Page 11
AF-300 G11™ Model Numbering System Diagram Description 6K G11 N
N (X/N)NN
X
N
X
N
GE Product Code
AF-300 Drive Family
Input Voltage 2 = 230V 50/60 Hz 4 = 460V 50/60 Hz Input Phases 3 = 3 Phase Horsepower F50 = 1/2 Hp 010 = 10 Hp 100 = 100 Hp Factory Installed Options N = None X = Keypad B = to be determined Enclosure Type 1 = NEMA 1 (UL Type 1) 2 = NEMA 12 (UL Type 12) 4 = NEMA 4 (UL Type 4) 8 = IP00 with NEMA 12 heatsink 9 = IP00 Product Revision A = 1st Revision B = 2nd Revision Minor Product Revision 1 = 1st Minor Revision 2 = 2nd Minor Revision
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA vii
Page 12
AF-300 G11 Dimensions & Weights HP Rating
NEMA Enclosure
Rated Output Overload Current (A) (150% 1min.)
AF-300G11 Model No.
Catalog Dimensions No. H x W x D (inches)
Weight (lbs)
230VAC, 3 phase, 50/60Hz Input, NEMA 1 0.25 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.5 3 5 8 11 17 25 33 46 59 74 87 115 145 180 215 283 346
2.3 4.5 7.5 12 17 26 38 50 69 89 111 131 173 218 270 323 425 519
6KG1123F25X1## 6KG1123F50X1## 6KG1123001X1## 6KG1123002X1## 6KG1123003X1## 6KG1123005X1## 6KG1123007X1## 6KG1123010X1## 6KG1123015X1## 6KG1123020X1## 6KG1123025X1## 6KG1123030X1## 6KG1123040X1## 6KG1123050X1## 6KG1123060X1## 6KG1123075X1## 6KG1123100X1## 6KG1123125X1##
D6501 D6502 D6503 D6504 D6505 D6506 D6507 D6508 D6509 D6510 D6511 D6512 D6513 D6514 D6515 D6516 D6517 D6518
10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 8.66 x 7.68 10.24 x 8.66 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 29.7 x 13.5 x 10.0 33.1 x 14.9 x 10.6 38.0 x 14.9 x 10.6 38.0 x 14.9 x 10.6 41.3 x 21.0 x 11.2 50.4 x 26.9 x 14.2
4.8 4.8 5.5 8.4 8.4 8.4 13.4 13.4 22.0 22.0 23.1 23.1 70 86 106 110 172 282
6KG1123F25X4## 6KG1123F50X4## 6KG1123001X4## 6KG1123002X4## 6KG1123003X4## 6KG1123005X4## 6KG1123007X4## 6KG1123010X4##
D6551 D6552 D6553 D6554 D6555 D6556 D6557 D6558
10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 8.66 x 7.68 10.24 x 8.66 x 7.68
4.8 4.8 5.5 8.4 8.4 8.4 13.4 13.4
6KG1123015X2## 6KG1123020X2## 6KG1123025X2## 6KG1123030X2##
D6559 D6560 D6561 D6562
15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68
22.0 22.0 23.1 23.1
230VAC, 3 phase, 50/60Hz Input, NEMA 4 0.25 0.5 1 2 3 5 7.5 10
4 4 4 4 4 4 4 4
1.5 3 5 8 11 17 25 33
2.3 4.5 7.5 12 17 26 38 50
230VAC, 3 phase, 50/60Hz Input, NEMA 12 15 20 25 30
12 12 12 12
46 59 74 87
69 89 111 131
230VAC, 3 phase, 50/60Hz Input, Open 40 Open 115 173 6KG1123040X9## --21.7 x 13.4 x 10.0 64 50 Open 145 218 6KG1123050X9## --24.2 x 14.8 x 10.6 79 60 Open 180 270 6KG1123060X9## --29.1 x 14.8 x 10.6 97 75 Open 215 323 6KG1123075X9## --29.1 x 14.8 x 10.6 101 100 Open 283 425 6KG1123100X9## --29.5 x 20.9 x 11.2 154 125 Open 346 519 6KG1123125X9## --34.6 x 26.8 x 14.2 253 ## Indicates product revision. Note: Horsepower rating is shown for 230V and 460V nominal systems, 1800 RPM motors. When applying at lower voltage and lower speed AC motors, select the drive by rated current and not Hp rating.
viii
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 13
AF-300 G11 Dimensions & Weights HP Rating
NEMA Enclosure
Rated Output Overload Current (A) (150% 1min.)
AF-300G11 Model No.
Catalog Dimensions No. H x W x D (inches)
Weight (lbs)
230VAC, 3 phase, 50/60Hz Input, Open with NEMA 12 Heatsink 40 50 60 75 100 125
Open Open Open Open Open Open
115 145 180 215 283 346
173 218 270 323 425 519
6KG1123040X8## 6KG1123050X8## 6KG1123060X8## 6KG1123075X8## 6KG1123100X8## 6KG1123125X8##
-------------
21.7 x 13.4 x 10.0 24.2 x 14.8 x 10.6 29.1 x 14.8 x 10.6 29.1 x 14.8 x 10.6 29.5 x 20.9 x 11.2 34.6 x 26.8 x 14.2
64 79 97 101 154 253
6KG1143F50X1## 6KG1143001X1## 6KG1143002X1## 6KG1143003X1## 6KG1143005X1## 6KG1143007X1## 6KG1143010X1## 6KG1143015X1## 6KG1143020X1## 6KG1143025X1## 6KG1143030X1## 6KG1143040X1## 6KG1143050X1## 6KG1143060X1## 6KG1143075X1## 6KG1143100X1## 6KG1143125X1## 6KG1143150X1## 6KG1143200X1## 6KG1143250X1## 6KG1143300X1## 6KG1143350X1## 6KG1143400X1## 6KG1143450X1## 6KG1143500X1## 6KG1143600X1##
D6519 D6520 D6521 D6522 D6523 D6524 D6525 D6526 D6527 D6528 D6529 D6531 D6532 D6533 D6534 D6535 D6536 D6537 D6538 D6539 D6540 D6541 D6542 D6543 D6544 D6545
10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 8.66 x 7.68 10.24 x 8.66 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 15.75 x 9.84 x 7.68 29.7 x 13.5 x 10.0 29.7 x 14.9 x 10.6 34.6 x 14.9 x 10.6 34.6 x 14.9 x 10.6 38.0 x 14.9 x 10.6 38.0 x 21.0 x 12.4 38.0 x 21.0 x 12.4 53.1 x 21.0 x 14.2 53.1 x 21.0 x 14.2 55.1 x 26.9 x 14.2 55.1 x 26.9 x 14.2 57.1 x 26.8 x 17.7 57.1 x 26.8 x 17.7 57.1 x 34.6 x 17.7 57.1 x 34.6 x 17.1
4.8 5.5 8.4 8.4 8.4 14.3 14.3 22.0 22.0 23.1 23.1 70 82 95 97 115 174 245 245 245 337 337 562 562 804 804
6KG1143F50X4## 6KG1143001X4## 6KG1143002X4## 6KG1143003X4## 6KG1143005X4## 6KG1143007X4## 6KG1143010X4##
D6569 D6570 D6571 D6572 D6573 D6574 D6575
10.24 x 4.33 x 5.12 10.24 x 4.33 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 5.91 x 5.71 10.24 x 8.66 x 7.68 10.24 x 8.66 x 7.68
4.8 5.5 8.4 8.4 8.4 14.3 14.3
460VAC, 3 phase, 50/60Hz Input, NEMA 1 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.5 2.5 3.7 5.5 9 13 18 24 30 39 45 60 75 91 112 150 176 210 253 304 377 415 520 585 650 740
2.3 3.8 5.6 8.3 14 20 27 36 45 59 68 90 113 137 168 225 264 315 380 456 566 623 780 878 975 1110
460VAC, 3 phase, 50/60Hz Input, NEMA 4 0.5 1 2 3 5 7.5 10
4 4 4 4 4 4 4
1.5 2.5 3.7 5.5 9 13 18
2.3 3.8 5.6 8.3 14 20 27
460VAC, 3 phase, 50/60Hz Input, NEMA 12 15 12 24 36 6KG1143015X2## D6576 15.75 x 9.84 x 7.68 22.0 20 12 30 45 6KG1143020X2## D6577 15.75 x 9.84 x 7.68 22.0 25 12 39 59 6KG1143025X2## D6578 15.75 x 9.84 x 7.68 23.1 30 12 45 68 6KG1143030X2## D6579 15.75 x 9.84 x 7.68 23.1 ## Indicates product revision. Note: Horsepower rating is shown for 230V and 460V nominal systems, 1800 RPM motors. When applying at lower voltage and lower speed AC motors, select the drive by rated current and not Hp rating.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA ix
Page 14
AF-300 G11 Dimensions & Weights HP Rating
NEMA Enclosure
Rated Output Overload Current (A) (150% 1min.)
AF-300G11 Model No.
Catalog Dimensions No. H x W x D (inches)
Weight (lbs)
460VAC, 3 phase, 50/60Hz Input, Open 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600
Open Open Open Open Open Open Open Open Open Open Open Open Open Open Open
60 75 91 112 150 176 210 253 304 377 415 520 585 650 740
90 113 137 168 225 264 315 380 456 566 623 780 878 975 1110
6KG1143040X9## 6KG1143050X9## 6KG1143060X9## 6KG1143075X9## 6KG1143100X9## 6KG1143125X9## 6KG1143150X9## 6KG1143200X9## 6KG1143250X9## 6KG1143300X9## 6KG1143350X9## 6KG1143400X9## 6KG1143450X9## 6KG1143500X9## 6KG1143600X9##
-------------------------------
21.7 x 13.4 x 10.0 21.7 x 14.8 x 10.6 26.6 x 14.8 x 10.6 26.6 x 14.8 x 10.6 29.1 x 14.8 x 10.6 29.1 x 20.9 x 12.4 29.1 x 20.9 x 12.4 39.4 x 20.9 x 14.2 39.4 x 20.9 x 14.2 39.4 x 26.8 x 14.2 39.4 x 26.8 x 14.2 55.1 x 26.8 x 17.7 55.1 x 26.8 x 17.7 55.1 x 34.6 x 17.1 55.1 x 34.6 x 17.1
64 75 86 88 106 154 154 220 220 308 308 551 551 793 793
460VAC, 3 phase, 50/60Hz Input, Open with NEMA 12 Heatsink 40 Open 60 90 6KG1143040X8## --21.7 x 13.4 x 10.0 64 50 Open 75 113 6KG1143050X8## --21.7 x 14.8 x 10.6 75 60 Open 91 137 6KG1143060X8## --26.6 x 14.8 x 10.6 86 75 Open 112 168 6KG1143075X8## --26.6 x 14.8 x 10.6 88 100 Open 150 225 6KG1143100X8## --29.1 x 14.8 x 10.6 106 125 Open 176 264 6KG1143125X8## --29.1 x 20.9 x 12.4 154 150 Open 210 315 6KG1143150X8## --29.1 x 20.9 x 12.4 154 200 Open 253 380 6KG1143200X8## --39.4 x 20.9 x 14.2 220 250 Open 304 456 6KG1143250X8## --39.4 x 20.9 x 14.2 220 300 Open 377 566 6KG1143300X8## --39.4 x 26.8 x 14.2 308 350 Open 415 623 6KG1143350X8## --39.4 x 26.8 x 14.2 308 400 Open 520 780 6KG1143400X8## --55.1 x 26.8 x 17.7 551 450 Open 585 878 6KG1143450X8## --55.1 x 26.8 x 17.7 551 500 Open 650 975 6KG1143500X8## --55.1 x 34.6 x 17.1 793 600 Open 740 1110 6KG1143600X8## --55.1 x 34.6 x 17.1 793 ## Indicates product revision. Note: Horsepower rating is shown for 230V and 460V nominal systems, 1800 RPM motors. When applying at lower voltage and lower speed AC motors, select the drive by rated current and not Hp rating.
x
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 15
1. Before Using This Product 1.1 Receiving Instructions Unpack and check the product as explained below. If you have any questions about the product, contact GE Fuji Drives or your local GE Drives distributor. 1.
Check the ratings nameplate to confirm that the delivered product is the one that was ordered.
SER. No. : 9 9 1 0 - 0 0 0 1 2 M 0 0 01 Ratings Nameplate Production lot serial number Production week: Fiscal week (01 to 53) Production year: Last two digits of year (99 = 1999) 2. 3.
4.
Check for damaged and/or missing parts upon delivery. In addition to the drive unit and this manual, the package contains rubber bushings (for products with 30 Hp or less) and a terminating resistor (1/2 W, 120 ohm). The terminating resistors for products with 30 Hp or less is packaged separately. The terminating resistors for products with 40HP or more are installed internal to the drive unit. To connect the internal terminating resistor, place hardware jumper J2 to the “ON” position. This terminating resistor is required for RS485 RTU communication. On drives rated 100 Hp and larger a separately mounted DC Link Reactor is provided. The reactor should be checked for proper rating before installation.
1.2 Appearance Mounting screws of surface cover (Total of 6 screws) Mounting screws of surface cover
Lifting Holes (4 holes total)
Keypad Panel Intermediate cover Surface cover
Ratings nameplate
Keypad Panel
30 HP or less
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
40 HP or more Surface Cover
1-1
Ratings Nameplate
Page 16
1.3 Handling the Product (1) Removing the Cover For drives 30HP or less, loosen the cover mounting screws, then remove the cover by pulling from the top (see Figure 1.3.1).
Fig.1-3-1 Removing the Cover (for drives of 30HP or less)
For drives 40HP or more, first remove the six cover mounting screws, then remove the cover.
Mounting screws of service cover (6 positions total)
Fig.1-3-2 Removing the Cover (for drives of 40HP or more)
(2) Removing the Keypad Panel After removing the cover as explained in (1), loosen the keypad panel mounting screws and remove as shown in Figure 1.3.3 for drives 40HP or less. Mounting screws of Keypad panel
Fig.1-3-3 Removing the Keypad Panel (for drives of 30 HP or less)
For drives 40HP or more, loosen the keypad panel mounting screws and remove, using the finger holds on the keypad panel case. Keypad panel case
Fig.1-3-4 Removing the Keypad Panel (for drives 40HP or more)
1-2
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 17
1.4 Carrying Carry the product by the main unit. Do not carry the product by its cover or parts other than the main unit. Use a crane or hoist to carry a product equipped with hanging holes.
1.5 Storage Temporary Storage Temporary storage of this product must meet the conditions listed in Table 1-5-1. Table 1-5-1 Storage Environment
Item Ambient Temperature
Specifications -10° to +50°C Condensation or freezing, as a result of sudden temperature (+14° to +122°F) changes, must not occur.
Storage Temperature
-25° to +65°C1 (-4° to +149°F)
Relative Humidity
5 to 95%2
Atmosphere
The standard product must not be exposed to dust, direct sunlight, corrosive gas, flammable gas, oil mist, vapor, water drops, or vibration. The salt content in the atmosphere should be minimized.
Note 1: The storage temperature applies only to short periods of time, such as during transport. Refer to comments on extended storage guidelines. Note 2: Since a large change in temperature within this humidity range may result in condensation or freezing, do not store where such temperature changes may occur. 1. 2. 3.
Do not place this product directly on the floor. To store the product in an extreme environment, pack in vinyl sheeting, etc. If the product is stored in a high-humidity environment, insert a drying agent (e.g., silica gel) and pack the product in vinyl sheeting.
Long-term Storage If the product is to be stored for an extended period of time after purchase, the method of storage depends primarily on the storage location. The general long-term storage method is as follows: 1. 2. 3. 4.
The above conditions for temporary storage must be satisfied.If the storage period exceeds three months, the upper limit of ambient temperature must be reduced to 30°C (86°F) to prevent the deterioration of the electrolytic capacitors. Pack the product thoroughly to eliminate exposure to moisture and include a drying agent to ensure a relative humidity of about 70% or less. Do not leave the product mounted in a control panel and exposed to the elements like moisture or dust (particularly on a construction site). In this case, remove the product and store in a suitable environment. Electrolytic capacitors will deteriorate if not provided with power for an extended period of time. Do not store electrolytic capacitors for one year or longer without providing power.
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
1-3
Page 18
1.6 AF-300 G11 Drive Ratings Efficiency and Watts Loss HP Rating
Rated Output Current (A)
Rated Output Power (KVA)
Efficiency at 2KHz (%)
Efficiency at 15KHz (%)
Watts Loss at 2KHz (W)
Watts Loss at 15KHz (W)
Internal DB (W)
0.25 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
1.5 3 5 8 11 17 25 33 46 59 74 87 115 145 180 215
0.59 1.1 1.9 3.1 4.3 6.7 9.9 13 18 23 29 34 45 57 71 85
283 346
112 137
90.5 91.7 94.0 94.1 94.9 95.4 95.2 95.3 95.2 95.9 95.8 95.5 96.5 96.4 96.6 96.8 10KHz (%) 97.0 97.0
25 35 50 80 110 170 240 300 450 540 670 880 950 1200 1400 1600 2KHz (W) 2150 2600
30 45 60 110 140 210 310 415 620 720 890 1160 1200 1550 1750 2050 10KHz (W) 2500 3000
10 10 10 30 30 30 60 60 N/A N/A N/A N/A N/A N/A N/A N/A
100 125
92.0 93.5 94.9 95.7 95.9 96.2 96.2 96.5 96.4 96.9 96.8 96.5 97.2 97.2 97.3 97.4 2KHz (%) 97.4 97.4
0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
1.5 2.5 3.7 5.5 9 13 18 24 30 39 45 60 75 91 112
1.1 1.9 2.9 4.3 7.1 10 14 19 23 31 35 47 59 72 89
150 176 210 253 304 377 415 520 585 650 740
119 140 167 202 242 300 330 414 466 518 590
89.3 91.7 94.1 94.5 95.0 95.3 95.4 95.9 96.5 96.4 96.4 96.4 96.1 96.4 96.5 10KHz (%) 97.2 97.2 97.3 97.3 97.3 97.4 97.4 97.4 97.4 97.4 97.4
35 45 60 80 130 170 230 300 360 460 550 750 950 1100 1300 2KHz (W) 1550 1950 2400 2650 3250 3900 4350 5450 6150 6700 7750
60 85 110 150 230 300 400 520 610 770 900 1250 1650 1850 2200 10KHz (W) 2350 2800 3350 3900 4700 5750 6300 7950 8950 9950 11300
10 10 30 30 30 60 60 N/A N/A N/A N/A N/A N/A N/A N/A
100 125 150 200 250 300 350 400 450 500 600
93.5 95.4 96.7 97.0 97.1 97.3 97.3 97.6 97.9 97.8 97.8 97.8 97.7 97.8 97.9 2KHz (%) 98.1 98.0 98.0 98.2 98.1 98.2 98.2 98.2 98.2 98.3 98.2
230VAC
N/A N/A
460VAC
1-4
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 19
2. Installation Environment and Connection 2.1 Operating Environment
CAUTION
Install this product in a location that meets the conditions listed in Table 2-1-1.
Ensure that the drive and heat sink surfaces are kept free of foreign matter such as lint, paper dust, small chips of wood or metal, and dust. Fire or accident may result.
Table 2-1-1 Operating Environment Item Location Ambient Temperature
Relative Humidity Atmosphere
Altitude Vibration
Specifications Indoors -10° to +50°C (+14° to +122°F) - for products of 30 HP or less, the ventilating covers must be removed if ambient temperature exceeds +40°C (104°F), NEMA Type 4 & 12 Unit -10° to +40°C (+14° to +104°F) 5 to 95% (No condensation).
Table 2-1-2 Output current reduction rate based on altitude Altitude 3300 feet (1000m or lower) 3300-4950 feet (1000-1500m) 4950-6600 feet (1500-2000m) 6600-8250 feet (2000-2500m) 8250-9900 feet (2500-3000m)
The product must not be exposed to dust, direct sunlight, corrosive gas, oil mist, vapor, or water. There must be a minimum salt content in the atmosphere. Do not store where condensation may occur as a result of sudden changes in temperature. 1000 m (3300 feet) or lower - For altitude above 1000 m (3300 feet), see Table 2-1-2. 3mm peak from 2 to 9Hz, 9.8m/s2 from 9 to 20Hz, 2m/s2 from 20-55Hz, 1m/s2 from 55 to 200Hzs.
Top
2.2 Installation Method 1.
2.
3.
Left X
5.
6.
Data subject to change without notice 9/00. © 1999 GE Fuji Drives USA
0.95 0.91 0.88
4” (100mm)
AF-300 G11 Drive
Bottom
Right X
4” (100mm)
Internal Heat Dissipation (30%)
Install this product on nonflammable material such as metal. When installing this product in a control panel, consider ventilation to prevent the drive’s ambient temperature from exceeding the specified value. Do not install the product in an area from which heat cannot be sufficiently released. If two or more drives must be installed in the same device or control panel, arrange the units horizontally to minimize the effect of heat. If two or more drives must be installed vertically, place an insulated plate between the drives to minimize the effect of heat. When shipped from the factory, drives provide internal cooling inside the panel. A drive of 30HP or less can be converted to external cooling simply by adding an optional mounting adapter.
0.97
Fig. 2-2-1 30 HP or less: Gap X can be 0. (side-by-side installation) 40HP or more: Gap X >= 2.0” (50mm)
Securely fasten the product in an upright position on a solid structure with the tag AF-300G11 facing the front. Do not turn the product upside down or install in a horizontal position. Fig. 2-2-1 Since heat is generated during drive operation, the spaces shown in Fig. 2-2-1 are required to ensure sufficient cooling. Do not install the product beneath a device sensitive to heat as heat radiates upward. The heat sink may reach a temperature of 90°C (+194°F) during drive operation. Ensure that the material surrounding the product can withstand this temperature.
WARNING
4.
Output current reduction rate 1
Internal fan Internal air supply
Fig. 2-2-2 Through Panel Mount
2-1
External Heat Dissipation
(70%) Cooling fan
Heatsink External air supply
Page 20
A drive of 40HP or more can be converted to external cooling simply by moving the upper and lower mounting brackets as shown in Fig. 2-2-3. Remove the M6 bracket screws, move the brackets, then secure the brackets using the M5 case mounting screws. (The bracket screws are no longer required after changing the bracket mounting position.)
Installation of Open Type with NEMA 12 Heatsink Drive (40 Hp and above)
Bracket Screws (M6) Case mounting screws (M5) 10 screws total
Fig. 2.2.6
Mounting
Fig.2.2.5 Mounting bracket
1. Fig. 2-2-3
In an external cooling system, a heat sink radiating about 70% of total drive heat (total loss) can be placed outside the device or control panel, as shown in Fig. 2-2-2.
2.
3.
7. For drives of 30HP or less, remove the ventilating covers if ambient temperature exceeds +40°C (104°F).
1. Removing the Ventilating Covers One ventilating cover is mounted on top of the drive and two or three are mounted at the bottom. Remove the main cover and then remove ventilating covers by popping out the cover inserts as shown in Fig. 2-2-4.
Remove adhesive protection strip from gasket and then mount gasket to panel/enclosure, carefully aligning cutout and mounting holes. Install the drive unit and tighten the mounting bolt and nut. (Tightening torque: 119 lbs-inch [M8], 425 lbs-inch [M12] ). Mounting hardware to be supplied by customer. (refer to figure 2.2.5) After proper torque has been applied to all mounting hardware, seal the outside end of the hardware with silicon glue. Silicon glue to be supplied by the customer. (Refer to Fig. 2.2.6)
Fig. 2-2-4 Removing the ventilating cover
2-2