For the GE AF-300G11, Fanuc AF-300G11 and GE Fanuc AF-300G11

Page 61

5.3 Function Explanation F: Fundamental function F00 Data protection F 0 0 D A T A

Set value

P R T C

0 : data can be changed 1 : data cannot be changed

This function protects the system by blocking any data changes from the keypad panel. Setting procedure: 0 to 1:

keys simultaneously to Press the STOP and change the value from 0 to 1, then press the

1 to 0:

FUNC DATA to validate the change.

keys simultaneously Press the STOP and to change the value from 1 to 0, then press the

FUNC DATA key to validate the change.

F01 Frequency setting 1 F 0 1 F R E Q

CMD 1

This function determines the method to be used for setting frequency. NOTE: Use only one terminal - V2 or C1, exclusively. 0:

Keypad operation (

1:

Voltage input (terminal 12 and V2) (0 to +10 VDC, 0 to +5VDC) Current input (terminal C1) (4 to 20 mA DC) Voltage and current input (terminals 12 and C1) Reversible operation with polarity (terminal 12) (0 to ± 10 VDC) Reversible operation with polarity (terminal 12 and V2) (0 to ± 10 VDC)

2: 3: 4: 5:

or key)

Related functions E01 to E09 (Set values 21 6: 7: 8: 9:

Inverse mode operation (terminal 12 and V2) (+10 to 0 VDC) Inverse mode operation ( terminal C1)(20 to 4 mA DC) UP/DOWN control 1 (initial freq. = 0 Hz UP/DOWN control 2 (initial freq. = last value)

F02 Operation method F 0 2 O P R

M E T H O D

This function determines the input method for operation commands. 0:

Keypad operation ( FWD or

1:

Terminal operation ( STOP key active)

2:

Terminal operation ( STOP key inactive)

3:

Terminal operation ( STOP key active) with GE start software

4:

Terminal operation ( STOP key inactive) with GE start software

REV or STOP key)

This function can only be changed when terminals FWD Related functions E01 to E09 (Set values 17, 18) 10. PATTERN operation Related functions: C21 to C28 and are open.

REMOTE/LOCAL switching from the keypad panel automatically changes the set value from 0 to 3 of this function.

11: DI option or Pulse train input For details, see instruction manual on options. Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

REV

5-7

Page 62

GE Start Software Selection During Terminal Operation Active: Setting 3 or 4

Inactive: Setting 1 or 2 POWER ON POWER

RESET

NETWORK MODE

POWER

FWD

FWD

OUTPUT

OUTPUT

ALARM

ALARM

RESET

RESET

FWD

FWD

OUTPUT

OUTPUT

ALARM

ALARM

NETWORK

NETWORK

(LE-CM)

(LE-CM)

FWD

FWD

(TERMINAL)

ER6

Multi Alarms*

(TERMINAL)

FWD

FWD

(NETWORK)

(NETWORK)

OUTPUT

OUTPUT

ALARM

ALARM

ER6

ER6 RESET

* See Alarm Mode, page 4-15. Note: Start Software does not work in AUTO RESET mode or PROGRAMMING mode

Stop Key Mode Selection During Terminal Operation Active: Setting 1 or 3

Inactive: Setting 2 or 4 STOP KEY FWD TERMINAL MODE

STOP KEY NETWORK MODE

FWD

STOP

STOP

OUTPUT

OUTPUT

ALARM

ALARM

ER6

NETWORK

NETWORK

(LE-CM)

(LE-CM)

FWD

FWD

(TERMINAL)

(TERMINAL)

STOP

STOP

OUTPUT

OUTPUT

ALARM

ALARM

5-8

ER6

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 63

Frequency Setting Block Diagram

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

5-9

Page 64

F03 Maximum output frequency 1 F 0 3 M A X

FO7 Acceleration time 1 F08 Deceleration time 1

H z – 1

Setting range 50 to 400 Hz

F 0 7 A CC F 0 8 D E C

This function sets the maximum output frequency for Motor 1.

Setting range

Setting a value higher than the rated value of the device to be driven may damage the motor or machine. Match the device rating when setting this function.

ACC TIME1: 0.01 to 3,600 seconds DEC TIME1: 0.01 to 3,600 seconds

These functions set the acceleration time for the output frequency from startup to maximum frequency, as well as the deceleration time from maximum frequency to operation stop.

F04 Base frequency 1 F 0 4 B A S E

T I M E 1 T I M E 1

H z – 1

Acceleration and deceleration times are represented by the three most significant (high-order) digits.

Setting range 25 to 400 Hz This function sets the maximum output frequency in the constant torque range of Motor 1 or the output frequency at the rated output voltage. Match the motor rating. Note: If the value of Base frequency 1 is set higher than that of Maximum output frequency 1, the output voltage does not increase to the rated voltage. The maximum frequency limits the output frequency.

Set acceleration and deceleration times with respect to maximum frequency. The relationship between the set frequency value and acceleration/deceleration times is as follows: Set frequency = maximum frequency The actual operation time matches the set value.

F05 Rated voltage 1 F 0 5 R A T ED

Setting range

Set frequency < maximum frequency

V – 1

The actual operation time differs from the set value.

230V AC series: 0, 80 to 240V 460 V series: 0, 320 to 480V

This function sets the rated value of the voltage output to Motor 1. Note that a voltage greater than the supply (input) voltage cannot be output. Value 0 terminates operation of the voltage regulator function, thereby resulting in the output of a voltage proportional to the supply voltage.

Acceleration *deceleration operation time = set value x (set frequency/maximum frequency) STOP

FWD

Note: If the value of Rated voltage 1 is set higher than Maximum output voltage 1, the output voltage does not increase to the rated voltage. The maximum output voltage limits the output voltage.

FO6 Maximum output voltage 1 F 0 6 M A X

Setting range

Note: If the set acceleration and deceleration times are set too low, even though the resistance torque and moment of inertia of the load are great, the torque limiting function or stall prevention function are activated, which prolongs the operation time beyond that stated above.

V – 1

230 V AC series: 80 to 240 VAC 460 VAC series: 320 to 480 VAC

This function sets the maximum value of the voltage output for Motor 1. Note that a voltage higher than the supply (input) voltage cannot be output.

5-10

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 65

F09 Torque Boost 1 F 0 9 T RQ

F 1 0 E L C T R N

BOO S T 1

Set value

This is a Motor 1 function. The following can be selected: Selection of load characteristics such as automatic torque boost, square law reduction torque load, proportional torque load, constant torque load. Enhancement of torque (V/f characteristics), which is lowered during low-speed operation. Insufficient magnetic flux of the motor due to a voltage drop in the lowfrequency range can be compensated.

O L 1

0: Inactive 1: Active (for general-purpose motor) 2: Active (for forced air motor)

This function specifies whether to operate the electronic thermal O/L relay and selects the target motor. When a general-purpose motor is selected, the operation level is lowered in the low speed range according to the cooling characteristics of the motor. F 1 1 O L

L E V E L 1

The setting range is 20 to 135% of the rated drive current. Setting Range 0.0

Characteristics Selected Automatic torque boost, where the torque boost value of a constant torque load (a linear change) is automatically adjusted.

0.1 to 0.9

Square law reduction torque for fan and pump loads

1.0 to 1.9

Proportional torque for middle class loads between square law reduction torque and constant torque (linear change)

2.0 to 20.0

Constant torque (linear change)

◆Torque characteristics < Square law reduction torque >

This function sets the operation level current for the electronic thermal O/L relay. Enter a value from 1 to 1.1 times the rated motor current value.

< Proportional torque >

F 1 2 T I M E

C N S T 1

The setting range is 0.5 to 75.0 minutes (in 0.1 minute increments). The time from when 150% of the operation level current flows continuously to when the electronic thermal O/L relay activates can be set with this function. < Constant torque >

Since a large torque boost value creates over-excitation in the low-speed range, continued operation may cause the motor to overheat. Check the characteristics of the driven motor.

F13 Electric thermal O/L relay (for braking) F 1 3 D BR

F10 Electric thermal O/L relay (operation selection) F11 Electric thermal O/L relay (level) F12 Electric thermal O/L relay (thermal time) The electronic thermal O/L relay manages the output frequency, output current, and operation time of the inverter to prevent the motor from overheating when 150% of the set current value flows for the time set by F12 (thermal time constant). Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

O L

This function controls the frequent use and continuous operating time of the braking resistor to prevent the resistor from overheating. Drive Capacity 10 Hp or less

15 Hp or more

5-11

Operation 0: Inactive 1: Active (built-in braking resistor) 2: Active (external braking resistor) 0: Inactive

Page 66

F14 Restart after momentary power failure (operation selection) F 1 4 R E S T A R T

The function for detecting power failure and activating protective operation (i.e., alarm output, alarm display, drive output cutoff) for undervoltage can be selected. The automatic restart function (for automatically restarting a coasting motor without stopping) when the supply voltage is recovered can also be selected.

Setting range: 0 to 5 The following table lists the function details. This function selects operation if a momentary power failure occurs.

Set Value 0

Function Name Inactive (intermediate drive trip)

Operation at Power Failure If undervoltage is detected, the drive will immediately trip and an undervoltage fault (LU) is displayed. The drive output stops and the motor will coast to a stop.

Operation at Power Recovery The drive operation is not automatically restarted. Input a reset command and operation command to restart.

1

Inactive (drive trip at recovery)

If undervoltage is detected, the drive output stops and the motor will immediately coast to a stop. A drive fault is not activated.

An undervoltage fault (LU) is activated at power recovery. Drive operation is not automatically restarted. Input a reset command to restart operation.

2

Inactive (drive trip after deceleration to a stop at power failure)

When the DC bus voltage reaches the operation The drive operation is not automatically voltage level (H15), a controlled deceleration to a restarted. Input a reset command and stop occurs. The drive collects the inertial energy operation command to restart operation. of the load to maintain the DC bus voltage and controls the motor until it stops, then an undervoltage fault (LU) is activated. The drive will automatically decrease the deceleration time if necessary. If the amount of inertial energy from the load is small, and the undervoltage level is achieved before the motor stops, the undervoltage fault is immediately activated and the motor will coast to a stop.

3

Active (operation ride- When the DC bus voltage reaches the operation through; for high-inertia voltage level (H15), energy is collected from the inertia of the load to maintain the DC bus voltage loads) and extend the ride-through time. The drive will automatically adjust the deceleration rate to maintain DC bus voltage level. If undervoltage is detected, the protective function is not activated, but drive output stops and the motor coast to a stop.

Operation is automatically restarted. For power recovery during ride-through, the drive will accelerate directly to the original frequency. If undervoltage is detected, operation automatically restarts with the frequency selected at the time that the undervoltage was detected.

4

Active (restart with the frequency at the time of power failure)

If undervoltage is detected, the protective function is not activated. The drive output stops and the motor will coast to a stop.

Operation is automatically restarted with the frequency selected at the time of power failure.

5

If undervoltage is detected, the protective function Active (restart with start frequency; for low- is not activated, but drive output stops. inertia loads)

Operation is automatically restarted with the frequency set by F23, “Starting frequency”.

Function codes H13 to H16 are provided to control a restart operation after momentary power failure. These functions should be understood and used. The pick-up (speed search) function can also be selected as a method of restarting when power is recovered after a momentary failure. (For setting details, see function code H09.) The pick-up function searches for the speed of the coasting motor to restart the motor without subjecting it to excessive shock.

5-12

In a high-inertia system, the reduction in motor speed is minimal even when the motor is coasting. A speed search time is required when the pick-up function is active. In such a case, the original frequency may be recovered sooner when the function is inactive and the operation is restarted with the frequency prior to the momentary power failure. The pick-up function works in the range of 5 to 120 Hz. If the detected speed is outside this range, restart the motor using the regular restart function.

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 67 read from a scan by OCR; it may hold reading errors

Power failure

A. V

Set value : 0

Main circuit DC voltage

Power recovery y

Output frequency

LU trip

Vv

Set value : 1 ’

Main circuit DC voltage v

Output frequency

LUtrip 7

Vv

ON

>

Set value : 2

Main circuit DC voltage

: H15 ; Operation continuation level

4

Output frequency

Vv

LU trip |

| ON

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Vv

Power failure

Set value : 3

Main circuit DC voltage

Output frequency (motor speed)

\/ H15 V

Power recovery

* : Operation continuation level v

LU trip |

Output I

(terminals Y1 to Y5) Set value : 4

Main circuit DC voltage

Output frequency

(motor speed)

LU trip Output |

(terminals Y1 to Y5)

Set value : 5

Main circuit DC voltage

Output frequency (motor speed)

LU trip | Output I

(terminals Y1 to Y5)

A

» >

Vv

Under voltage

Vv

»

>

+ Synchronization

»

< - Acceleration

» ~

|_on

Under voltage |

Vv

» ~

_H13:Waiting time: /

» >

Vv

ON

Vv

Note : Dotted-dashed lines indicate motor speed.

Page 68

F15 Frequency limiter (High) F16 Frequency limiter (Low)

F18 Bias frequency

F 1 5 H F 1 6 L

This function adds a bias frequency to the set frequency value from analog input.

F 1 8 F R E Q

L I M I T E R L I M I T E R

Set values: 0 to 400 Hz

The operation follows the figure below. If the bias frequency is higher than the +Maximum frequency or lower than the -Maximum frequency, it is limited to the +Maximum or -Maximum frequency.

These functions are used to define the upper and lower limits of the set frequency.

F20 DC injection Brake (starting) F21 DC injection brake (operation level) F22 DC injection brake (time)

The drive output starts with the start frequency when operation begins, and stops with the stop frequency when operation ends.

F 2 0 D C

If the upper limit value is less than the lower limit value, the upper limit value overrides the lower limit value.

BR K

H z

Set values: 0 to 60 Hz Starting frequency: This function sets the frequency with which to start a DC injection brake in order to decelerate the motor to a stop.

F17 Gain F 1 7 F R E Q

B I A S

G A I N

F 2 1 D C

This function assigns the rate of the set frequency value to analog input.

BR K

L V L

Set values: 0 to 100%

Operation follows the figure below.

Operation level: This function sets the output current level, when a DC injection brake is applied, as a percentage of the rated output current in 1% increments. F 2 2 D C

BR K t

Set value

0.0: Inactive 0.1 to 30.0 seconds

Time: This function sets the time for a DC injection brake operation.

CAUTION Do not use the drive brake function for mechanical holding. Injury may result.

5-14

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 69

F23 Starting frequency (frequency) F24 Start frequency (Holding time) F25 Stop frequency F 2 3 S T A R T

1.

H z

Reducing the set value adversely affects the output current waveform (i.e., higher harmonics), increases motor loss, and raises motor temperature. For example, at 0.75 kHz, reduce the motor torque by about 15%. Increasing the set value increases drive loss and raises drive temperature.

Setting range: 0.1 to 60 Hz

2

The starting frequency can be set to reserve the torque at startup and can be sustained until the magnetic flux of the motor is established.

F27 Motor sound (sound tone)

Frequency: This function sets the frequency at startup.

F 2 7 M T R

F 2 4 H O L D I N G t

Setting range: 0.1 to 10.0 seconds Holding time: This function sets the holding time during which the start frequency is sustained at startup. The holding time does not apply during switching between forward and reverse. The holding time is not included in the acceleration time. The holding time also applies when pattern operation (C21) is selected. The holding time is included in the timer value. F 2 5 S T O P

T O N E

Setting range: 0 , 1, 2 , 3 The tone of motor noise can be altered if the carrier frequency is 7 kHz or lower. Use this function as required.

F30 FMA terminal (voltage adjustment) F31 FMA terminal (function selection) F 3 0 F MA

V – A D J

Setting range: 0 to 200% Monitor data (e.g.,output frequency, output current) can be output to terminal FMA as a DC voltage. The amplitude of the output can also be adjusted. This function adjusts the voltage value of the monitor item selected in F31 when the monitor amount is 100%. A value from 0 to 200% can be set in 1% increments.

H z

Setting range: 0.1 to 6.0 Hz This function sets the frequency at stop.

The operation will not start if the starting frequency is less than the stopping frequency or if the set frequency is less than the stopping frequency.

F26 Motor sound (carrier frequency) F 2 6 M T R

S O U N D

This function adjusts the carrier frequency to prevent resonance with the machine system, reduce motor and drive noise, and also reduce leakage current from output circuit wiring. Drive Capacity 75 Hp or less 100 Hp or more Carrier frequency Motor noise Output current waveform Leakage current Noise occurrence

F 3 1 F MA

This function selects the monitor item to be output to Terminal FMA. Value 0

1

Setting Range 0.75 to 15kHz 0.75 to 10kHz

2 3 4 5 6 7 8

Low, High High, Low Bad, Good Small amount Large amount Extremely low High

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

F U N C

5-15

Monitor Item Output frequency 1 (before slip compensation) Output frequency 2 (after slip compensation) Output current Output voltage

9

Output torque Load rate Output PID feedback amount PG feedback amount (only when option is installed) DC link circuit voltage

10

Universal AO

100% Monitor Amount Maximum output frequency Maximum output frequency 2x rated output current of drive 230V series: 250V 460V series: 500V 2x rated motor torque 2x rated load of motor 2x rated drive output Feedback amount at 100% Synchronous speed at maximum frequency 230V series: 500V 460V series: 1,000V Output from RS485 or Bus option

Page 70

F33 FMP terminal (pulse rate) F34 FMP terminal (voltage adjustment) F35 FMP terminal (function selection)

F36 30Ry operation mode F 3 6 3 0 R Y

Monitor data (e.g., output frequency, output current) can be output to terminal FMP as pulse voltage. Monitor data can also be sent to an analog meter as average voltage. When sending data to a digital counter or other instrument as pulse output, set the pulse rate in F33 to any value and the voltage in F34 to 0%. When data is sent to an analog meter or other instrument as average voltage, the voltage value set in F34 determines the average voltage, and F33 is fixed at 2670 (p/s). F 3 3 F MP

P L U S E S

The F33 function sets the pulse frequency of the monitor item selected in F35.

Value 0

1

Drive no power At normal At alarm Drive no power At normal At alarm

Operation 30A - 30C: OFF, 30B - 30C: ON 30A - 30C: OFF, 30B - 30C: ON 30A - 30C: ON, 30B - 30C:OFF 30A - 30C: OFF, 30B - 30C: ON 30A - 30C: ON, 30B - 30C: OFF 30A - 30C: OFF, 30B - 30C: ON

If the set value is 1, contacts 30A and 30C are connected when the drive control voltage is established (about one second after power on).

F 4 0 D R V F 4 1 B RK

T R Q I T R Q I

The torque limit operation calculates motor torque from the output voltage, current and the primary resistance value of the motor, and controls the frequency so the calculated value does not exceed the limit. This operation enables the drive to continue operation under the limit even if a sudden change in load torque occurs.

Pulse frequency (p/s) = 1/T

Limits are set for driving torque and braking torque.

Duty (%) = T1/T x 100

When this function is activated, acceleration and deceleration operation times are longer than the set values.

Average voltage (V) = 15.6 x T1/T

V – A D J

Function Torque limit (driving)

Set value 0%: The pulse frequency varies depending on the amount of the monitor item selected in F35 (max. value is the value set in F33). The F34 function sets the average voltage of pulse output to terminal FMP.

Torque limit (braking)

1 to 200%: Pulse frequency is fixed at 2,670 p/s. The average voltage of the monitor item selected in F35, when the monitor amount is 100%, is adjusted in the range 1 - 200%, in 1% increments (pulse duty varies). F 3 5 F MP

This function specifies whether to activate (excite) the alarm output relay (30Ry) for any fault at normal or alarm status.

F40 Torque limit 1 (drive) F41 Torque limit 1 (brake)

Set values: 300 to 6,000 p/s, in 1 p/s increments

F 3 4 F MP

MO D E

Set Value 20% to 200%

Operation The torque is limited to the set value.

999 20% to 200%

Torque limiting inactive The torque is limited to the set value.

0

Automatically prevents OU trip due to power regeneration effect Torque limiting inactive

999

F U N C

The F35 function selects the monitor item to be output to terminal FMP. The set value and monitor items are the same as those used for F31 (refer to table).

5-16

WARNING When the torque limit function is selected, an operation may not match the set acceleration and deceleration time or set speed. The machine should be so designed that safety is ensured even when operation does not match the set values.

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA