Page 21

2.3 Connection Remove the main cover before connecting the terminal blocks as follows. 2-3-1 Basic Connection 1. 2. 3. 4.

5.

Always connect power to the L1/R, L2/S, and L3/T main circuit power terminals on the drive. Connecting power to another terminal will damage the drive. Check that the power voltage is within the maximum allowable voltage marked on the nameplate, etc. Always wire the ground terminal to ground to prevent problems such as fire or electric shock and to minimize noise. Use a reliable crimp terminal for connection between a power terminal and a power wire. After terminating the wiring connection, confirm the following: a. Confirm that the connection is correct. b. Confirm that all necessary connections have been made. c. Confirm that there is no short-circuit or ground fault between the terminals and wire. Connection modification after power-on The smoothing capacitor in the direct current portion of the main circuit cannot be discharged immediately after the power is turned off. To insure safety, use a multimeter to check that the direct current (DC) voltage is lowered to the safety range (25V DC or less) after the charge lamp goes off. Also, confirm that the voltage is zero before shortcircuiting. The residual voltage (electric charge) may cause sparks.

WARNING Always connect a ground wire. Electric shock or fire may result. Ensure that a trained specialist performs all wiring. Confirm that the power is turned off (open) before beginning any wiring operations. Electrical shock may result.

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

2-3

Page 22

2.3.1 Basic Connection Diagram (Sink Logic)

Note: The control circuit common terminals [11], (CM) and <CMY> are isolated (*1) Use a drive with rated voltage matching the power supply voltage. (*2) Use as required. (*3) Use this peripheral device when necessary. (*4) Remove the jumper wire (*4) between P1 and P(+) before connecting a DC REACTOR. (*5) Be sure to use the braking unit (option)(*6) when connecting the external braking resistor (option)(*5) (*6) Connect the braking unit to P(+) ans N(-). The auxiliary terminals [1] and [2] have polarity. Connect them as shown in the figure above. (*7) The drive can be operated without connecting the auxiliary control power supply. (*8) Terminal (X1) to (X9) can be set to 9 (THR) - Braking unit thermal trip input. (*9) If usingV2 or C1, as a reference signal, they must be used exclusively. (*10) It is possible to input voltage signals (0 to +10 VDC or 0 to +5 VDC) to terminals [12] [11] instead of the potentiometer

2-4

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 23

Basic Connection Diagram to PLC (Sink Logic)

See page 2-4 for notes

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

2-5

Page 24

Basic Connection Diagram (Source Logic, Typically used in Europe)

Note: The control circuit common terminals [11], (CM) and <CMY> are isolated (*1) Use a drive with rated voltage matching the power supply voltage. (*2) Use as required. (*3) Use this peripheral device when necessary. (*4) Remove the jumper wire (*4) between P1 and P(+) before connecting a DC REACTOR. (*5) Be sure to use the braking unit (option)(*6) when connecting the external braking resistor (option)(*5) (*6) Connect the braking unit to P(+) ans N(-). The auxiliary terminals [1] and [2] have polarity. Connect them as shown in the figure above. (*7) The drive can be operated without connecting the auxiliary control power supply. (*8) Terminal (X1) to (X9) can be set to 9 (THR) - Braking unit thermal trip input. (*9) If usingV2 or C1, as a reference signal, they must be used exclusively. (*10) It is possible to input voltage signals (0 to +10 VDC or 0 to +5 VDC) to terminals [12] [11] instead of the potentiometer

2-6

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 25

Basic Connection Diagram to PLC (Source logic, Typically used in Europe)

See page 2-4 for notes

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

2-7

Page 26

2.3.2 Connecting the Main Circuit and Ground Terminals Table 2.3.1 Functions of main circuit terminals and ground termnals

Symbol L1/R,L2/S,L3/T U,V,W R0,T0

Terminal Name Main circuit power terminals Inverter output terminals Input terminals for auxiliary control power

Description Connects a 3-phase power supply Connects a 3-phase motor Connects a backup AC power supply to the circuit (not supported for drives of 1 Hp or less)control

P1,P(+) P(+),DB

DC reactor terminals Terminals for external braking resistor

P(+),N(-)

Terminals for DC link circuit

G

Ground terminal

Connects the optional power correcting DC reactor Connects the optional external braking resistor (for drives of 10 Hp or less) Supplies DC link circuit voltage to the external braking unit (option) or power regeneration unit (option). Connects the drive chassis (case) to ground.

(1) Main circuit power terminals (L1/R, L2/S, L3/T) 1. 2. 3. 4.

Connect these terminals to the power supply via a molded-case circuit breaker or ground-leakage circuit breaker for circuit protection. Phase-sequence matching is unnecessary. To insure safety, a magnetic contactor should be used to disconnect the drive from the power supply when the drive protective function activates. Use control circuit terminal FWD/REV or the RUN/STOP key on the keypad panel to start or stop the drive. The main circuit power should be used to start or stop the drive only if absolutely necessary and then should not be used more than once every hour. If you need to connect these terminals to a single-phase power supply, please contact the factory.

(2) Drive output terminals (U, V, W) 1. 2. 3.

Connect these terminals to a 3-phase motor in the correct phase sequence. If the direction of motor rotation is incorrect, exchange any two of the U, V, and W phases. Do not connect a power factor correction capacitor or surge absorber to the drive output. If the cable from the drive to the motor is very long, a high-frequency current may be generated by stray capacitance between the cables and result in an overcurrent trip of the drive, an increase in leakage current, or a reduction in current indication precision.

When a motor is driven by a PWM-type drive, the motor terminals may be subject to surge voltage generated by drive element switching. If the motor cable (with 460V series motors, in particular) is particularly long, surge voltage will deteriorate motor insulation. To prevent this, use the following guidelines:

Drives 7.5 HP and larger Motor Insulation Level 460 VAC Input Voltage 230 VAC Input Voltage

1000V 66 ft (20 m) 1312 ft (400 m) *

1300V 328 ft (100 m) 1312 ft (400 m) *

1600V 1312 ft (400 m) * 1312 ft (400 m) *

Drives 5 HP and smaller Motor Insulation Level 1000V 1300V 1600V 460 VAC Input Voltage 66 ft (20 m) 165 ft (50 m) * 165 ft (50 m) * 230 VAC Input Voltage 328 ft (100 m) * 328 ft (100 m) * 328 ft (100 m) * * For this case the cable length is determined by secondary effects and not voltage spiking. Note: When a motor protective thermal O/L relay is inserted between the drive and the motor, the thermal O/L relay may malfunction (particularly in the 460V series), even when the cable length is 165 feet (50m) or less. To correct, insert a filter or reduce the carrier frequency. (Use function code “F26 Motor sound”.) 2-8

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 27

(3) Input terminals for auxiliary control power (R0 and T0) The drive operates even if power is not provided to these terminals. If a protective circuit operates, and the magnetic contactor on the drive’s power is opened (off), the inverter control circuit power, the alarm output (30A, B, and C), and the keypad panel display goes off. To prevent this, the main circuit AC power must also be supplied as auxiliary control power to the auxiliary control power input terminals (R0 and T0). 1. To ensure effective noise reduction when using a radio noise filter, the output power from the filter must go to the auxiliary control power input terminals. If these terminals are connected to the input side of the filter, the noise reduction effect deteriorates.

Fig. 2-3-2 Connection the auxiliary control-power input terminals not exceed 16.5 feet (5m).

(4) DC reactor terminals (P1 and P(+))

(6) Terminals for DC link circuit (P(+) and N(-))

1.

The G11 drive of 15 Hp or more, does not contain a drive circuit for the braking resistor. To improve braking performance, an external braking unit (option) and an external braking resistor (option) must be installed.

Before connecting a power factor correcting DC reactor (optional) to these terminals, remove the factory-installed jumper. 2. If a DC reactor is not used, do not remove the jumper. Note: For drives of 100 Hp or more, the DC reactor is provided as a separate standard component and should always be connected to the terminals. DC reactor is provided as open type, enclosure to be provided by other.

CAUTION A DC reactor does not come with drives rated less then 100 Hp, however, use a DC reactor or AC reactor under the following conditions otherwise the drive may be damaged or malfunction. 1) 2. 3. 4.

Used when the capacity of the power supply transformer exceeds 500k VA and exceeds the rated capacity of the drive tenfold. Used when a thyrister converter is connected as a common load on the same transformer. Used to prevent a drive OV trip from occuring when the power factor capacitor in the power line is switched on and off. Used when the voltage imbalance exceds 3%.

(Max. voltage [V] - Min. voltage [V] Imbalance rate between phase [%] = 3-phase average voltage [V]

1.

Connect terminals P(+) and N(-) on the braking unit to terminals P(+) and N(-) on the drive. The wiring length (twisted pair cables, etc.) should not exceed 16.5 feet (5m). 2. Connect terminals P(+) and DB on the braking resistor to terminals P(+) and DB on the braking unit. The wiring length (twisted pair cables, etc.) should not exceed 33 feet (10m). If terminals P(+) and N(-) on the drive are not used, leave the terminals open. If P(+) is connected to N(-), or the braking resistor is connected directly, the resistor will burn up. 3. Auxiliary contacts 1 and 2 of the braking unit have polarity. 4. Refer to DB unit instruction book for paralleled resistors. Note: Braking units and resistors are rated on degree of braking, duration and system frequency of braking cycle. Verify units meet application requirements.

x 100%

(5) Terminals for external braking resistor (P(+) and DB) (10 Hp or less)

Fig. 2-3-3

For the G11 of 10 Hp or less, a built-in braking resistor is connected to terminals P(+) and DB. If this braking resistor does not provide sufficient thermal capacity (e.g., in highly repetitive operation or heavy inertia load operation), an external braking resistor (option) must be mounted to improve braking performance. 1. 2. 3.

Remove the built-in braking resistor from terminals P(+) and DB. Insulate the resistor-removed terminals with adhesive insulation tape, etc. Connect terminals P(+) and DB on the external braking resistor to terminals P(+) and DB on the drive. The wiring length (twisted pair cables, etc.) should

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Fig. 2-3-4 Connection (10 Hp or less

2-9

Page 28

<Enlarged view of part A>

When shipped from the factory, CN UX is connected to the U1 side.

+ U1

U2

RO-TO L1/R-L3T

Fig. 2-3-5 Connection 15 Hp or more, 100 Hp or more parallel resistors, 200 Hp or more parallel braking units.

(7) Ground terminal The grounding connector should be sized in accordance with the NEC or Canadian Electrical Code. The connection should be made by a UL listed or CSA certified closed-loop termianl connector sized for the wire gauge involved. The connector is to be fixed using the crimp tool specified by the connector manufacturer.

<3D view of part A> Factory Shipment Status Connector CN UX: U1

(8) Auxiliary power switching connector (CN UX) (for drives of 40 Hp or more) When a drive of 40 Hp or more requires main circuit power voltage as listed in Table 2-3-3, disconnect the auxiliary power switching connector CN UX from U1 and connect to U2. For the switching method, see Fig. 2-3-7. Table 2-3-3 Main Voltage Requiring Auxiliary Power Switching Connector

Frequency [Hz]

Power Voltage Range [VAC]

50

380 - 398

60

380 - 430

CAUTION • • •

Check that the number of phases and rated voltage match those of the AC power supply. Do not connect the AC power supply to the output terminals (U, V, W). Injury may result. Do not directly connect a braking resistor to the DC terminals (P[+] and N[-]). Fire may result.

The switching connectors are mounted on the power PCB above the control PCB as shown on the right. Note: To remove a connector, unlock the connector (using the locking mechanism) and pull. To install, firmly push the connector until it click locks.

CN UX (red)

CN UX

2-10

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Page 29

2.3.3 Connecting the Control Terminals Table 2.3.3 lists the functions of the control circuit terminals. A control circuit terminal should be connected according to its function setting. Table 2-3-3

Classification

Terminal Symbol

Terminal Name

Function

Analog input

13

Potentiometer power supply

Used for +10V DC power supply for frequency setting POT (resistance of 1 to 5k Ohms)

12

Voltage input

1. Frequency is set according to the analog input voltage supplied from an external circuit. - 0 to +10V DC / 0 to 100% - Reversible operation using positive and negative signals: 0 to +/- 10V DC / 0 to 100% - Reverse operation: +10 to 0V DC / 0 to 100% 2. Input feedback signal for PID control is input. 3. The analog input value from the external circuit is used for torque control * Input resistance: 22 k Ohms

V2

Voltage input supplied from an external circuit.

¨ Frequency is set according to the analog input voltage - 0 to +10V DC/0 to 100% - Reverse operation: +10 to 0V DC/0 to 100% * It can be used only one terminal “V2” or “C1” alternatively. * Input resistance: 22 k Ohms

C1

Current input

1. Frequency is set according to the analog input current supplied from an external circuit. - 4 to 20mA DC / 0 to 100% - Reverse operation: 20 to 4mA DC / 0 to 100% 2. The feedback signal for PID control is input. 3. PTC thermistor input

* Use only one terminal - V2 or C1 Exclusively * Input resistance: 250 Ohms * PTC switch is off when PTC function is not used 11

Analog input common

Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA

Common terminal for analog input signals

2-11

Page 30

Digital input

FWD

Forward operation / Stop command

Used for forward operation (when FWD-CM is on) or deceleration and stop (when FWD-CM is opened)

REV

Reverse operation / Stop command

Used for reverse operation (when REV-CM is on) or deceleration and stop (when REV-CM is opened)

X1

Digital input 1

The coast-to-stop command, external alarm, alarm reset, multistep frequency selection, and other functions (from an external circuit) can be assigned to terminals X1 to X9. For details, see "Setting the Terminal Functions E01 to E09" in Section 5.2 Function Explanation. <Specifications of digital input circuit> Item Operating voltage

Analog output min. 0V 22V – – typ. – 24V 3.2mA – max. 2V 27V 4.5 mA 0.5 mA

X2 X3 X4 X5 X6 X7 X8 X9

Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital input 6 Digital input 7 Digital input 8 Digital input 9

P24

Control Unit power Supply

+24VDC power supply for control input. Maximum output current 100mA

PLC

PLC signal power

Used to connect power supply for PLC output signals; rated voltage = 24 VDC (22 to 27) at sink logic operation.

CM

Digital input common

Common terminal for digital input signals and P24

FMA

Analog monitor

Outputs monitor signal using analog DC voltage 0 to +10V DC. The signal indicates one of the following: - Output frequency (before slip compensation) - Load factor - Output frequency (after slip compensation) - Power consumption - Output current - PID feedback value - Output voltage - PG feedback value - Output torque - DC link circuit voltage * Connectable impedance: min. 5k ohms

Frequency monitor (pulse waveform output)

Outputs a monitor signal using the pulse waveform. This signal has the same function as the FMA signal.

Maximum load current Leakage current

(11: common terminal)

Pulse output

ON OFF ON OFF

FMP (CM: common terminal)

2-12