Page 111
8. Maintenance and Inspection Proceed with daily inspection and periodic inspection to prevent malfunction and ensure long-term reliability. Some tips regarding things to look for during these inspections are listed below.
8.1 Daily Inspections During operation, a visual inspection for abnormal operation can take place externally without removing the covers. The inspection should cover the following areas: (1) The performance, according to standard specifications, is as expected. (2) The environment conforms to standard specifications. (3) The keypad panel display is normal. (4) There are no abnormal sounds, vibrations, or odors. (5) There are no indications of overheating or discoloration.
8.2 Periodic Inspections Periodic inspections should be made after stopping operations, cutting off the power source, and removing the surface cover. Note that after turning off the power, the smoothing capacitors in the DC section of the main circuit take time to discharge. To prevent electric shock, confirm with a multimeter that the voltage has dropped below the safety value (25 V DC or below) after the charge lamp (CRG) goes off.
WARNING •
• •
Start the inspection at least five minutes after turning off the power supply for inverters rated at 30 Hp or less. Wait at least ten minutes for inverters rated at 40 Hp or more. Check that the charge lamp (CRG) went off and that the voltage is 25V DC or less between terminals P(+) and N(-). Electric shock may result. Only authorized personnel should perform maintenance and component replacement operations. Remove metal jewelry such as watches and rings, and always use insulated tools. Never modify the drive. Electric shock or injury may result.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
8-1
Page 112
Items to Check
Environment
1) Check the ambient temperature, humidity, vibration, atmosphere (dust, gas, oil mist, water drops). 2) Is the area surrounding the equipment free of foreign objects.
1) Conduct a visual inspection and use appropriate meters. 2) Visual inspection
1) Results comply with all standard specifications. 2) The area is clear.
Voltage
Are the voltages in the main circuit and the control circuit normal?
Measure with a multi-meter.
Results comply with all standard specifications.
Keypad panel
1) Is the display hard to read? 2) Are the characters complete?
1) Visual inspection 2) Visual inspection
1), 2) The display can be easily read and characters are normal.
Structure (frame or cover)
1) Is there abnormal sound or vibration? 2) Are nuts or bolts loose? 3) Is there deformation or damage? 4) Is there discoloration as a result of overheating? 5) Are there stains or dust?
1) Visual and aural inspection 2) Tighten 3), 4), 5) Visual inspection
1), 2), 3), 4), 5) No abnormalities
Common
1) Are there loose or missing nuts or bolts? 2) Are there deformations, cracks, damage, or discoloration due to overheating or deterioration in the equipment and insulation? 3) Are there stains and dust?
1) Tighten. 2), 3) Visual inspection
1), 2), 3) No abnormalities Note: Discolorationof the bus bar does not indicate a problem.
Conductors and wiring
1) Is there discoloration or distortion of a conductor due to overheating? 2) Are there cracks, crazing or discoloration of the cable sheath?
1), 2) Visual inspection
1), 2) No abnormalities
Terminal block Is there damage?
Visual inspection
No abnormalities
Smoothing capacitor
1) Is there electrolyte leakage, discoloration, crazing, or swelling in the case? 2) Is the safety valve not protruding, or are valves protruding too far? 3) Measure the capacitance if necessary.
1), 2) Visual inspection 3) *Estimate life expectancy from maintenance information and from measurements using capacitance measuring equipment.
1), 2) No abnormalities 3) Capacitance is within 85% of initial value
Resistor
1) Is there any unusual odor or damage to the insulation by overheating? 2) Is there an open circuit?
1) Visual and olfactory inspection 2) Conduct a visual inspection or use a multi-meter by removing the connection on one side.
1) No abnormalities 2) Less than about ±10% of the indicated resistance value
Transformer and reactor
Is there abnormal buzzing or an unpleasant smell?
Aural, olfactory, and visual inspection
No abnormalities
Magnetic conductor and relay
1) Is there a rattling noise during operation? 2) Are the contacts rough?
1) Aural inspection. 2) Visual inpection.
1), 2) No abnormalities
Control PC board and connector
1) Are there any loose screws or connectors? 2) Is there an unusual odor or discoloration? 3) Are there cracks, damage, deformation, or excessive rust? 4) Is there electrolyte leakage or damage to the capacitor?
1) 2) 3) 4)
1), 2), 3), 4) No abnormalities
Cooling fan
1) Is there abnormal sound or vibration? 2) Are nuts or bolts loose? 3) Is there discoloration due to overheating?
1) Aural and visual inspection. Turn manually (confirm the poewr is off). 2) Tighten. 3) Visual inspection 4) *Estimate life expectancy by maintenance information
1) The fan must rotate smoothly. 2), 3) No abnormalities
Ventilation
Is there foreign matter on the heat sink or intake and exhaust ports?
Visual inspection
No abnormalities
Cooling System
Control Circuit
Main Circuit
Area to Check
See additional notes on following page.
How to inspect
8-2
Aural inspection. Visual and olfactory inspection Visual inspection *Estimate life expectancy by visual inspection and maintenace information
Evaluation Criteria
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 113
Note: If equipment is stained, wipe with a clean cloth. Use a vacuum to remove dust. *Estimate of life expectancy based on maintenance information. The maintenance information is stored in the drive keypad panel. It indicates the electrostatic capacitance of the main circuit capacitors and the life expectancy of the electrolytic capacitors on the control PC board and the cooling fans. Use this data as the basis to estimate the life expectancy of parts. 1) Determining the capacitance of the main circuit capacitors This drive is equipped with a function to automatically indicate the capacitance of the capacitors installed in the main circuit when powering up the drive after disconnecting the power according to the prescribed conditions. The initial capacitance values are set in the drive when shipped from the factory, and the decrease ratio (%) to those values can be displayed. Use this function as follows: (1) Remove any option boards from the inverter. Disconnect the DC bus connections to the main circuit [Terminals P(+) and N(-)] from the braking unit or other inverters, if connected. The power factor correcting reactor (DC reactor) does not need be disconnected. A power supply introduced to the auxiliary input [Terminals R0, T0] that provides control power should be isolated. (2) Disable all the digital inputs (FWD, REV, X1-X9) on the control terminals. Also disconnect RS485 serial communication, if used. Turn on the main power supply. Confirm that the cooling fan is rotating and that the inverter is not operating. (There is no problem if the “OH2 External thermal relay tripped” function is activated by the digital input terminal.) (3) Turn the main power off. (4) Turn on the main power again after verifying that the charge lamp is completely off. (5) Open the maintenance information on the keypad panel and confirm the capacitance values of the built-in capacitors. 2) Life expectancy of the PC control board The actual capacitance of a capacitor is not measured in this case. However, the integrated operating hours for the control power supply, multiplied by the life expectancy coefficient as defined by the temperature inside the inverter, will be displayed. Hence, the hours displayed may not agree with the actual operating hours, depending on the operational environment. Since the integrated hours are counted in unit hours, power input for less than one hour will be disregarded. 3) Life expectancy of cooling fan The integrated operating hours of the cooling fan are displayed. Since the integrated hours are counted in unit hours, power input for less than one hour will be disregarded. The displayed value should be considered a rough estimate because the actual life of a cooling fan is influenced significantly by the temperature.
Table 8..-2 Rough estimate of life expectancy using maintenance information
Parts
Recommended Level
Capacitor in main circuit
85% or less of the initial value
Electrolytic capacitor on control PC board
61,000 hours
Cooling fan
40,000 hours (5 Hp or less), 25,000 hours (Over 7.5 Hp)*
* Estimated life expectancy of a ventilation-fan at inverter ambient temperature of 40°C
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
8-3
Page 114
8.3 Main Circuit Measurements The indicated values depend on the type of meter, because the harmonic component is included in the voltage and current of the main circuit power (input) and the output (motor) side of the inverter. If measuring with a meter for commercial power frequency use, use the meters shown in Table 8.3.1. The power factor cannot be measured using power factor meters currently available on the market, which measure the phase difference between voltage and current. If power factors must be measured, measure the power, voltage, and current on the input side and output side, then calculate the power factor using the following formula:
Power factor =
Power [W] 3 x Voltage [V] x Current [A] x 100 [%]
Table 8.3-. Meters for Measuring Main Circuit
Item
Input (power supply) Side
Output (motor) Side
Voltage
Voltage
Current
Voltmeter Powermeter VR,S,T WR,S,T
DC Link Circuit Voltage P(+) - N(-)
Current
Meter name
Ammeter AR,S,T
Ammeter AU,V,W
Voltmeter VU,V,W
Powermeter WU,V,W
DC Voltmeter V
Meter type
Moving iron Rectifier or Digital Moving iron type moving-iron power meter type type
Rectifier type
Digital power meter
Moving coil type
Symbol Note: If the output voltage is measured with a rectifier type meter, an error may occur. Use a digital AC power meter to ensure accuracy.
8-4
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 115
8.4 Insulation Test Avoid megger testing on an drive since an insulation test was completed at the factory. If a megger test must be completed, proceed as described below. Incorrect testing methods may result in product damage. If the specifications for the dielectric strength test are not followed, the drive may be damaged. If a dielectric strength test must be completed, contact your local distributor or nearest Fuji Electric sales office. (1) Megger test for the main circuit 1. 2. 3. 4. 5.
Use a 500V DC megger and isolate the main power before starting measurement. If the test voltage is connected to the control circuit, remove all connection cables to the control circuit. Connect the main circuit terminals using common cables, as shown in Fig. 8-4-1. Perform the megger test only between the common cables connected to the main circuit and ground (Terminal ). A megger indicating 5M Ohm or more is normal. (This is the value measured with only the drive connected.)
(2) Insulation test in the control circuit Megger and dielectric strength tests are not performed on the control circuit. Use a resistance multimeter with a high resistance range to check the control circuit. 1. Remove all external cables from the control circuit terminals. 2. Conduct a continuity test between grounds. A result of 1M Ohm or more is normal. (3) Exterior main circuit and sequence control circuit Remove all cables from drive terminals to ensure that test voltage is not applied to the drive.
8.5 Replacement Parts The life expectancy of a part depends on the type of part, the environment, and operating conditions. Parts should be replaced as shown in Table 8-5-1. Table 8-5-1 Part replacement Part name
Standard period for replacement
Cooling fan
3 years
Exchange for a new part
Smoothing capacitor
5 years
Exchange for a new part (determine after checking
Comments
Electrlytic capacitor on the PC board
7 years
Exchange for a new PC board (determine after checking)
Fuse
10 years
Exchange for a new part, Determine after checking
Other parts
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
8-5
Page 116
Notes:
8-6
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 117
9. Warranty Parts and Service The purpose of this section is to provide specific instructions to the user of the standard drive referenced in this book regarding warranty administration and how to obtain assistance on both in-warranty and out-ofwarranty equipment.
WARRANTY COVERAGE The warranty covers all major parts of the drive such as the main printed circuit boards, transistor modules, etc. The warranty does not cover replacement of fuses or of the entire drive.
For all warranty procedures, refer to section 10 of this instruction manual to identify the part or assembly.
“Warranty period is 12 months after installation or 18 months after shipment from the Company, whichever occurs first.”
If assistance is required to determine warranty status, identify defective parts, or obtain the name of your local distributor, call:
However, the guarantee will not apply in the following cases, even if the guarantee term has not expired: 1.
GE Industrial Systems Product Service Engineering 1501 Roanoke Blvd. Salem, VA 24153-6492 USA Phone: 1 800 533 5885 (United States) + 1 540 378 3280 (International) Fax: + 1 540 387 8606 (All) (“+” indicates the international access code required when calling from outside of the USA.)
2. 3. 4.
Damage was caused by incorrect use or inappropriate repair or modification. The product was used in an environment outside the standard specified range. Damage was caused by dropping the product after purchase or occurred during transportation. Damage was caused by an earthquake, fire, flooding, lightning, abnormal voltage, or other natural calamities and secondary disasters.
Before calling the number at left to determine warranty status, the drive serial number will be required. This is located on the drive nameplate. If the drive is still under warranty, further information will be required per the “InWarranty Failure Checklist” shown on page 9-2 of this instruction manual. OUT-OF WARRANTY PROCEDURES When the defective part has been identified, contact your local authorized GE standard drives distributor to order replacement parts. MOTORS Motor repairs on General Electric motors are generally handled by GE Authorized Electric Motor Servicenters or GE Apparatus Service Shops. For specific instructions on your motor, call the distributor from which it was purchased and be prepared to furnish complete nameplate data.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
9-1
Page 118
IN-WARRANTY FAILURE CHECKLIST To assist with warranty troubleshooting, the following information is required. This data is needed to evaluate the cause in an effort to eliminate any further failures. Model No.: ______________________________________________________________________ Serial No.: ______________________________________________________________________ Start-Up Date: __________________________________________________________________ Failure Date: ____________________________________________________________________ Status When Failure Occurred (check one): Power-Up __________ Running ___________ Accel ___________ Decel _________ Explanation of Failure ____________________________________________________________ Application Information (check Yes or No) Input Transformer: If Yes:
Yes ___________ No _______________
KVA ___________________________________ L1 Volts ___________ L2 Volts ________ L3 Volts ______________
Power Factor Correction Capacitors: Yes __________ No _______________ If Yes: Microfarrad ______________________________ Other Equipment on Same Power If Yes, what?
Yes __________ No _______________
Line Reactor on Input Input Starter
Yes __________ No _______________ Yes __________ No _______________
Output Starter Motor Overloads
Yes __________ No _______________ Yes __________ No _______________
Function Codes Different From Factory Settings Function Code Setting
X9
X8 SD
X7 DX
X6 DX
X4
X5 P24
REV
Function Code
P24
X3
X2 FWD
CM
CM
X1
PLC
FMP V2
FMA 13
C1 12
Y1 11
Y3 Y2
CMY Y4
Y5A Y5C
30B
30C
30A
Control Terminals Used (circle if used)
Setting
Failure Message (see Section 4) Latest Fault _______________ Previous Faults: No Message _____________ Hz ______________________ 1. _____________________________ A _______________________ V _______________________
2. _____________________________ 3. _____________________________
After all of the Checklist information is acquired, contact the following number for assistance: (540) 387-5739 or (800) 533-5885 When returning failed parts, reference the C_ _ _ _ # on the shipping documents that came with the replacement parts and ship failed parts to: GE Fuji Drives. (Marked C _ _ _ _ #) 9-2
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 119
10. Replacement Parts Catalog No.
Rating
Drive HP & Quantity per drive 1/4 1/2 1 2 3
5
7.5
10
15
20
25
30
1
1
1
1
1
1
1
AF-300 G11 230 VAC, 30 Hp and Below Main Control Card G11CPCBB1 1 1 1 1 1 Gate Driver & Power Supply Card G11PPCBG2002 1 G11PPCBG2004 1 G11PPCBG2008 1 G11PPCBG2015 1 G11PPCBG2022 1 G11PPCBG2037 G11PPCBG2055 G11PPCBG2075 G11PPCBG2110 G11PPCBG2150 G11PPCBG2185 G11PPCBG2220 KEYPAD PANEL (Only one type per drive) TPAG11S NEMA 1 1 1 1 1 1 TPAG11S4 NEMA 4, 12 1 1 1 1 1 DC CAPACITOR * * * G11CAP01 PCB 1 G11CAP02 PCB 1 G11CAP03 PCB G11CAP09 2700µF G11CAP10 3900µF G11CAP11 4700µF G11CAP12 5400µF * Located on Gate drive & Power supply Card FAN G11FAN01 1 1 G11FAN02 POWER MODULE * * * PS11046 30A 600V 1 1 PS11047 50A 600V 6MBP75RS060 75A 600V 6MBP100RS060 100A 600V 6MBP150RS060 150A 600V 6MBP200RS060 200A 600V * Located on Gate drive & Power supply Card RECTIFIER MODULE * * * * * PVC758 75A 800V CLK120AA80 120A 800V CLK180AA80 180A 800V CHARGE RESISTOR * * * * * 30W66 30W 6.6WJ 80W25 80W 2.5WJ * Located on Gate drive & Power supply Card FRONT COVER G11UPCG008 1 1 1 G11UPCG040 1 G11UPCG075 G11UPCG220 INTERNAL DB RESISTOR G11DBR0082 100W 40W 1 1 1 G11DBR0372 40W 80W 1 1 G11DBR0752 24W 90W Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
10-1
1 1 1 1 1 1 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
2 1
2 2 2
1 1
1
2
2
1
1
2
2
1
1
1
1
1 1 1
* 1
1 1
1
* 1
1 1
1
1
1
1
1
1
1
1 1
1
1 1
1
Page 120
Catalog No.
Rating
Drive HP & Quantity per drive 40 50 60
75
100
125
1
1
1
1
1
1
AF-300 G11 230 VAC, 40 Hp and Above Main Control Card EP4113B1
1
Gate Driver & Power Supply Card EP3956C1 EP3956C2 EP3956C3 EP3957C1 EP3957C2
1 1 1 1
KEYPAD PANEL TPAG11S4 DC CAPACITOR LNT2G302MSMAFF HCGHA2G362N3K HCGHA2G452NE3K HCGHA2G592N3K
1
1 400V 3000µF 400V 3600µF 400V 4500µF 400V 5900µf
1
1
1
1
1
4
5
6
2
2
4
3
4
3
4
4 4 4
FAN FBA09A24H1B0 (Standard) 4715PS22TB30 2750MTP15 6250MG1 (For NEMA12 Heatsink) UHS4556MLOT1 2750MTP15OT1 U6250MKG1LTPOT1
1
1
2
2
2
2 2 2 2
2 2
IGBT MODULE 2MBi300NB060 CM400DU12H206 2MBi300NB06001 PD1008AC
3 3
RECTIFIER MODULE PD1008AC
3
6
6 6
6 9
9 9
12 9
3
6
6
9
9
9
1
1
1
2
2
2
2
2
CHARGE RESISTOR HF5C5504
80W 7.5ohm
1
DC CONTACTOR FC3UL FC1UL FC4UL SC7NUL
AC220VAUX2B AC220VAUX2B AC220VAUX2B AC200-240V
1 2 1
DC FUSE CR2L260UL CR2L400UL A50P6004
1
1 1
INPUT MODULE CARD EP3985C1 EP3985C3
1
10-2
1
1
1 1
1
1
1
1
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA