The text of a manual · part 4 of 16

AF-300 G11 User's Guide, pages 31 to 40

Pages 31 to 40 of 160

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the GE AF-300G11, Fanuc AF-300G11 and GE Fanuc AF-300G11

Page 31

Transistor

Y1

Transistor output 1

A running signal, frequency equivalence signal, overload early warning output signal, and other signals from the drive are output (as transistor output) to arbitrary ports. For details, see "Setting the Terminal Functions E20 to E23" in Section 5.2 Function Explanation. * <Specifications of transistor output circuit>

Item Operating voltage Y2 Y3 Y4

Transistor output 2 Transistor output 3 Transistor output 4

CME

Transistor output common

Relay output 30A,30B,30C

Alarm outputs for any fault.

Maximum load current Leakage current

ON OFF ON OFF min. – – – – typ. 1V 24V – – max. 2V 27V 50 mA 0.1 mA

Common terminal for transistor output signals. This terminal is insulated from terminals (CM) and [11]. If the drive is stopped by an alarm (protective function), the alarm signal is output from the relay contact output terminal (1SPDT). Contact rating: 250 VAC, 0.3A,cosØ = 0.3, 48 VDC, 0.5A for CE Marking An excitation mode (excitation at alarm occurrence or at normal operation) can be selected.

Y5A,Y5C

Multi-purpose signal

These signals can be output similar to the Y1 to Y4 signals above. The contact rating is the same as that of the alarm output above.

Communication

DX+,DX–

RTU communication

Input / output signal terminals for RTU communication input / output Up to 31 inverters can be connected using the daisy chain method.

SD

Communication cable shield connection terminal

Terminal for connecting the cable shield. The terminal is electrically floating.-

(1) Analog input terminals (13, 12, C1, and 11) 1. These terminals receive low level analog signals that may be affected by external noise. The cables must be as short as possible (20 meters or less), must be shielded, and the shields must be grounded. If the cables are affected by external induction noise, the shielding effect may be improved by connecting the shield to terminal [11]. 2.

If contacts must be connected to these circuits, twin (bifurcated) contacts for handling low level signals must be used. A contact must not be connected to terminal [11].

3.

If an external analog signal output device is connected to these terminals, it may malfunction as a result of drive noise. To prevent malfunction, connect a ferrite core or capacitor to the external analog signal output device.

Drive Shielded wires

13 12 11

VR 1k to 5K ohms Fig. 2-3-9

Fig. 2-3-10 Example of Noise Prevention

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

2-13

Page 32

(2) Digital input terminals (FWD, REV, X1 to X9, PLC, and CM) 1. Digital input terminals (e.g., FWD, REV, X1 to X9) are generally turned on or off by connecting or disconnecting the line to or from the CM terminal. If digital input terminals are turned on or off by switching the PLC’s open collector output using an external power supply, a resulting bypass circuit may cause the drive to malfunction. To prevent a malfunction, connect the PLC terminal as shown in Fig. 2-311.

(6) Wiring of control circuit (inverter of 40 Hp or more) 1. 2.

3.

Pull out the control circuit wiring along the left panel as shown in Fig. 2-3-12. Secure the cable to cable binding hole A (on the left wall of the main circuit terminal block) using a cabletie (e.g., Insulock). The cable-tie must not exceed 0.14" (3.5mm) in width and 0.06" (1.5mm) in thickness. When the optional PC board is mounted, the signal lines must be secured to cable binding hole B.

Fig. 2-3-11 Prevention of Bypass Current by External Power

2.

When using a contact input, a high-quality relay with reliable contacts must be used. (3) Transistor output terminals (Y1 to Y4, CME) 1. These terminals have a circuit configuration as shown in Table 2-3-3, "Transistor Output". Confirm the polarity of the external power supply. 2. To connect a control relay, connect a surge absorbing diode to both ends of its exciting coil. (4) Sink or Source Logic Selection. 1. Set SWI for Sink or Source Connection to the PLC. The factory default setting is Sink and this instruction manual explains Sink logic function only. 2. When you need to connect source type logic, refer to Basic Connection Diagram Fig. 2-3-3 and Fig. 2-3-4 and Technical Information Manual. (Sink Logic is commonly used in the USA and Source Logic is commonly used in Europe.) (5) Others 1. To prevent a malfunction as a result of noise, control terminal cables must be placed as far as possible from the main circuit cables. 2. The control cables inside the inverter must be secured to prevent direct contact with the main circuit (e.g., main circuit terminal block).

Fig. 2-3-12 The Control Wiring Route

Cable ties

Cable binding Hole B wiring

Cable binding Hole A

Fig. 2-3-13 Securing Positions for Inverter Control Circuit Wiring (40 HP or more)

WARNING Control lines generally do not have enhanced insulation. If the insulation of a control line is damaged, the control signals may be exposed to high voltage in the main circuit. The Low Voltage Directive in Europe also restricts the exposure to high voltage. Electric shock may result

CAUTION The inverter, motor, and cables generate noise. Check that the ambient sensors and devices do not malfunction. Accident may result. 2-14

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 33

2.3.4 Terminal Configuration (1) Main circuit terminals

50 To 75 Hp 230 VAC 100 to 150 Hp 460 VAC

1/4 to 1 Hp 230 VAC 1/2 to 1 Hp 460 VAC L1/R L2/S L3/T DB

G G

P1 P(+) N(–)

V

U

R0 T0

W

L1/R L2/S L3/T DB

L1/R L2/S L3/T DB

R0

T0

N(–)

P1 P(+) N(–)

U

V

W

L1/R L2/S L3/T P1 P(+) N(-) U V

G G

G

R0

Screw size M4

125 Hp 230 VAC 200 to 350 Hp 460 VAC

T0

Screw size M3.5 P1 P(+) N(–)

U

W

Screw size G = M10 Other terminals = M12

Screw size M4

R0 T0 V

G

W

L1/R

L2/S

U

L3/T P1

G

V P(+)

W N(-)

G G Screw size G = M10

Screw size M5

Other terminals = M12 400, 450 Hp 460 VAC

15 to 30 Hp 230 VAC 15 to 30 Hp 460 VAC

R0

T0

R0 T0

Screw size M3.5 P1 P(+) N(–)

U

V

W

Screw size M4

V W L1/R L2/S L3/T P1 U V W L1/R L2/S L3/T P1 U

G

G G

P(+)

Screw size G = M8 Other terminals = M10

R0 T0

Screw size M3.5

7.5 to 10 Hp 230 VAC 7.5 to 10 Hp 460 VAC

L1/R L2/S L3/T DB

W

100 Hp 230 VAC

Screw size M4

L1/R L2/S L3/T DB

V

P1

G G

Screw size M3.5

2 to 5 Hp 230 VAC 2 to 5 Hp 460 VAC

G

U

G

Screw size M6

P(+)

P(+)

N(-)

N(-)

Screw size G = M10 Other terminals = M12 500, 600 Hp 460 VAC

40 Hp 230 VAC 40 to 75 Hp 460 VAC Screw size M4

R0 T0 U

R0 T0 L1/R L2/S L3/T DB

G G

P1

V

L1/R L2/S L3/T P1 P(+) N(-) U V W L1/R L2/S L3/T P1 P(+) N(-) U V W

W

P(+)

G

N(–)

Screw size M8

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

G

Screw size RO,TO = M4 G = M10 Other terminals = M12 2-15

Page 34

(2) Control circuit terminals 30A Y5A CMY

30C 30B Y5C

Y3

Y4

Y1

Y2

C1

11

FMA FMP PLC

12

13

V2

X1

CM

X2

X3

X4

X5

X6

X7

X8

CM FWD REV P24 P24 DX- DX+

X9

SD

2.3.5 AF-300 G11 Drive Cable Size, Tightening Torque and Circuit Protection Rating Incoming Device

Tightening Torque lb-Inch (Nm)

Cable size AWG

Input Fuse

HP

L1/R, L2/S, L1/R, L2/S, L3/T L3/T (Nominal) (Maximum) (*1)

Auxiliary Input R0, T0

Input L1/R, L2/S, Circuit L3/T, UVW, Breaker P1, P(+), DB, (*1) N(-)

230VAC Input 0.25 3 0.5 5 1 10 2 15 3 20 5 35 7.5 60 10 70 15 100 20 125 25 150 30 175 40 200 50 225 60 300 75 350 100 300 125 400

3 6 15 20 30 50 80 125 150 200 225 250 -

3 3 3 3 3 3 3 3 3 3 3 3 5 5 5 5 5 5

15 15 20 30 40 60 100 125 175 225 250 300 200 225 300 350 300 400

460VAC Input 0.5 3 1 5 2 10 3 15 5 20 7.5 30 10 40 15 50 20 70 25 80 30 100 40 100 50 125 60 175 75 150 100 175 125 200 150 225 200 300 250 400 300 450 350 500 400 600 450 700 500 700 600 1000

3 6 10 15 25 45 60 90 110 125 125 -

3 3 3 3 3 3 3 3 3 3 3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

15 15 15 20 35 50 70 90 110 150 175 100 125 175 150 175 200 225 300 400 450 500 600 700 700 1000

E(G)

10.6 (1.2)

20.8 (2.36)

R0, T0

Control

10.6 (1.2)

6.2 (0.7)

L1/R, L2/S, L3/T

51.3 (5.8)

119(13.5) 239(27) 119(13.5)

4/0 Qty2 - 1 Qty2 - 2/0 Qty2 - 3/0 Qty 2 - 2/0 Qty2 - 4/0

239(27)

10.6 (1.2)

10.6 (1.2)

20.8 (2.36)

P1, P(+), N(-), DB

14 10 8 6 4 3 2 1 1/0 3/0 4/0 Qty2 - 1/0 Qty2 - 3/0 Qty2 - 4/0

R0, T0

14

16

31.0 (3.5)

425(48)

U, V, W

2/0 4/0 Qty2 - 1 Qty2 - 2/0 Qty2 - 4/0 Qty2 - 250

6.2 (0.7)

22

10

14

16

Control

22

14 12 10

31.0 (3.5) 51.3 (5.8)

119(13.5)

239(27)

119(13.5) 239(27)

425(48)

2 1 2/0 3/0 2/0 3/0 Qty2 - 1/0 Qty2 - 1/0 Qty2 - 3/0 Qty2 - 4/0 Qty2 - 250 Qty2 - 350 Qty2 - 500 Qty2 - 600 Qty2 - 700

8 6 4 3 2 2 1/0 3/0 4/0 Qty2 - 1/0 Qty2 - 2/0 Qty2 - 3/0 Qty2 - 250 Qty2 - 300 Qty2 - 400 Qty2 - 500 Qty2 - 600 Qty2 - 750

3 2 1 2/0 4/0 Qty2 - 1 Qty2 - 1/0 Qty2 - 3/0 Qty2 - 4/0 Qty2 - 300 Qty2 - 350 Qty2 - 500 Qty2 - 700 Qty2 - 800 Qty2 - 1000

10

(*1)Class J Fuse or Circuit Breaker reted 600V with the maximum current rating as shown in the above table shall be connected to the drive for 30HP and less. Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user. Wire size from NEC tables 310-16. Copper wire rated 60 Deg. C for 100amps or less, 75 Deg. C for over 100 amps in 30 Deg. C ambient and 1.25 times Drive rated amps. These are minimum wire sizes : consult and confirm to local and national codes.

2-16

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 35

2.3.6 DC Link Reactor Dimensions in inches

Height

Terminal

Depth

Width

Hp 230V G11 100 125 460V G11 100 125 150 200 250 300 350 400 450 500 600

Model No.

Width

Depth

Height

Weight

Loss [W]

DCR2-75B DCR2-90B

7.87 7.09

10.63 11.02

7.09 8.46

37 37

55 57

DCR4-75B DCR4-90B DCR4-110B DCR4-132B DCR4-160B DCR4-200B DCR4-220B DCR4-280B DCR4-315B DCR4-355B DCR4-400B

7.48 7.48 7.48 7.87 8.27 8.27 8.66 8.66 9.84 9.84 9.84

10.63 11.02 11.02 11.02 12.6 12.99 13.78 14.57 12.01 12.99 13.78

6.89 7.87 7.87 8.07 8.07 9.06 9.06 9.65 8.78 8.78 9.17

35 44 46 55 68 75 81 95 88 99 106

58 64 73 84 90 126 131 133 150 205 215

Note: • AF-300 G11 Drives rated 100 Hp and above are furnished with a DC link reactor. This reactor must be installed between terminal P1 and P+ prior to commissioning of the Drive. • The weight of the DC Link Reactor is not included with that of the Drive. • DC Link Reactor is provided as open type and is separately mounted. Enclosure to be provided by others.

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

2-17

Page 36

Notes

2-18

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 37

3. Operation Drive

3.1 Inspection and Preparation Before Operation Check the following before operation: 1. Check that the connections are correct. In particular, check that the power supply is not connected to any of the U, V, or W output terminals and that the ground terminal is securely grounded. 2. Check for short circuits and ground faults between the terminals and sections under power. 3. Check for loose terminals, connectors, or screws. 4. Check that the motor is disconnected from the mechanical equipment. 5. Turn off switches before turning on power to ensure that the drive will not start or operate abnormally at power-on. 6. Check the following after power-on: a. No alarm message is displayed on the keypad panel (see Figure 3-1-2). b. The fan inside the drive is rotating. (For drives with 2Hp or more.)

L1/R, L2/S, L3/T, U,

V, motor power

Fig. 3-1-1 Drive connection

WARNING Be sure to have the drive cover in place before turning on the power (closed). Never remove the cover while power is applied to the drive. To ensure safety, do not operate switches with wet hands. Electric shock may result.

3.2 Operation Method

Fig. 3-1-2 Display on keypad panel at power-on

There are various methods of operation. Select a method of operation according to the operating requirements and specifications; refer to Section 4-2 Operating the Keypad Panel, and Chapter 5 Function Selection. Table 3-2-1 lists general methods of operation.

3.3 Trial Run

Operation

Frequency Setting

Command Operation

Operation Command

Keys on keypad panel using keypad

FWD

REV

STOP panel

Once inspection is completed (see Section 3-1), proceed with a trial run. The motor is initially disconnected and the drive is operated (factory setting) using the keypad panel. 1.

Turn power on and confirm that the LED monitor display 0.00 Hz is blinking.

2.

Set the frequency to about 5 Hz using

3.

To start the run, press

FWD

REV key (for reverse rotation). To stop, press STOP key. Verify frequency increases for zero to the set point. Connect motor and repeat steps 1-3 4. Check the following items: a. Is the direction of rotation correct? b. Is the rotation smooth (no buzzing or abnormal vibration)? c. Are acceleration and deceleration smooth? 5. If no abnormality is detected, increase the frequency and check the above items again. If the results of the trial run are normal, start a formal run.

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Input from Terminals terminal

FWD-CM and signals

REV-CM Frequency Setting POT(VR), analog voltage, analog current key.

key (for forward rotation) or

Operation using external

3-1

Notes: If an error is detected in the drive or motor’s operation, immediately stop and attempt to determine the cause of error by referring to Chapter 7 Troubleshooting. Since voltage is still present at the main circuit terminals (L1/R, L2/S, L3/T) and auxiliary control power terminals (R0, T0), even when the output from the drive is terminated, do not touch the terminals. The smoothing capacitor in the drive is charged after the power is turned off and it is not discharged immediately. Before touching an electric circuit, confirm that the charge lamp is off or use a multimeter to check that the volatge has decreased below 25 VDC for low voltage at the DC (P-N) terminals.

Page 38

Notes

3-2

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 39

4. Keypad Panel The keypad panel has various functions for specifying operations such as frequency setting, run/stop command, confirming and changing function data, confirming status, and copying function code settings. Review the use of each function before attempting to operate the drive from the keypad panel. The keypad panel can also be removed or inserted during inverter operation. However, if the keypad panel is removed during keypad panel operation (e.g., run/stop, frequency setting), the drive stops and outputs an alarm.

4.1 Appearance of Keypad Panel LED monitor 4-digit display. Used to display data such as setting frequency, output frequency and alarm code. Auxiliary Information Related to LED Monitor Indicates selected units or multiple of the data shown on the LED monitor and is displayed on the top line of the LCD monitor. The ■ symbol indicates selected units or multiple number. The symbol indicates that there is an upper screen not currently displayed. LCD Monitor: Used to display various items of information such as operation status and function data. An operating guide message, is scrolled and displayed at the bottom of the LCD monitor. This LCD monitor has a backlight feature which turns on when the control power is applied or any keypad key is pressed, and stays on approximately 5 minutes after the last key stroke. Status Indicators on LCD Monitor: Displays current operating status: FWD: Forward operation REV: Reverse operation STOP: Stop Control keys (valid during keypad panel operation): Used for drive run and stop FWD

Forward operation command

REV

Reverse operation

STOP

Stop command

Operation keys:

Displays the selected operating mode: REM: terminal block LOC: keypad panel COMM: communication terminal JOG: jogging mode The symbol indicates that there is a lower screen not currently displayed.

RUN LED (valid during operation from keypad panel): Indicates that an operation command was input by pressing the FWD or REV key.

Used for switching screens, data change,frequency setting, etc. Operation Keys

Primary Function

PRG

Used to switch the current screen to the menu screen or switch to the initial screen in operation / trip mode.

FUNC DATA

Used to switch the LED monitor or to determine the entered frequency, function code, or data Used to change data, move the cursor up or down, or scroll the screen

SHIFT

Used to move the cursor horizontally at data change. When this key is pressed with the up or down key, the cursor moves to the next function block.

RESET

Used to cancel current input data and switch the displayed screen. If an alarm occurs, this key is used to reset the trip status (valid only when the initial alarm mode screen is displayed)

STOP

+

Used to switch normal operation mode to jogging operation mode or vice versa. The selected mode is displayed on the LCD monitor.

STOP

+ RESET

Switches operation mode (from keypad panel operation mode to terminal block operation mode or reverse). When these keys are operated, function F01 data is also switched from 0 to 3 or from 1-4 to 0. The selected mode is displayed on the LCD indicator.

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

4-1

Page 40

4.2 Operation From the Keypad Panel (LCD Screen, Level Structure) 4.2.1 Normal Operation The keypad panel operating system (screen transition, level structure) is structured as follows:

60.00 Operation Mode

PRG

60.00

FUNC DATA

FUNC DATA

60.00

60.00 Supplementary Screen

Program Menu

RESET

Screen for each Function

RESET

FUNC RESET DATA

PRG 4.2.2 Alarm Modes If an alarm is activated, operation is changed from normal keypad panel operation to an alarm mode operation. The alarm mode screen appears and alarm information is displayed. The program menu, function screens, and supplementary screens remain unchanged as during normal operation, though the switching method from program menu to alarm mode is limited to PRG.

60.00 Operation Mode

Keypad panel operating system during normal operation

Alarm is activated

Alarm mode processing (including RESET ) Alarm Alarm mode

PRG

Alarm Program Menu

FUNC DATA

FUNC D ATA

Alarm

DAT Screen for each Function

RESET

Alarm Supplementary Screen

FUNC RESET D ATA

PRG

4-2

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA