Page 51
4.3.13 Data Copy Select 9. Data Copy to display the Data Copy on the Program Menu screen. Read screen. A copy operation is then performed in the following order: function data is read from the first inverter, the keypad panel is removed and attached to a second inverter, the data from the first inverter is written to and stored in the second inverter. The “verify” feature also makes it possible to compare and check differences in the data stored in the keypad panel and the data stored in the inverter. Read data
Write data
60.00
RUN
Attach keypad panel, Turn power ON.
FWD
PRG
PRG > PRG MENU F/D > LED SHIFT
60.00
RUN
PRG
FWD
PRG > PRG MENU F/D > LED SHIFT
60.00 1.DATA SETTING 2.DATA CHECK 3. OPR MNTR 4. I/O CHECK
PRG
60.00 1.DATA SETTING 2.DATA CHECK 3. OPR MNTR 4. I/O CHECK
5. MAINTENANCE 6. LOAD FCTR 7. ALM INF 8. ALM CAUSE > 9. DATA COPY FUNC DATA
<DATA COPY> READ
Data copy screen
5. MAINTENANCE 6. LOAD FCTR 7. ALM INF 8. ALM CAUSE > 9. DATA COPY
Mode (read mode)
FUNC DATA
<DATA COPY> 30 HP-2
FUNC DATA
READ
Drive type of data stored by keypad panel
<DATA COPY> READ Reading
<DATA COPY> 30 HP-2 WRITE
<DATA COPY> 30 HP-2 READ COMPLETE
Data of drive type read by keypad panel Read complete
FUNC DATA
<DATA COPY> 30 HP-2 WRITE
Remove keypad pananel
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Mode (write mode)
Writing
4-13
<DATA COPY> 30 HP-2 WRITE COMPLETE
Write complete
Page 52
Data check (verify)
Error processing
60.00 1. Change disabled during operation
RUN
If a write operation is attempted during a drive operation, or vice versa, the error message below will appear. After stopping the drive and pressing RESET retry the write operation.
FWD
PRG > PRG MENU F/D > LED SHIFT PRG
<DATA COPY> 30HP-2
60.00 1.DATA SETTING 2.DATA CHECK 3. OPR MNTR 4. I/O CHECK
WRITE INV RUNNING
2. Memory error
5. MAINTENANCE 6. LOAD FCTR 7. ALM INF 8. ALM CAUSE > 9. DATA COPY
If a write operation is attempted while data has not been saved (i.e. no data) in the keypad panel data memory during the read mode or when the drive type of data read by keypad panel is different from the drive type to which data is to be written, the following error message will appear.
FUNC DATA
<DATA COPY> 30HP-2 READ
<DATA COPY> Drive type of data stored in the keypad panel
WRITE MEMORY ERROR
3. Verify error <DATA COPY> 30HP-2
During a data check (verify) operation, if data stored in the keypad panel differs from data stored in the drive, the following error message is displayed to indicate the function number. The data is suspended. To continue the data check and check for other mismatching data, press FUNC DATA . To stop the data check and switch to another operation, press RESET .
WRITE
<DATA COPY> 30 HP-2 VERIFY
Mode (data check) <DATA COPY> 50HP-2 WRITE ERR-F25
FUNC DATA
<DATA COPY> 30 HP-2 VERIFY Data check in progress <DATA COPY> 30 HP-2 VERIFY COMPLETE
Data check complete
4-14
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 53
4.3.14 Alarm Mode If an alarm occurs, the Alarm Screen indicating the alarm contents is displayed. Use
∧ and
∨ to display alarm history and multiple alarms (if more than two alarms occur simultaneously). Alarm detection on order
1.OC1
Alarm code No. of consecutive occurences Alarm name
1=xxx xxx xxxxxxxxxxxxx PRG>PRG MENU RESET>RESET
Operation guide
Alarm detection order LED display 5. 4. 3. 2. 1. Blank Blank Blank Blank Alarm code: See Table 6-1-1 Operation method
LCD display 5 4 3 2 1 0 -1 -2 -3
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Description No. 5 alarm No. 4 alarm No. 3 alarm No. 2 alarm No. 1 alarm (more than two alarms occurred) Latest alarm (only one alarm occurred/alarm released) Previous alarm history Alarm history before previous alarm Alarm history two times before previous alarm
4-15
Page 54
Notes:
4-16
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 55
5. Function Selection 5.1 Function Select List
F:Fundamental Functions Pg.
5-7
Func.
Name
No.
Unit
Min.
DATA PRTC
0, 1
-
-
0
1
N
F01
Frequency command 1
F01
FREQ CMD 1
0 to 11
-
-
0
1
N
F02
Operation method
F02
OPR METHOD
0 to 4
-
-
0
1
N
F03
Maximum frequency 1
F03
MAX Hz-1
50 to 400Hz
Hz
1
60
1
N
F04
Base frequency 1
F04
BASE Hz-1
25 to 400Hz
Hz
1
60
1
N
F05
Rated voltage 1
F05
RATED V-1
0V:
V
1
230: (230V class)
1
(Output voltage proportional to source voltage)
Maximum voltage 1
F06
MAX V-1
(at Maximum frequency 1) F07
Acceleration time 1
F07
ACC TIME1
F08
Deceleration time 1
F08
DEC TIME1
F09
Torque boost 1
F09
230V class:
80 to 240V
460V class:
320 to 480V
230V class:
80 to 240V
460V class:
320 to 480V
460: (460V class)
V
1
0.01 to 3600 s s
0.01
TRQ BOOST1
0.0, 0.1 to 20.0
-
0.1
N
6.0
20.0
12
12
2.0
Y Y
F10
Electronic
(Select)
F10
ELCTRN OL1
0, 1, 2
-
-
1
3
Y
Thermal 1
(level)
F11
OL LEVEL1
20 to 135% of drive rated current
A
0.01
Motor rated current
1
Y
(time constant)
F12
TIME CNST1
0.5 to 75.0 min min
0.1
19
Y
F13
DBR OL
[ Up to 10 HP ]
-
-
F12
Electronic thermal overload relay (for braking resistor)
0, 1, 2
F14
Restart mode after
F14
RESTART
0 to 5
0 to 400 Hz
F15
Frequency
(high)
F15
H LIMITER
Limiter
(low)
F16
L LIMITER
10.0
3 Y
0 -
-
Hz
1 momentary power failure
F16
5.0
1
0
1 0
N
70
1
Y
0
1
N
F17
Gain (for frequency set signal)
F17
FREQ GAIN
0.0 to 200.0%
%
0.1
100.0
1
Y
F18
Bias frequency
F18
FREQ BIAS
-400.0 to +400.0 Hz
Hz
0.1
0.0
1
Y
F20
DC brake
(starting frequency)
F20
DC BRK Hz
0.0 to 60.0 Hz
Hz
0.1
0.0
3
F21
(braking level)
F21
DC BRK LVL
0 to 100%
%
1
0
1
F22
(braking time)
F22
DC BRK t
0.0s (inactive)
s
0.1
0.0
3
F23
START Hz
0.1 to 60.0 Hz
Hz
0.1
0.5
3
F24
HOLDING t
0.0 to 10.0 s s
0.1
0.0
3
F25
STOP Hz
0.1 to 6.0 Hz
Hz
0.1
0.2
1
F26
MTR SOUND
0.75 to 15 kHz (10kHz)
kHz
1
2
1
Y
F27
SOUND TONE
0 to 3
-
-
0
1
Y
(voltage adjust)
F30
FMA V-ADJ
0 to 200%
%
1
100
1
Y
(function)
F31
FMA FUNC
0 to 10
-
-
0
1
Y
(pulse rate)
F33
FMP PULSES
300 to 6000 p/s (full scale)
p/s
1
1440
1
Y
F34
(voltage adjust)
F34
FMP V-ADJ
0%, 1 to 200%
%
1
0
1
Y
F35
(function)
F35
FMP FUNC
0 to 10
-
-
0
1
Y Y
F23
Starting frequency (holding time)
F24 F25
Stop frequency
F26
Motor sound
F27 F30
F33
FMA
FMP
F36
30RY operation mode
F40
Torque limiter1
F41 F42
(carrier freq.) (sound tone)
F31
5-17
1
460: (460V class)
[ 15 HP and above ]
5-16
230: (230V class)
N
F11
F13
5-15
Change during op
F00
F06
5-14
Data Formst
40 HP
Data protection
5-10
5-12
Factory Setting 30 HP
F00
(at Base frequency 1)
5-11
Setting Range
LCD Display
Torque vector control 1
F36
30RY MODE
0, 1
-
-
0
1
(driving)
F40
DRV TRQ 1
20 to 200%, 999
%
1
999
1
(braking)
F41
BRK TRQ 1
0%, 20 to 200%, 999
999
1
F42
TRQVECTOR1
0, 1
0
1
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
-
5-1
-
Y
N
Y N
Page 56
E:Terminal Extension Functions Pg.
Func. Name
No.
5-18/21
Change During op
E01 X1 FUNC
0
1
N
E02 X2 FUNC
1
1
N
E03
X3 terminal function
E03 X3 FUNC
2
1
N
E04
X4 terminal function
E04 X4 FUNC
3
1
N
E05
X5 terminal function
E05 X5 FUNC
4
1
N
E06
X6 terminal function
E06 X6 FUNC
5
1
N
E07
X7 terminal function
E07 X7 FUNC
6
1
N
E08
X8 terminal function
7
1
N
E09
X9 terminal function
E08 X8 FUNC E09 X9 FUNC
8
1
N
E10
Acceleration time 2 Deceleration time 2
E10 ACC TIME2 E11 DEC TIME2
Acceleration time 3 Deceleration time 3
E15
Acceleration time 4 Deceleration time 4
E16
Torque limiter 2
E13
0 to 32
-
20.00
12
Y
6.00
20.00
12
Y
E12 ACC TIME3 E13 DEC TIME3
6.00
20.00
12
Y
6.00
20.00
12
Y
E14 ACC TIME4 E15 DEC TIME4
6.00
20.00
12
Y
6.00
20.00
12
Y Y
E16 DRV TRQ 2 (braking) E17 BRK TRQ 2 E20 Y1 FUNC (driving)
E20
Y1 terminal function
E21
Y2 terminal function
E21 Y2 FUNC
E22
Y3 terminal function
E22 Y3 FUNC
E23
Y4 terminal function
E24
0.01 to 3600 s s
-
6.00
0.01
20 to 200%, 999
%
1
999
1
0%, 20 to 200%, 999
%
1
999
1
Y
0
1
N
0 to 33
1
1
N
2
1
N
E23 Y4 FUNC
7
1
N
Y5A, Y5C terminal function
E24 Y5 FUNC
10
1
N
E25
Y5 RY operation mode
E30
FAR function
(Hysteresis)
E25 Y5RY MODE E30 FAR HYSTR
E31
FDT function
E32 signal
E31 FDT1 LEVEL (Hysteresis) E32 FDT1 HYSTR
E33
OL function
(mode select)
(level)
E33 OL1 WARNING
-
-
0,1
-
1
0
1
N
0.0 to 10.0 Hz
Hz
0.1
2.5
3
Y
0 to 400 Hz
Hz
1
60
1
0.0 to 30.0 Hz
Hz
0.1
1.0
3
0: Thermal calculation
-
-
0
1
A
0.01 motor rated current
19
1: Output current
5-25 E34 signal
(L
E35 E36
FDT2 function
E37
OL2 function
E40
Display coefficient A
E41
Display coefficient B
E42
LED Display filter
E43
LED Monitor
E45
5 to 200% of rated drive current
(timer)
E35 OL1 TIMER
0.1 to 60.0 s s
0.1
10.0
3
E36 FDT2 LEVEL (level) E37 OL2 LEVEL
0 to 400 Hz
Hz
1
60
1
5 to 200% of rated drive current
A
0.01 motor rated current
19
-999.00 to 999.00
-
0.01
0.01
12
-999.00 to 999.00
-
0.01
0.00
12
Y
0.0 to 5.0 s s
0.1
0.5
3
Y
E40 COEF A E41 COEF B E42 DISPLAY FL (function) E43 LED MNTR
LCD Monitor
Y
0 to 12
-
-
0
1
Y
E44 LED MNTR2 (function) E45 LCD MNTR
0, 1
-
-
0
1
Y
0, 1
-
-
0
1
Y
E46 LANGUAGE (contrast) E47 CONTRAST
0 to 5
-
-
1
1
Y
0(soft) to 10(hard)
-
-
5
1
Y
0 to 400 Hz
Hz
1
0
1 1 1 1 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
(language)
E47
Y
E34 OL1 LEVEL
(level)
E46
Y
(level)
(display in STOP mode)
E44 5-27
Data Format
40 HP
X1 terminal function
E17
5-26
Factory Setting 30 HP
X2 terminal function
E14
5-24
Min.
E01
E12
5-22/24
Unit
E02
E11
5-22
Setting Range
LCD Display
C:Frequency Control Functions C01
Jump
(Jump freq. 1)
C01 JUMP Hz 1
C02 frequency
(Jump freq. 2)
C02 JUMP Hz 2
C03 JUMP Hz 3 (Hysteresis) C04 JUMP HYSTR
(Jump freq. 3)
C03 C04 C05
Multistep
C06 frequency
C07 setting
C05 MULTI Hz-1 (Freq. 2) C06 MULTI Hz-2 (Freq. 3) C07 MULTI Hz-3 (Freq. 1)
0 0 to 30 Hz
Hz
1
3
0.00 to 400.00 Hz
Hz
0.01
0.00 0.00 0.00 0.00
C09
C08 MULTI Hz-4 (Freq. 5) C09 MULTI Hz-5
C10
(Freq. 6)
C10 MULTI Hz-6
0.00
C11
(Freq. 7)
C11 MULTI Hz-7
0.00
C12
(Freq. 8)
0.00
C13
C12 MULTI Hz-8 (Freq. 9) C13 MULTI Hz-9
C14
(Freq. 10) (Freq. 11)
0.00
C16
C14 MULTI Hz-10 C15 MULTI Hz-11 (Freq. 12) C16 MULTI Hz-12
0.00
C15 C17
(Freq. 13)
0.00
C18
C17 MULTI Hz-13 (Freq. 14) C18 MULTI Hz-14
C19
(Freq. 15)
C19 MULTI Hz-15
0.00
C08 5-28
0
(Freq. 4)
0.00
0.00
0.00 0.00
5-2
Y
Y
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 57
Pg.
5-29
Func. Name
No. C20
JOG frequency
C21
PATTERN
Setting Range
LCD Display (mode select)
C20 JOG Hz C21 PATTERN
Unit
Min.
Factory Setting
Data
Change
30 HP
Format during op Y
40 HP
0.00 to 400.00 Hz
Hz
0.01
5.00
5
0,1,2
-
-
0
1 s
0.01 operation
5-29/30
5-30
STAGE 1
Operation time: 0.00 to 6000 s
STAGE 2
F1 to F4 and R1 to R4
FREQ CMD 2
0 to 11
-
(terminal [12]) C31 (terminal [C1]) C32
BIAS 12
-100.0 to +100.0%
GAIN 12
(Stage 1)
C23
(Stage 2)
C24
(Stage 3)
C25
(Stage 4)
C26
(Stage 5)
C27
(Stage 6)
C28
(Stage 7)
C30
Frequency command 2
C31
Offset adjust
C32 5-31
C22 C23 C24 C25 C26 C27 C28 C30
C22
C33
Analog setting signal filter
N
0.00 F1
13
0.00 F1
13
STAGE 3
0.00 F1
13
STAGE 4
0.00 F1
13
STAGE 5
0.00 F1
13
STAGE 6
0.00 F1
13
STAGE 7
0.00 F1
13
-
2
1
%
0.1
0.0
4
Y
0.0 to +200.0%
%
0.1
100.0
3
Y
C33 REF FILTER
0.00 to 5.00s s
0.01
0.05
5
Y
P01 M1 POLES P02 M1-CAP
2 to 14
-
2
4
9
N
Up to 30 HP: 0.01 to 60 HP
Hp
0.01 motor capacity
5
Y
N
P:Motor Parameters P01
Number of motor 1 poles
P02
Motor 1
(capacity)
5-32
40 HP and above: 0.01 to 600 HP P03 P04 P05 P06
5-33
P07 P08 P09
P03 P04 (on-line tuning) P05 (no-load current) P06 (%R1 setting) P07 (%X setting) P08 Slip compensation control P09 (rated current)
(tuning)
M1-Ir
0.00 to 2000 A
A
0.01 motor rated current
19
M1 TUN1
0, 1, 2
-
-
0
21
M1 TUN2
0, 1
-
-
0
1
M1-Io
0.00 to 2000 A
A
0.01 standard rated value
19
M1-%R1
0.00 to 50.00%
%
0.01 standard rated value
5
M1-%X
0.00 to 50.00%
%
0.01 standard rated value
5
SLIP COMP1
0.00 to 15.00 Hz
Hz
0.01
0.00
5
DATA INIT
0, 1
-
-
0
1
AUTO-RESET
0, 1 to 10 times
-
1
0
1
RESET INT
2 to 20 s s
1
5
1
FAN STOP
0, 1
-
-
0
1
ACC PTN
0,1,2,3
-
-
0
1
REV LOCK
0, 1
-
-
0
1
START MODE
0, 1, 2
-
--
0
1
ENERGY SAV
0, 1
-
-
0
1
DEC MODE
0, 1
-
-
0
1
INST CL
0, 1
-
-
1
RESTART t
0.1 to 10.0 s s
0.1
0.00 to 100.00 Hz/s
Hz/s
0.01
10.00
5
3-phase, 230V class: 200 to 300V
V
1
200V class: 235V
1
N N N N N Y Y Y
H:High Performance Functions
5-34
5-35
5-36
H03 H04 (reset interval) H05 H05 H06 H06 Fan stop operation (mode select) H07 H07 ACC/DEC pattern H08 H08 Rev. phase sequence lock H09 H09 Start mode H10 H10 Energy-saving operation H11 H11 DEC mode H12 H12 Instantaneous OC limiting (restart time) H13 H13 Auto-restart H03
Data initializing
H04
Auto-reset
(times)
(freq. fall rate)
H14 FALL RATE (holding DC voltage) H15 HOLD V
H14 H15
3-phase, 460V class: 400 to 600V H16 5-37
5-38 5-39/40
5-41
(OPR command self hold time)
H18
Torque control
H19
Active drive
H20
PID control
H21
(feedback signal)
H22
(P-gain)
H23
(I-gain)
H24
(D-gain)
H25
(feedback filter)
H26
PTC thermistor
H28
Droop operation
H30
Serial link
H31
Modbus-RTU
H32
5-43
(mode select) (level)
H27
5-42
(mode select)
(function select)
H16 H18 H19 H20 H21 H22 H23 H24 H25 H26 H27 H28 H30
H34
(baud rate)
H35
(data length)
H36
(parity check)
H37
(stop bits)
H38
(no response error detection time)
H39
(response interval)
H33 H34 H35 H36 H37 H38 H39
3
0.0 to 30.0 s, 999 s
0.1
999
3
0, 1, 2
-
-
0
1
AUT RED
0, 1
-
-
0
1
PID MODE
0, 1, 2
--
-
0
1
FB SIGNAL
0, 1, 2, 3
-
-
1
1
P-GAIN
0.01 to 10.00 times
-
0.01
0.1
5
I-GAIN
0.0, 0.1 to 3600 s s
0.1
0.0
3
D-GAIN
0.00 s , 0.01 to 10.0 s s
0.01
0.00
5
FB FILTER
0.0 to 60.0 s s
0.1
0.5
3
PTC MODE
0, 1
0
1
PTC LEVEL
0.00 to 5.00V
V
0.01
1.60
5
DROOP
9.9 to 0.0 Hz
Hz
0.1
0.0
4
LINK FUNC
0, 1, 2, 3
-
-
0
1
0 (broadcast), 1 to 247
-
1
1
1
0, 1, 2, 3
-
-
0
1
TIMER
0.0 to 60.0 s s
-
2.0
3
BAUD RATE
0, 1, 2, 3
-
-
1
1
LENGTH
0 (8-bit fixed)
-
-
0
1
PARITY
0, 1, 2
-
-
0
1
STOP BITS
0 (2-bit), 1(1-bit)
-
-
0
1
NO RES t
0 (no detection), 1 to 60 s s
1
0
1
INTERVAL
0.00 to 1.00 s s
0.01
0.01
5
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
5-3
Y
400V class: 470V
TRQ CTRL
H31 ADDRESS (mode select on no response error) H32 MODE ON ER (timer)
1 0.5
SELFHOLD t
(address)
H33
0.1
N Y Y Y N N N Y Y N N
N Y N N Y Y Y Y Y Y Y Y N Y Y Y Y Y Y Y Y
Page 58
A. Alternative Motor Parameters A: Alternative Motor Parameters Pg.
Factory Setting
Func. Name
A01
Maximum frequency 2
LCD Display A01 MAX Hz-2
A02
Base frequency 2
A02 BASE Hz-2
A03
Rated voltage 2
A03 RATED V-2
No.
(at Base frequency 2 ) A04
5-44
Maximum voltage 2
A04 MAX V-2
Setting Range
Data
Change
Format
During op
Unit
Min.
50 to 400 Hz
Hz
1
60
1
N
25 to 400 Hz
Hz
1
60
1
N
V
1
230V class: 230
1
0 230V class:
80 to 240V
460V class:
320 to 480V
230V class:
80 to 240V
460V class:
320 to 480V
30 HP
40 HP
N
460V class: 460 V
1
230V class: 230
1
N Y
460V class: 460
A05
Torque boost 2
A05 TRQ BOOST2
0.0, 0.1 to 20.0
-
-
2.0
3
A06
Electronic
(select)
A06 ELCTRN OL2
0, 1, 2
-
-
1
1
Y
A07 thermal 2
(level)
A07 OL LEVEL2
20% to 135% if INV rated current
A
0.01 motor rated current
19
Y
A08 TIME CNST2
0.5 to 75.0 min min
0.1
A09 TRQVECTOR2 A10 M2 POLES
0, 1
-
-
2 to 14 poles pole
2
A11 M2-CAP
Up to 30 HP: 0.01 to 60 HP
HP
0.01
(thermal time constant)
A08 A09
Torque vector control 2
A10
Number of motor 2 poles
A11
Motor 2
(capacity)
5.0
10.0
3
Y
1
N
4
9
N motor capacity
5
0
40 HP and above: 0.01 to 600 HP
5-45
N
A12
(rated current)
A12 M2-Ir
0.00 to 2000 A
A
0.01 motor rated current
19
N
A13
(tuning)
A13 M2 TUN1
0, 1, 2
-
-
0
21
N
A14
(on-line tuning)
A14 M2 TUN2
0, 1
-
-
0
1
N
A15
(no-load current)
A15 M2-Io
0.00 to 2000 A
A
0.01 standard rated value
19
N
A16
(%R1 setting)
A16 M2-%R1
0.00 to 50.00%
%
0.01 standard rated value
5
Y
A17
(%X setting)
A17 M2-%X
0.00 to 50.00%
%
0.01 standard rated value
5
Y
A18
(slip compensation control 2)
A18 SLIP COMP2
0.00 to 15.00 Hz
Hz
0.01
0.00
5
Y
5-4
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 59
5.2 Alphabetical Function List PG. NAME 5-16 30RY operation mode 5-10 Acceleration time 1 5-22 Acceleration time 2 5-22 Acceleration time 3 5-22 Acceleration time 4 5-34 ACC/DEC Pattern 5-37 Active Drive 5-31 Analog setting signal filter 5-10 Base frequency 1 5-44 Base frequency 2 5-14 Bias frequency 5-34 Data initializing 5-7 Data protection 5-14 DC brake (Braking level) 5-14 DC brake (Braking time) 5-14 DC brake (Starting freq.) 5-36 DEC mode 5-10 Deceleration time 1 5-22 Deceleration time 2 5-22 Deceleration time 3 5-22 Deceleration time 4 5-26 Display coefficient A 5-26 Display coefficient B 5-41 Droop operation 5-11 Electronic Thermal 1 (Level) 5-11 Electronic Thermal 1 (Select) 5-11 Electronic Thermal 1 (Thermal time constant) 5-44 Electronic thermal 2 (Level) 5-44 Electronic thermal 2 (Select) 5-44 Electronic thermal 2 (Thermal time constant) 5-11 Electronic thermal overload relay (for DB resistor) 5-36 Energy-saving operation 5-34 Fan stop operation 5-25 FAR function (Hysteresis) 5-25 FDT function (Level) 5-25 FDT signal (Hysteresis) 5-25 FDT2 function (Level) 5-15 FMA (Voltage adjust) 5-15 FMA (Function) 5-16 FMP (Function) 5-16 FMP (Pulse rate) 5-16 FMP (Voltage adjust) 5-7 Frequency command 1 5-30 Frequency command 2 5-14 Frequency limiter (High) 5-14 Frequency limiter (Low) 5-14 Gain (for freq set signal) 5-36 Instantaneous OC limiting 5-29 JOG frequency 5-28 Jump frequency (Hysteresis) 5-28 Jump frequency (Jump freq 1) 5-28 Jump frequency (Jump freq 2) 5-28 Jump frequency (Jump freq 3) 5-27 LCD Monitor (Contrast) 5-27 LCD Monitor (Function) 5-27 LCD Monitor (Language) 5-26 LED Display filter 5-26 LED Monitor (Function)
F36 F07 E10 E12 E14 H07 H19 C33 F04 A02 F18 H03 F00 F21 F22 F20 H11 F08 E11 E13 E15 E40 E41 H28 F11 F10 F12
LCD Display 30RY MODE ACC TIME1 ACC TIME2 ACC TIME3 ACC TIME4 ACC PTN AUT RED REF FILTER BASE Hz-1 BASE Hz-2 FREQ BIAS DATA INIT DATA PRTC DC BRK LVL DC BRK t DC BRK Hz DEC MODE DEC TIME1 DEC TIME2 DEC TIME3 DEC TIME4 COEF A COEF B DROOP OL LEVEL1 ELCTRN OL1 TIME CNST1
A07 OL LEVEL2 A06 ELCTRN OL2 A08 TIME CNST2 F13
DBR OL
H10 H06 E30 E31 E32 E36 F30 F31 F35 F33 F34 F01 C30 F15 F16 F17 H12 C20 C04 C01 C02 C03 E47 E45 E46 E42 E43
ENERGY SAV FAN STOP FAR HYSTR FDT1 LEVEL FDT1 HYSTR FDT2 LEVEL FMA V-ADJ FMA FUNC FMP FUNC FMP PULSES FMP V-ADJ FREQ CMD 1 FREQ CMD 2 H LIMITER L LIMITER FREQ GAIN INST CL JOG Hz JUMP HYSTR JUMP Hz 1 JUMP Hz 2 JUMP Hz 3 CONTRAST LCD MNTR LANGUAGE DISPLAY FL LED MNTR
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
PG. NAME 5-26 LED Monitor (Display @ STOP mode) 5-10 Maximum frequency 1 5-44 Maximum frequency 2 5-10 Maximum voltage 1 5-44 Maximum voltage 2 5-42 Modbus-RTU (Address) 5-42 Modbus-RTU (Baud rate) 5-42 Modbus-RTU (Data length) 5-42 Modbus-RTU (Mode select on no response error) 5-43 Modbus-RTU (No response error detection time) 5-42 Modbus-RTU (Parity check) 5-43 Modbus-RTU (Response interval) 5-42 Modbus-RTU (Stop bits) 5-42 Modbus-RTU (Timer) 5-33 Motor 1 (%R1 setting) 5-33 Motor 1 (%X setting) 5-32 Motor 1 (Capacity) 5-33 Motor 1 (No-load current) 5-33 Motor 1 (On-line Tuning) 5-32 Motor 1 (Rated current) 5-32 Motor 1 (Tuning) 5-45 Motor 2 (%R1 setting) 5-45 Motor 2 (%X setting) 5-44 Motor 2 (Capacity) 5-45 Motor 2 (No-load current) 5-45 Motor 2 (On-line Tuning) 5-44 Motor 2 (Rated current) 5-45 Motor 2 (Slip compensation control 2) 5-45 Motor 2 (Tuning) 5-15 Motor sound (Carrier freq.) 5-15 Motor sound (Sound tone) 5-28 Multistep frequency setting (Freq. 1) 5-28 Multistep frequency setting (Freq. 2) 5-28 Multistep frequency setting (Freq. 3) 5-28 Multistep frequency setting (Freq. 4) 5-28 Multistep frequency setting (Freq. 5) 5-28 Multistep frequency setting (Freq. 6) 5-28 Multistep frequency setting (Freq. 7) 5-28 Multistep frequency setting (Freq. 8) 5-28 Multistep frequency setting (Freq. 9) 5-28 Multistep frequency setting (Freq.10) 5-28 Multistep frequency setting (Freq.11) 5-28 Multistep frequency setting (Freq.12) 5-28 Multistep frequency setting (Freq.13) 5-28 Multistep frequency setting (Freq.14) 5-28 Multistep frequency setting (Freq.15)
5-5
E44
LCD Display LED MNTR2
F03 A01 F06 A04 H31 H34 H35 H32
MAX Hz-1 MAX Hz-2 MAX V-1 MAX V-2 ADDRESS BAUD RATE LENGTH MODE ON ER
H38 NO RES t H36 PARITY H39 INTERVAL H37 H33 P07 P08 P02 P06 P05 P03 P04 A16 A17 A11 A15 A14 A12 A18
STOP BITS TIMER M1-%R1 M1-%X M1 -CAP M1-lo M1 TUN2 M1-lr M1 TUN1 M2-%R1 M2-%X M2-CAP M2-Io M2 TUN2 M2-Ir SLIP COMP2
A13 F26 F27 C05
M2 TUN1 MTR SOUND SOUND TONE MULTI Hz-1
C06 MULTI Hz-2 C07 MULTI Hz-3 C08 MULTI Hz-4 C09 MULTI Hz-5 C10 MULTI Hz-6 C11 MULTI Hz-7 C12 MULTI Hz-8 C13 MULTI Hz-9 C14 MULTI Hz-10 C15 MULTI Hz-11 C16 MULTI Hz-12 C17 MULTI Hz-13 C18 MULTI Hz-14 C19 MULTI Hz-15
Page 60
5.2 Alphabetical Function List (continued) PG. NAME 5-32 Number of motor 1 poles 5-44 Number of motor 2 poles 5-30 Offset adjust (terminal [12]) 5-30 Offset adjust (terminal [C1]) 5-25 OL function (Mode select) 5-25 OL function siganl (Timer) 5-25 OL function signal (Level) 5-25 OL2 function (Level) 5-7 Operation method 5-29 Pattern (Stage 1) 5-29 Pattern (Stage 2) 5-29 Pattern (Stage 3) 5-29 Pattern (Stage 4) 5-29 Pattern (Stage 5) 5-29 Pattern (Stage 6) 5-29 Pattern (Stage 7) 5-29 PATTERN operation (Mode select) 5-39 PID control (D-gain) 5-41 PID control (Feedback filter) 5-38 PID control (Feedback signal) 5-39 PID control (I-gain) 5-37 PID control (Mode select) 5-39 PID control (P-gain) 5-41 PTC thermistor (Level) 5-41 PTC thermistor (Mode select) 5-10 Rated voltage 1 5-44 Rated voltage 2 (at Base frequency 2) 5-12 Restart mode after momentary power failure 5-35 Rev. phase sequence lock 5-42 Serial link (Function select) 5-33 Slip compensation control 5-35 Start mode 5-15 Starting frequency (Freq.) 5-15 Starting frequency (Holding time) 5-15 Stop frequency 5-11 Torque boost 1 5-44 Torque boost 2 5-37 Torque control 5-16 Torque limiter 1 (braking) 5-16 Torque limiter 1 (Driving) 5-22 Torque limiter 2 (braking) 5-22 Torque limiter 2 (Driving) 5-177 Torque vector control 1 5-44 Torque vector control 2 5-18 X1 terminal function 5-18 X2 terminal function 5-18 X3 terminal function 5-18 X4 terminal function 5-18 X5 terminal function 5-18 X6 terminal function 5-18 X7 terminal function 5-22 Y1 terminal function 5-22 Y2 terminal function 5-22 Y3 terminal function 5-22 Y4 terminal function 5-24 Y5 RY operation mode 5-22 Y5A, Y5C terminal func.
P01 A10 C31 C32 E33 E35 E34 E37 F02 C22 C23 C24 C25 C26 C27 C28 C21
LCD Display M1 POLES M2 POLES BIAS 12 GAIN 12 OL1 WARNING OL1 TIMER OL1 LEVEL OL2 LEVEL OPR METHOD STAGE 1 STAGE 2 STAGE 3 STAGE 4 STAGE 5 STAGE 6 STAGE 7 PATTERN
H24 H25 H21 H23 H20 H22 H27 H26 F05 A03
D-GAIN FB FILTER FB SIGNAL I-GAIN PID MODE P-GAIN PTC LEVEL PTC MODE RATED V-1 RATED V-2
F14
RESTART
H08 H30 P09 H09 F23 F24
REV LOCK LINK FUNC SLIP COMP1 START MODE START Hz HOLDING t
F25 F09 A05 H18 F41 F40 E17 E16 F42 A09 E01 E02 E03 E04 E05 E06 E07 E20 E21 E22 E23 E25 E24
STOP Hz TRQ BOOST1 TRQ BOOST2 TRQ CTRL BRK TRQ 1 DRV TRQ 1 BRK TRQ 2 DRV TRQ 2 TRQVECTOR1 TRQVECTOR2 X1 FUNC X2 FUNC X3 FUNC X4 FUNC X5 FUNC X6 FUNC X7 FUNC Y1 FUNC Y2 FUNC Y3 FUNC Y4 FUNC Y5RY MODE Y5 FUNC
5-6
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA