limiting H 1 2 I N S T
Set value 0: Inactive
C L
1: Active
R A T E
Setting range: 0.00, 0.01 to 100.00 Hz/s If H14 = 0.00, the frequency is reduced according to the set deceleration time. This function determines the reduction rate of the output frequency for synchronizing the drive output frequency with the motor speed. This function is also used to reduce the frequency and thereby prevent stalling under a heavy load during normal operation. Note: A frequency reduction rate that is set too large may temporarily increase the regeneration energy from the load and invoke the overvoltage protective function. Conversely, a rate that is too small extends the operation time of the current limiting function and may invoke the drive overload protective function.
An overcurrent trip generally occurs when current flows above the drive protective level, following a rapid change in motor load. The instantaneous overcurrent limiting function controls drive output and prohibits the flow of a current exceeding the protective level, even if the load changes.
H15 Auto-restart (holding DC voltage)
Since the operation level of the instantaneous overcurrent limiting function cannot be adjusted, the torque limiting function must be used.
This function is used when F14 Restart after momentary power failure (operation selection) is set to 2 (deceleration-to-stop at power failure) or 3 (operation continuation). Either function starts a control operation if the main circuit DC voltage drops below the set operation continuation level.
Motor generation torque may be reduced when instantaneous overcurrent limiting is applied. Set this function to be inactive for equipment such as elevators, which are adversely affected by reduced motor generation torque, in which case an overcurrent trip occurs when the current flow exceeds the drive protective level. A mechanical brake should be used to ensure safety.
5-36
H 1 5 H O L D
Setting range
V
230V series: 200 to 300V 460 V series: 400 to 600V
If power supply voltage to the drive is high, control can be stabilized even under an excessive load by raising the operation continuation level. However, if the level is too high, this function activates during normal operation and causes unexpected motion. Please contact GE Fuji before changing the factory default value.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA