Page 71
F42 Torque vector control 1 F 4 2 T RQ V E C T O R 1
To obtain the most efficient motor torque, the torque vector control calculates torque according to load, to adjust the voltage and current vectors to optimum values based on the calculated value. Value
Operation
0 inactive
1 active Related Functions P01 to P09
If F42 = 1 (active), the following functions are affected: 1. 2.
F09 Torque boost 1 is automatically set to 0.0 (automatic torque boosting). P09 Slip compensation control is automatically activated. If set to 0.0, the amount of slip compensation for a standard 3-phase Fuji motor is applied. Otherwise, the set value is applied.
Use the torque vector control function under the following conditions: 1. There can only be one motor. Connection of two or more motors makes accurate control difficult. 2. The function data (rated current P03, no-load current P06,, %R1 P07, and %X P08) for Motor 1 must be correct. If a standard 3-phase GE motor is used, setting the capacity (Function P02) ensures entry of the above data. An auto-tuning operation should be performed for other motors. 3. The rated current of the motor must not be significantly less than the rated current of the drive. A motor two sizes lower in capacity than the nominal motor indicated for the drive is the smallest that should be used. 4. To prevent leakage current and ensure accurate control,, the length of the cable between the drive and motor should not exceed 50 m. 5. If a reactor is connected between the drive and the motor and wiring impedance cannot be disregarded, use P04 Auto tuning to reset data. If these conditions are not satisfied, set F42 = 0 (Inactive).
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-17
Page 72
E: Extension Terminal Functions E01 Terminal X1 E09 Terminal X9 E 0 1 X 1 E 0 2 X 2 E 0 3 X 3 E 0 4 X 4 E 0 5 X 5 E 0 6 X 6 E 0 7 X 7 E 0 8 X 8 E 0 9 X 9
Multi-step frequency selection Value 0,1, 2, 3: The frequency can be switched to a preset frequency in function codes C05 to C19 by switching the external digital input signal. Assign values 0 to 3 to the target digital input terminal. The combination of input signals determines the frequency.
F U N C F U N C F U N C F U N C F U N C F U N C F U N C F U N C F U N C
Functions can be individually set from each of the digital input terminals X1 to X9. Value 0,1,2,3 4,5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 32
Function Multi-step frequency selection (1 to 15 steps) Acceleration and deceleration time selection (3 steps) Self-hold selection (HLD) Coast-to-stop command (BX) Alarm reset (RST) External alarm (THR) Jogging (JOG) Frequency setting 2 / Frequency setting 1 (Hz 2 / Hz1) Motor 2 / Motor 1 (M2 / M1) DC injection brake command (DCBRK) Torque limit 2 / Torque limit 1 (TL2 / TL1) Switching operation from line to drive (50 Hz) (SW50) Switching operation from line to drive (60 Hz) (SW60) UP command (UP) DOWN command (DOWN) Edit permission command (data change permission) (WE-KP) PID control cancellation (Hz / PID) Normal/Inverse switching (Terminals 12 and C1) (IVS) Interlock (52-2) (IL) Torque control cancellation (Hz/TRQ) Link operation selection (Standard: RS485, Option: BUS) (LE) Universal DI (U-DI) Pick up start mode (STM) SY-PG enable (PG/Hz) Zero speed command (ZERO) Timed alarm stop command (STOP1) Timed alarm stop command with Deceleration time 4 (STOP2) Pre-exciting command (EXCITE)
Combination of Input Signals 3 2 1 (SS8) (SS4) (SS2) off off off off off on off off on off on off off on off off on on off on on on off off on off off on off on on off on on on off on on off on on on on on on
Selected Frequency 0 (SS1) on off on off on off on off on off on off on off on
C05 MULTI Hz-1 C06 MULTI Hz-2 Related C07 MULTI Hz-3 Functions: C08 MULTI Hz-4 C05-C19 C09 MULTI Hz-5 C10 MULTI Hz-6 Setting C11 MULTI Hz-7 Setting C12 MULTI Hz-8 0.00 to C13 MULTI Hz-9 - 400.00 Hz C14 MULTI Hz-10 C15 MULTI Hz-11 C16 MULTI Hz-12 C17 MULTI Hz-13 C18 MULTI Hz-14 C19 MULTI Hz-15
Acceleration and Deceleration time selection Value 4, 5: The acceleration and deceleration time can be switched to a preset time in function codes E10 to E15 by switching the external digital input signal. Assign values 4 and 5 to the target digital input terminal. The combination of input signals determines the acceleration and deceleration times. Combination of Input Signals 5 4 (RT2) (RT1) off off off on on off on on
Selected Acceleration / Deceleration Times
F07 ACC TIME1 F08 DEC TIME1 E10 ACC TIME2 E11 DEC TIME2 E12 ACC TIME3 E13 DEC TIME3 E14 ACC TIME4 E15 DEC TIME4
Related Functions E10-E15 Setting Range 0.01 to 3600s
Note: Values which are not set in the functions from E01 to E09 are assumed to be inactive.
5-18
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 73
Self-hold selection (HLD) Value 6: This selection is used for 3-wire operation. The FWD or REV signal is self-held when HLD-CM is on, and this self-hold is cleared when HLD-CM is turned off. To use this HLD terminal function, assign 6 to the target digital input terminal.
operation is performed with the jogging frequency set in function code C20 while the operation command (FWDCM or REV-CM) is on. To use this JOG terminal function, assign 10 to the target digital input terminal.
Frequency setting 2/frequency setting 1 Value 11: This function switches the frequency setting method defined by function codes F01 and C30 using an external digital input signal. Input Signal 11 off on
Selected Frequency Setting F01 FREQ CMD1 C30 FREQ CMD2
Motor 2/Motor 1 FWD
FWD
REV
REV
HLD STOP
Value 12: This function switches motor constants using an external digital input signal. This input is effective only when the operation command to the drive is off and operation has stopped and does not apply to the operation at 0Hz.
CM
Input Signal 12 off on
Coast-to-stop command (BX) Value 7: When BX and CM are connected, drive output is cut off immediately, and the motor starts to coast to a stop. An alarm signal is neither output nor self-held. If BX and CM are disconnected when the operation command (FWD or REV) is on, operation begins at the start frequency. To use this BX terminal function, assign value 7 to the target digital input terminal. Output Frequency
F WD-CM
Forward rotation
Forward rotation
Forward rotation
Ignored
ON
ON
REV-CM BX-CM
ON
ON
ON
Selected Motor Motor 1 Motor 2 Related Functions: A01-A18
DC injection brake command (DCBRK) Value 13: This function is used for DC Brake time control by digital input including extending braking operation during stopping as well as during start up into a rotating load. When the external digital input signal is on, DC injection braking starts when the drive’s output frequency drops below the frequency preset in function code F20 after the operation command goes off. (The operation command goes off when the STOP key is pressed during keypad panel operation or when both terminals FWD and REV go off during terminal block operation.) The DC injection braking continues while the digital input signal is on. In this case, the longer of the following times is selected:
Alarm reset (RST)
- The time set with function code F22
Value 8: If a drive trip occurs, connecting RST to CM clears the alarm output (for any fault). Disconnecting them clears the trip indication and restarts operation. To use this RST terminal function, assign value 8 to the target digital input terminal.
- The time during which the input signal is set ON
External alarm (THR)
Input Signal 13 off on
Value 9: Disconnecting THR and CM during operation cuts off drive output (i.e., motor starts to coast to a stop) and outputs alarm OH2, which is self-held internally and cleared by RST input. This function is used to protect an external brake resistor and other components from overheating. To use this THR terminal function, assign value 9 to the target digital input terminal. ON input is assumed if this terminal function is not set.
Output Frequency
Jogging (JOG)
DCBRK-CM
DC injection brake command not given DC injection brake command given
DC Brake Frequency ON
DC Brake FWD-CM
Value 10: This function is used for jogging operation to position a workpiece. When JOG and CM are connected, the Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Selected Operation
5-19
ON
ON
ON ON
ON
Page 74
Torque limit 2/torque limit 1 Value 14: Frequency setting 2/frequency setting 1. This function switches the torque limit value set with function codes F40, F41, E16, and E17, using an external digital input signal. Input Signal 14 off on
Selected Torque Limit Value F40 DRV TRQ1 F41 BRK TRQ1 E16 DRV TRQ2 E17 DRV TRQ2
Related Functions F40-F41, E16-E17 Setting Range DRV 20 to 200% ,999 BRK0, 20 to 200%, 999
Switching operation from line drive (60Hz)(SW60)/(50Hz)(SW50) Value 15, 16: Motor operation can be switched from 60 Hz/50 Hz commercial power to drive operation without stopping the motor by switching the external digital input signal. Input Signal 16 off > on on > off
Function Drive operation to line operation (60 Hz)/(50 Hz) Line operation to drive operation (60 Hz)/(50 Hz)
The change ranges from 0 to maximum frequency. Operation in the opposite direction of the operation command is not allowed.
on on
Selected Function Prohibit data changes Allow data changes
Value 20: The PID control can be disabled by an external digital input signal.
Value 17, 18: When an operation command is input (on), the output frequency can be increased or decreased using an external digital input signal.
off
19 off on
PID control cancellation (Hz/PID)
UP command (UP)/DOWN command (DOWN)
on
Value 19: This function allows the data to be changed only when input is received from an external signal, thereby preventing function code data changes.
Note: If a terminal is assigned the value 19, the data cannot be changed. To change data, turn the terminal on and change its setting to another number.
Following a momentary power failure, if the digital input signal goes off, 50 or 60 Hz (according to the input signal) is output after the restart waiting time (function code H13). The motor is then directed to drive operation.
Combination of Input Signals 18 17 off off off on
Edit permission command (data change permission)(WE-KP)
Input Signal 20 off on
Selected Function [Related Functions: H20-H25] Enable PID control Disable PID control
(When the PID control is disabled, the frequency is set from keypad panel)
Normal operation/inverse
Selected Function (when operation command is on) Holds the output frequency Increases the output frequency according to the acceleration time Decreases the output frequency according to the deceleration time Holds the output frequency
Value 21: Analog input (Terminals 12 and C1) can be switched between normal and inverse operations using an external digital input signal. Input Signal 21 off on
There are the two types of UP/DOWN operations as shown below. Select the desired type by setting the frequency (F01 or C30).
Selected Function [Related Function: F01] Normal operation if normal operation is set and vice versa Inverse operation if normal operation is set and vice versa
Interlock (52-2) Value 22: When a contactor is installed on the output side of the drive, the contactor opens at the time of a momentary power failure. This prevents the reduction of the DC circuit voltage and may prevent the detection of a power failure and a correct restart operation after power is recovered. The restart operation, in the event of a momentary power failure, can be performed effectively with power failure information provided by an external digital input signal. 5-20
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 75
Input Signal 22 off on
Function No momentary power failure detection by digital input Momentary power failure detection by digital input
Torque control cancellation (Hz/TRQ)
SY-PG enable (PG/Hz) Value 27: This selects the closed loop control with PG (encoder) or open loop control. Input Signal 27 off on
Operation Select open loop control close loop control
Value 23: If function code H18 Torque control is set to active (value = 1 or 2), this operation can be cancelled externally by assigning 23 to the target digital input terminal and switching between active and inactive for this input signal.
Note: PG Option Card is required for this function
Input Signal 23 off
Selected Function [Related Function: H18] Torque control function active – the input voltage to Terminal 12 is the torque command value
Input Signal 29 off on on
Torque control function inactive - the input voltage to Terminal 12 is the frequency command value. PID feedback amount when PID control operation is selected (H20 = 1 or 2).
Note: PG Option Card is required for this function
Zero speed command (zero) Value 29: This function is used for stall torque operation with vector control at zero. Selected Function zero speed control disabled zero speed control enabled
Link Operation selection (LE)
Timed alarm stop command (STOP1) Timed alarm stop command with deceleration time 4 (STOP2)
Value 24: Frequency and operation commands from the data communications link can be enabled or disabled by switching the external digital input signal. Select the command source in H30-Link function and assign 24 to the target digital input terminal to enable or disable commands in this input signal state.
Value 30, 31: Disconnecting STOP1 and CM during operation, the drive decelerates and stops by a present deceleration time (STOP1)/deceleration time 4 (STOP2) setting and then outputs alarm Er6 which is latched internally and cleared by RST input. ON input is assumed when this terminal function is not set.
Input Signal 24 off on
Pre-exciting command (EXCITE)
Selected Function [Related Function: H30] Link command disabled Link command enabled
Universal DI (U-DI) Value 25: Assigning 25 to a digital input terminal renders the terminal a universal DI terminal. The ON/OFF state of signal input to this terminal can be checked through the RS485 and BUS option. This input terminal is only used to check for an incoming input signal through communication and does not affect drive operation.
Pick up start mode (STM) Value 26: The (pick-up start mode): in function code H09 can be enabled or disabled by switching the external digital input signal. Assign 26 to the target digital input terminal to enable or disable the function in this input signal state. Input Signal 26 off on
Value 32: When EXCITE transition ON, the motor enters into a pre-exciting state during flux vector control mode. When an operation command (FWD or REV) is initiated, the motor returns from the pre-exciting state to the ordinary state. Note: PG Option Card is required for this function Digital Value Input Terminal X1 0 Terminal X2 1 Terminal X3 2 Terminal X4 3 Terminal X5 4 Terminal X6 5 Terminal X7 6 Terminal X8 7 Terminal X9 8
Selected Function [Related Function: H09] Start characteristic function disabled Start characteristic function enabled
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-21
Factory Settings at Shipment Description Multi-step frequency selection (SS1) Multi-step frequency selection (SS2) Multi-step frequency selection (SS4) Multi-step frequency selection (SS8) Acceleration and deceleration selection (RT1) Acceleration and deceleration selection (RT2) Self-hold selection (HLD) Coast-to-stop command (BX) Alarm reset (RST)
Page 76
E10 Acceleration time 2 E11 Deceleration time 2 E12 Acceleration time 3 E13 Deceleration time 3 E14 Acceleration time 4 E15 Deceleration time 4 E 1 0 A CC E 1 1 D E C E 1 2 A CC E 1 3 D E C E 1 4 A CC E 1 5 D E C
E20 Terminal Y1 (function selection) E24 Terminals Y5A and Y5C (funtion selection) E 2 0 Y 1 E 2 1 Y 2 E 2 2 Y 3 E 2 3 Y 4 E 2 4 Y 5
T I M E 2 T I M E 2 T I M E 3 T I M E 3 T I M E 4 T I M E 4
Some control and monitor signals can be selected and output from terminals Y1 to Y5. Terminals Y1 to Y4 use transistor output; terminals Y5A and Y5C use relay contacts.
Acceleration time1 (F07) and Deceleration time1 (F08), as well as three other acceleration and deceleration times, can be selected. The operation and setting ranges are the same as those for Acceleration time1 and Deceleration time1. See explanations for F07 and F08. For switching acceleration and deceleration times, select any two terminals (from Terminal X1 in E01 to Terminal X9 in E09) as switching signal input terminals. Set the selected terminals to 4 (acceleration and deceleration time1) and 5 (acceleration and deceleration time2) and input a signal to each terminal to switch acceleration and deceleration times. Switching is possible during acceleration, deceleration, or constant speed operation. Example: When Terminals X2 and X3 are set to 4 and 5:
Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
E16 Torque limit 2 (drive) E17 Torque limit 2 (brake) E 1 6 D R V E 1 7 B RK
T R Q T R Q
F U N C F U N C F U N C F U N C F U N C
Output Signal Drive Running (RUN) Frequency arrival (FAR) Frequency detection (FDT1) Stopping due to undervoltage (LV) Torque polarity detection (B/D) Torque limiting (TL) Restart after momentary power failure (IPF) Overload - early warning (OLI) Keypad panel operation (KP) Drive stopping (STP) Ready for operation (RDY) Switching between line and drive (SW88) Switching between line and drive (SW52-2) Switching between line and drive (SW52-1) Motor 2 switching (SWM2) Terminal AX function (AX) Pattern operation stage change (TU) Pattern operation cycle operation completed (TO) Pattern operation stage number (STG1) Pattern operation stage number (STG2) Pattern operation stage number (STG4) Alarm detail (AL1) Alarm detail (AL2) Alarm detail (AL4) Alarm detail (AL8) Cooling fan operating (FAN) Retry function operating (TRY) Universal DO (U-DO) * Heat sink overheat - early warning (OH) Synchronization completed by synchronous operation card (SY) * unused 2nd Freq. level detection (FDT2) 2nd OL level early warning (OL2) Terminal C1 off signal (C1OFF)
Note: For output signals marked *, refer to instruction manuals for RTU communication and the synchronous operation card.
2 2
This function is used to switch the torque limit level set by F40 and F41, using an external control signal. Input an external signal by setting any of the digital input terminals (X1 to X9) to 14 for Torque limit 2 / Torque limit 1 in E01 to E09. 5-22
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 77
Drive running (RUN) Value 0: The RUN signal is output when there is output speed (drive is outputting a frequency). When the DC injection brake function is active, the RUN signal is off.
For setting procedure, see E33 Overload early warning (operation selection) and E34 Overload early warning (operation level). Note: This function is only effective for Motor 1.
Frequency arrival (FAR)
Keypad panel operation
Value 1: See the explanation for function code E30 (frequency arrival [detection width]).
Value 8: An ON signal is output when the operation command keys (FWD, REV and STOP) on the keypad panel can be used (i.e., F02 Operation = 0) to issue operation and stop commands.
Frequency detection (FDT1) Value 2: See the explanation for function codes E31 and E32 (frequency detection).
Stopping due to undervoltage (LV) Value 3: If the undervoltage protective function activates, i.e. if the main circuit DC voltage falls below the undervoltage detection level, an ON signal is output. The signal goes off when the voltage recovers and increases above the detection level. The ON signal is retained as long as the undervoltage protective function is active. Undervoltage detection level:
230V series: 200V 460V series: 400V
Torque polarity detection (B/D) Value 4: This function determines the torque polarity calculated in the drive and outputs a signal indicating driving or braking torque. An OFF signal is output for driving torque; an ON signal is output for braking torque.
Torque limiting (TL) Value 5: When torque limiting is active, the stall prevention function is automatically activated to change the output frequency. The torque limiting signal is output to lighten the load and also used to display overload conditions on the monitor device. This ON signal is output while the current or torque is limited or power regeneration is prevented.
Restart after momentary power failure (IPF) Value 6: Following a momentary power failure, this function reports the start of restart mode, the occurrence of an automatic pull-in, and the completion of the recovery operation. Following a momentary power failure, an ON signal is output when power is recovered and a synchronization (pull-in) operation is performed. The signal goes off after a frequency level equal to that prior to power failure has been recovered. For 0 Hz restart at power recovery, no signal is output because synchronization ends when power is recovered. The frequency is not recovered to the level before the power failure occurred.
Overload early warning (OL1) Value 7: Before the motor is stopped by a trip operation of an electronic thermal O/L relay, this function outputs an ON signal when the load reaches the overload early warning level.
Drive stopping (STOP) Value 9: This function outputs an inverted signal to RUN to indicate zero speed. An ON signal is output when the DC injection brake function is operating.
Ready for operation (RDY) Value 10: This function outputs an ON signal when the drive is ready to operate. The drive is ready to operate after the main circuit and control circuit power have been established where the drive protective function is not activated. About one second is required from power-on to ready for operation under normal conditions.
Switching between the AC line and the drive (SW88)(SW52-2)(SW52-1) Value 11, 12, 13: To perform a transfer between the line and the drive, the relay sequence can be accomplished using values 11, 12 and 13 on the “Y” outputs. These values will provide outputs that can be used for opening and closing contactors in the transfer sequence. For a detailed explanation of these outputs please refer to the factory.
Motor 2 switching (SWM2) Value 14: When a signal for switching to Motor 2 is input from the terminal selected by Terminals X1 to X9, this function selects and outputs the signal to switch the magnetic contactor for the motor. Since this switching signal is not output during running, including when the DC injection braking function is operating, a signal must be reinput after output stops.
Terminal AX function (AX) Value 15: When an operation command (FWD or REV) is entered, this function outputs an ON signal. When a stop command is entered, the signal goes off after drive output stops. When a coast-to-stop command is entered, and the drive protective function is operating, the signal goes off immediately.
Pattern operation stage change (TU) Value 16: When the pattern operation stage changes, this function outputs a one-shot, 100ms ON signal to report a stage change.
Either the electronic thermal O/L relay early warning or output current overload early warning can be selected.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-23
Page 78
Pattern operation cycle operation completed (TO)
Universal DO(U-DO) Value 27: Assigning a value of 27 to a transistor output terminal renders the terminal a universal DO terminal.
Value 17: After the seven stages of a pattern operation have been completed, this function outputs a one-shot, 100 ms ON signal to report the completion of all stages.
This function enables ON/OFF through the RS485 and BUS option.
Pattern operation stage number (STG1)(STG2)(STG4)
This function serves only to turn the transistor output on or off through communication and is not related to drive operation.
Value 18, 19, 20: During pattern operation, this function reports the stage (operation process) being operated. Pattern Operation Stage No. Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Stage 6 Stage 7
Heat sink overheat early warning (OH) Value 28: This function outputs an early warning signal when the heat sink temperature (overheat detection level) is within 10°C of the overtemp trip point.
Output Terminal STG1 on off on off on off on
STG2 off on on off off on on
STG4 off off off on on on on
Synchronization completed by synchronous operation card (SY) Value 29: This is the synchronization complete signal for the synchronize operation option. See Option Instruction Book for details.
When pattern operation is not activated (i.e., no stage has been selected), the terminals do not output a signal.
Alarm detail (AL1)(AL2)(AL4)(AL8) Value 21, 22, 23, 24: This function reports the operating status of the drive protective function.
2nd Freq. level detection (FDT2) Vallue 31: This function sets the 2nd Freq. level detection. See the explanation of Function Code E36 and E37 Hysteresis width is same as FDT1 (E32).
2nd OL level early warning (OL2) Value 32: This function sets the 2nd overload early warning. See the explanation of “overload early warning (OL)”, E37.
Alarm Detail (Drive Protective Function
Output Terminal AL1 AL2 AL4 AL8
Overcurrent, ground fault, blown fuse on
Overvoltage Undervoltage shortage, input phase failure Motor 1 and Motor 2 overload drive overload Heat sink overheating, drive overheating internally External alarm input, braking resistor overheating Memory error, CPU error Keypad panel communication error, option communication error Option error Output wiring error RTU communication error Overspeed, PG disconnection off on off off
Terminal C1 off signal (C1OFF)
on on off off off on off off on on off off
Value 33: This function outputs an ON signal, when the C1 current input is smaller than 2mA.
off on on off on on on off off off off off off off on on off off on off off on off on off off on off on on on on on on on
SETTINGS WHEN SHIPPED FROM THE FACTORY Digital Output Value
Factory Setting at Shipment Description
Terminal Y1
0
Operating (RUN)
Terminal Y2
1
Frequency arrival (FAR)
Terminal Y3
2
Frequency detection (FDT)
Terminal Y4
7
Overload early warning (OL)
Terminal Y5
15
Terminal AX function (AX)
Under normal operation, terminals do not output a signa
Cooling fan operating (FAN)
E25 Y5 Ry operation mode
Value 25: When used with H06 Cooling fan ON/OFF control, this function outputs a signal while the cooling fan is operating.
E 2 5 Y 5 R Y
Retry function operating (TRY) Value 26: When H04 Retry operating is set to 1 or higher, the signal is output during the retry operation, if the drive protective function has been activated.
MO D E
This function specifies whether to excite the Y5 relay at “ON signal mode” or “OFF signal mode” Set Value
Operation
0
At “OFF signal mode” Y5A - Y5C: OFF
1
At “OFF signal mode” Y5A - Y5C: ON
At “ON signal mode” Y5A - Y5C: ON At “ON signal mode” Y5A - Y5C: OFF
5-24
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 79
When the set value is 1, contacts Y5A and Y5C are connected when the drive control voltage is established (about one second after power on).
E30 Frequency arrival (detection width) E 3 0 F AR
H Y S T R
Setting range: 0.0 to 10.0 Hz This function adjusts the detection width when the output frequency is the same as the set operating frequency. The detection width can be adjusted from 0 to ±10 Hz of the setting frequency.
E33 Overload early warning (operation) E 3 3 O L
L E V E L
Set value 0: Electronic thermal O/L relay
Select one of the following two types of overload early warning: early warning by electronic thermal O/L relay function or early warning by output current. 1: Output current Value 0
Function Electronic thermal O/L relay
Description Overload early warning by electronic thermal O/L relay (with inverse time characteristics) to output current. The operation selection and thermal time constant for the inverse time characteristics are the same as those of the electronic thermal O/L relay for motor protection (F10 and F12).
1
Output current
An overload early warning is issued when output current exceeds the set current value for the set time.
When the frequency is within the detection width, an ON signal can be selected and output from terminals [Y1] to [Y5]
E34 Overload early warning (operation level) E 3 4 O L 1
L E V E L
Setting range: Drive rated output current x (5 to 200%)
This function determines the operation level for the electronic thermal O/L relay or output current. The operation release level is 90% of the set value.
E35 Overload early warning (operation time) E 3 5 O L
T I M E R
E31 Frequency detection (operation level) E32 Frequency detection (hysteresis width)
Setting range: 0.0 to 60.0 seconds
E 3 1 F D T E 3 2 F D T
Sets the time from when the operation level is attained until the overload early warning function is activated.
L E V E L H Y S T R
Setting range (Operation level): 0 to 400 Hz These functions determine the operation level of the output frequency and hysteresis width for operation release. If the output frequency exceeds the set operation level, an ON signal can be output from terminals Y1 to Y5. (Hysteresis width): 0.0 to 30.0 Hz
This function is used when E33 Overload early warning (operation selection) is set to 1.
E36 Frequency detection 2 (operation level) E 3 6 F D T 2
L E V E L
This function determines the operation (detection) level 2 of the output frequency for operation release. This function operates the same as “E31 Frequency detection 1 (operation level)”. For details, see the explanation for E31.
E37 Overload early warning 2 (operationlevel) E 3 7 O L 2
L E V E L
This function determines the operation level 2 of the output current. This function operates same as E33 output current and E35 setting.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-25
Page 80
Display during running and stopping During running, the items selected in E43 LED monitor (display selection) are displayed. In E44 LED monitor (display at stopping), specify whether to display selected items or the same items as during running.
E40 Display coefficient A E41 Display coefficient B E 4 0 C OE F E 4 1 C OE F
A B
Value of E43
Setting range:
E44 = 0
Display coefficient A: -999.00 to 0.00 to +999.00 Display coefficient B: -999.00 to 0.00 to +999.00 at stopping
These coefficients are conversion coefficients which are used to determine the load and line speed and the PID controller target value and feedback (process) amount displayed on the LED monitor.
1
Although the setting range is ±999.00, the effective range of display data is 0.01 to 200.00. Therefore, values smaller or larger than this range are limited to a minimum value of 0.01 or a maximum value of 200.00.
2 3 4 5
Target value and feedback amount of PID controller
6
Set the maximum value of display data in E40 Display coefficient A and the minimum value in E41 Display coefficient B.
7 8 9 10 11 12
Displayed value = (target value or feedback amount) x (Display coefficient A - B) + B during during at stopping running running output frequency before slip compensation (Hz)
set frequency value (Hz) output frequency before slip set compensation (Hz) frequency value (Hz) set frequency value (Hz) output current (A) output voltage command value (V) synchronous synchronous speed (rpm) speed set value (rpm) line speed line speed (m/min) set value (m/min) load speed (rpm) set load speed (rpm)
0
Load and line speed Use display coefficient A. Displayed value = output frequency x (0.01 to 200.00)
E44 = 1 calculated torque value (%) output power (kW) PID target value 1 (direct input from keypad panel) PID target value 2 (input from F02 Frequency 1) PID feedback amount
Note: For E43 = 10 to 12, the data is displayed only if selected in H20 PID control (operation selection).
E42 Display filter
Display at frequency setting
E 4 2 D I S P L A Y
When a set frequency is checked or changed by the keypad panel, the value shown below is displayed.
F L
Setting range: 0.0 to 5.0 seconds Among data in E43 LED monitor (display selection), some data need not be displayed instantaneously when the data changes. For such data, a flicker suppression filter can be used.
Display Output current Output voltage
Value 8 9
Display Calculated torque value Power consumption
E43 LED monitor (display selection) E44 LED monitor (display at stopping) E 4 3 L E D E 4 4 L E D
Value of E43 0,1,2,3,4
Monitored items in E43 LED monitor (display selection) Value 3 4
Select the display item by using E43 LED monitor (display selection). This display is not affected by E44 LED monitor (display at stopping). Frequency Setting set value of frequency (Hz)
5 set value of synchronous speed (rpm)
6 set value of line speed (m/min.)
7 set value of load speed (rpm)
8,9 set value of frequency (Hz)
10,11,12 set value of frequency (Hz)
Note: For E43 = 10 to 12 the data is displayed only if selected in H20 PID control (operation selection).
MN T MN T 2
The data during drive operation, stopping, at frequency setting, and at PID setting is displayed on the LED. 5-26
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA