Page 141

Code 0 1 2 3 5 6 7 8 10 11 14 16 17 18 19

Description No alarm Overcurrent, during acceleration (INV output ) Overcurrent, during deceleration (INV output ) Overcurrent, during steady state operation (INV output ) Ground fault Overvoltage, during acceleration Over voltage, during deceleration Overvoltage, during steady state operation DC undervoltage Power supply open phase Blown DC fuse Output wiring error Overheat, heat sink, inverter Overheat, outside thermal Overheat, unit inside temp

Data format [11] Code 7 15 25 50 100 200 300 500 750 1000 1500

Data format [12]

Code 2000 2500 3000 4000 5000 6000 7500 10000 12500 15000

Description Overheat, DB resistor Overload, motor 1 Overload, motor 2 Overload, drive dbH OL1 OL2 OLU

27 28 31 32 33 34 35 36 37 38

Overspeed PG wire break Memory error Keypad error CPU error Option comm error Option error PL error Output wiring error RS485 comm error

OS Pg Er1 Er2 Er3 Er4 Er5 Er6 Er7 Er8

Capacity (HP) 20 25 30 40 50 60 75 100 125 150

Code 17500 20000 25000 30000 35000 40000 45000 50000 60600 60700 60800

Capacity (HP) 175 200 250 300 350 400 450 500 600 700 800

Index data (ACC/DEC time, display coefficient)

15

14

13

12

11

Polarity

0

0

0

Index portion

0: Positive (+),

EF OU1 OU2 OU3 LU Lin FUS Er7 OH1 OH2 OH3

Code 22 23 24 25

Capacity code Capacity (HP) 0.07 (spare) 0.15 (spare) 0.25 0.5 1 2 3 5 7.5 10 15

1: Negative ( - ), OC1 OC2 OC3

10

9

0: 0.01 X 1: 0.1 X 2: 1 X 3: 10 X

8

7

6

4

3

2

Data portion 001–999 00–999 100–999 100–999

Example: If F07 (acceleration time 1) = 20.0 s 10.0 < 20< 99.9 ➞ index =1 20.0 = 0.1 X 200 ➞ 0400H + 00C8H = 04C8H

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

5

12-5

(0.00–9.99) (10.0–99.9) (100–999) (1000–9990)

1

0

Page 142

Data format [13]

Pattern operation

15

14

13

Direction of rotation

0

Time

12

11

9

8

7

6

Index portion

0: 1st ACC/DEC time 1: 2nd ACC/DEC time 2: 3rd ACC/DEC time 3: 4th ACC/DEC time

0: FWD 1: REV

10

5

4

3

2

1

0

1

0

Data portion

0: 0.01 X 1: 0.1 X 2: 1 X 3: 10 X

001–999 100–999 100–999 100–999

(0.00–9.99) (10.0–99.9) (100–999) (1000–9990)

Example) If C22 (Stage1) = 10.0s R2 (10s, reverse rotation, acceleration time 2/deceleration time 2) Since 10.0 = 0.1 X 100 > 9000H + 0400H + 0064H = 9464H Data format [14] 15 14 13 RST

0

0

Operation command 12 11 10 9

8

7

6

5

4

3

2

0

X7

X6

X5

X4

X3

X2

X1 REV FWD

0

X9

X8

(All bit are ON by 1) Example If S06 (operation command) = FWD, X1 and X5 = ON 0000 0000 0100 0101b = 0045H Data format [15]

Universal output terminal

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

Y5

Y4

Y3

Y2

Y1

4

3

2

1

0

(All bit are ON by 1) Example) If M15 (Universal output terminal)=Y1 and Y5 = ON 0000 0000 0001 0001b = 0011H Data format [16] 15 14 13

Operating state 12 11 10

BUSY

RL

WR

ALM

9

DEC ACC

8

7

6

5

IL

VL

TL

NUV BRK INT EXT REV FWD

12-6

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 143

(All bit are ON or active by 1) FWD: Forward operation IL: REV:0: Reverse operation ACC: EXT: DC braking active (or pre-excitation) DEC: ALM: INT: No Output RL: BRK: Braking active WR: NUV: DC link voltage is established (undervoltage at 0) TL: Torque limiting VL: Voltage limiting BUSY:

Data format [17] 15

14

Type code 13

12

11

Type Code 1 2 3 4 5 6

14

10

9

8

7

6

Generation Type G P -

Data format [18]

15

Current limiting Under acceleration Under deceleration Drive fault Transmission valid Function writing privlege 0: Keypad panel 1: RS485 2: Fieldbus (option) Processing data write

Generation G11 -

5

4

3

Series

Series USA -

12

11

Data 4

Voltage series 230V three phase 460V three phase 575V three phase -

10

9

8

7

6

Data 3

5

4

3

Data 2

Amperage value Decimal data (positive ): Min. unit 0.01 inverter capacity is not more than 30HP Min unit 0.01 for not less than 40HP Example) If F11 (electronics thermal overload relay 1 level)107.0A (40HP) 107.0 X 10=1070=042EH If F11 (electronics thermal overload relay 1 level)=3.60A (1HP) Since 3.60 X 100=360=0168H

7

0

Voltage series

Data format [19]

Code 1 2 3

1

Code setting (1–4 figures)

13

Data format [20]

2

Transmission error code

Description FC (function code) error Illegal address Illegal address (Data range error)

Code 71 72 73

Description CRC error (no response) Parity error (no response) Other errors (no response) -Framing error -Overrun error -Buffer full error

NAK -Priority for comm -No privilege for writing error -Forbidden writing error

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

12-7

2

1

Data 1

0

Page 144

Data format [21]

Auto tuning

15

14

13

12

11

10

9

8

0

0

0

0

0

0

REV FWD

7

6

5

4

3

2

1

0

Data portion 0: Without forward rotation command 1: With forward rotation command. 0: Without reverse rotation command. 1: With reverse rotation command.

Example) If P04 (motor 1 auto - tuning)=1: Forward rotation 0000 0001 0000 0001b=0101H 12-7 Communication Errors Exception Response When the drive receives a message that does not contain communication errors but the message can not be processed, the drive will return an exception response. The exception response contains an error sub-code in the data field that represents the problem. Exception Response Errors Sub-Code Name 1 Illegal Function 2 Illegal Data Address

3 7

Illegal Data Value Negative Acknowledge

Causes Received RTU Function other than 03, 06 or 16 • The starting parameter address is an unused drive parameter.. The starting parameter address plus the offset refers to drive • parameter greater than the last parameter in a Function Code sort. • The number of registers is greater than 16. Data contains an out of range value for a drive parameter • Requested data cannot be changed while the drive is running. The drive parameter function is owned by the network interface • option card and cannot be changed.

Communication errors Communication errors occur when the drive receives an invalid message. The drive will not return a response to a communication error. A code that represents the last communication error is stored in drive parameter M26. Typical communication message errors include parity, framing, and CRC errors.

12-8

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 145

13. Options 13.1 Built-in Options The drive supports two internally mounted cards. One option card is mounted under the main cover (Location A) and the other option card is mounted in a special adapter under the keypad (Location B). Only one card can be mounted in these locations. There are two different types of option cards, Type 1 and Type 2. You cannot use two Type 1 or Two Type 2 cards but you can mix any combination of Type 1 and Type 2 provided you only have one option per mounting location. Each option card must be mounted in the designated location. The chart below lists the option card, their types, and their mounting locations. Name

Type Loc

2nd Option Function Type/Loc 2/B • Relay output card The transistor output from the drive control output terminals Y1 and Y4 are converted to the relay output (1SPDT). None • Frequency setting by binary code (max. 16 bits) • Monitoring (8 bits) of frequency, output current, and output voltage

OPCG11SRY (Relay output card)

1

A

OPCG11SDIO (Digital interface card)

2

A

OPCG11SAIO (Analog interface card)

2

A

None

• Auxiliary input for analog frequency setting (0 to +/-10 V) • Monitoring of drive output frequency, current, and torque in analog voltage, analog output 0-10 VDC abd 4-20mA

OPCG11SPG (PG Feedback Card)

1

A

2/B

• This will enable vector control by pulse generator feedback signal • Proportional operation, tuning operation (12/15 V; A, B Signal)

OPCG11SPG2 (PG Feedback Card)

OPCG11SSY (Synchronized operation card) OPCG11SCIO (Interface card) OPCG11SLON (Communication card) OPCG11SPDP (Communication card) OPCG11SDEV (Communication card) OPCG11SCOP (Communication card) OPCG11SMBP (Communication card) OPCG11SIBS (Communcation card) HE300GEN150 (Communication card)

1

A

2/B

• This will enable vector control by pulse generator feedback signal • Proportional operation, tuning operation (5V; A, not A, B, not B Signals) • Two motors are driven synchronously.

1

A

2/B

1

A

2/B

2

B

1/A

• 115 VAC Control input, an isolation amplifier, relay output, PG encoder, analog output 4-20mA • Serial communication card for LonWorks

2

B

1/A

• Serial communication card for Profibus-DP

2

B

1/A

• Serial communication card for Device Net

2

B

1/A

• Serial communication card for CAN

2

B

1/A

• Serial commnication card for Modbus plus

2

B

1/A

• Serial communcation card for Interbus-S

2

B

1/A

• Serial communication card for Genius

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

13-1

Page 146

Name Type Function Specifications

Digital I/O interface card OPCG11SDIO 4 digital inputs: Binary code input of max. 16 bits or BCD input (Sink/Source changeable) 3 digital outputs: Binary code output of max. 8 bits. Input Digital signal input (4 points) by short-circuiting terminals L1, L16 and M1 <Sink> ON operation current: 4.5mA max. OFF operation voltage: 27V max. <Source> ON operation current: 4.5mA max. OFF operation voltage: 27V max. Related function code: o19, o20 Output Digital signal output (3 points) by short-circuiting terminals between O1 to O6, and M2 <Sink> ON operation current: 50mA max. OFF operation voltage: 27V max. <Source> ON operation current: -50mA max. OFF operation voltage: 27V max. Related function code: o21 Power Source +24 VDC (3.2mA x 4 + 12.8mA)

L1/R L2/S L3/T

AF-300 G11S

Connection diagram U V W

OPC-G11S-DIO

I16 O8(MSB) I15 I14 O7 I13 I12 O6 I11 I10 O5 I9 I8 O4 I7 I6 O3 I5 I4 O2 I3 Sink I2 O1(LSB) I1(LSB) M1

M

Ry Ry Ry Ry Ry Ry Ry Ry

M2

CM

∂@ G

Remarks

13-2

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 147

Name Type Function Specifications

Connection diagram

PG feedback card (AF-300 G11 only) OPCG11SPG2 To perform speed control by detecting motor rotating speed using a pulse generator. Speed Control Range Control 3 to 3600 [rpm] (for 4-pole motor) Speed Control Accuracy ±0.02% Starting Torque 150% zero-speed (at ZERO signal ON) short time Maximum number of Input Pulse 100 (kp/s) Applicable Output Pulse 20 to 3000P/R (A, not A, B, not B) encoder PG Power Supply +5 VDC ± 10%/200mA (generator) Maximum Response Frequency 100kHz Input Terminal PI Pg External Power Supply Input PO PG Power Supply Output CM Common YA Input Feedback PG Phase A (+) Pulse *YA Input Feedback PG Phase A (-) Pulse YB Input Feedback PG Phase B (+) Pulse *YB Input Feedback PG Phase B (-) Pulse +5 VDC ± 10%/200mA1 Power Internal Power Supply Source External Power Supply 5 VDC ± 10% 1 Please use an external power supply when you exceed 200mA. I. Drive internal power supply L1/R

II. External Power Supply

U

L2 / S

V

L3 / T

W

U

L1 /R L2/ S L3/ T

M

G

G PI D Fe edba ck Car d

PI D Fe edba ck Car d

PI

PI

J1 INT

M

V W

J1 INT

EXT PO YA * YA YB * YB CM

EXT PO YA * YA YB * YB CM

PG

PG

5 Vdc –10%

Remarks

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

13-3

Page 148

Name Type Function Specifications

PG feedback card ( AF-300 G11 only) OPCG11SPG To perform speed control by detecting motor rotating speed using a pulse generator. Speed Control Range Control 1: 1200 (3 to 3600r/min) Maximum speed 3600r/min) (120 Hz) Speed Control accuracy ±0.02% Speed Control response 40 Hz Applicable • No. of output pulses: 100 to 3000P/R A/B phase (incremental) encoder • Maximum response frequency: 100kHz (generator) • Pulse output method: Totem pole / open collector. Output current 7mA or more. Input terminal YA, YB, CM Connect A- and B-phase output signal from pulse generator on feedback side. YZ, CM

Output Power source

Connect Z-phase output signal from ppulse generator on feedback side. When the pilse generator does not have Z-phase, these terminals need not be connected.

None • Internal power source: +15 VDC ± 10% 120mA, + 12 VDC ± 10% 120mA (Changeable on PC board1) (Terminal: PO, CM) • External power source: +12 VDC (-10%) to +15 VDC (+1-%) / 300mA or less2) (Terminal P1, CM. 1

Use external power source when more than one PG feedback cards are used and the total input current exceeds 120mA. 2 Take note of the power source matches the specifications of the applied pulse generator. Connection diagram

I. Drive internal power supply L1 /R

U

L2/ S

V

L3 / T

II. External Power Supply

M

W

L 1 /R

U

L 2 /S

V

L3 /T

W

G

G

PI D Fe edba ck Car d a)12VDC

PI D Fe edba ck Car d

PI PO INT EXT XA J2 XB 15V 12V XZ b) 1 5 VDC CM PO J1 INT EXT YA YB J2 1 5 V 1 2 V YZ CM J1

J1 INT J2 15V

PG

M

PI PO XA XB EX T XZ CM 12V PO YA YB YZ CM

PG

1 2 VDC –10% 1 5 VDC –10%

The Jumper J2 can be connected to the 12V or 15V side.

Remarks

Terminals XA, XB abd XZ are not in use.

13-4

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

Page 149

Name Type Function Specifications

Synochronized operation card ( AF-300 G11 only) OPCG11SSY To perform position control by pulse train input, synchronized operaton of 3 motors (wait-and-synchronize operation, simultaneous-start-and synchronize operation, and proportional speed ration operation) Speed Control Range Control 1: 1200 (3 to 3600r/min) Maximum speed 3600r/min) (120 Hz) Speed Control accuracy ±0.02% Speed Control response 40 Hz Applicable • No. of output pulses: 20 to 3000P/R A/B phase (incremental) encoder • Maximum response frequency: 100kHz (generator) • Wiring length: 100m (totem pole) / 20 (Open collector) • Pulse output method: Totem pole / open collector, output current 7mA or more. XA, XB, CM Connect A- and B-phase output signal of master rotary encoder Input terminal XZ, CM Connect Z-phase output signal of master rotary encoder YA, YB, CM Connect A- and B-phase output signal of feedback or master rotary encoder YZ, CM Connect Z-phase output signal of master rotary encoder None 1 Use external power source when more than one PG feedback cards are used and the total input current exceeds 120mA. 2 Take note of the power source matches the specifications of the applied rotary encoder.

Output Power source

Connection diagram

I. Drive internal power supply

R

U

S

V

T

W

II. External Power Supply Slave side

Command side

R

U

M

M

S

V

T

W

G

G

Synchronous option card

Synchronous option card a) 12 Vdc

PI PO YA J2 YB 15V 12V YZ b) 15Vdc C M J1 INT

EXT

PO EXT XA XB J2 15V 12V XZ CM

J1

PG

I NT J2 15 V

J1 INT

PG

PI PO YA YB EXT YZ CM

Slave side

Command side

M

M

PG

12 V

PO XA XB XZ CM

PG

12Vdc – 10% 15Vdc – 10%

* Pin J2 may be connected on either the 12V or 15V side.

The above diagrams are used when the drive internal power source is used. When using external power source, perform connection similar to the above connection, be referring to footnote2 Whne using external power supply of the PG feedback card. Remarks

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA

13-5

Page 150

Name Type Function Specifications

Connection diagram

Analog I/O Interface Card OPCG11SAIO 3 analog inputs (2 voltage inputs and 1 current input): Torque limiting value (driving, braking), frquency setting, ratio setting can be input respectively. 2 analog outputs (1 voltage output and 1 current output): 11 types of data can be output. Input Analog signal input (3 points) 32 and 31, 22 and 21, C2 and 21. Terminal 32: Voltage input (both sides): 0 to ±10 VDC / 0 to ±100%, input impedance: 22k ohm. Terminal 22: Voltage input (both sides): 0 to +10 VDC / 0 to +100%, input impedance: 22k ohm. Terminal C2: Current input: 4 to + 20mADC / 0 to +100%, input impedance: 250k ohm. For voltage input, power supply terminal for variable resistor (P10) should be connected. Related function code o22 Output Analog signal input (2 points) between AO+ and AO-, CS+ and CSTerminal AO+: Voltage output: 0 to ±10 VDC, for max. 2 voltmeters, input impedance: 10k ohm Terminal AO-: Voltage output common. Terminal CS+: Current output: 4 to 20mAdc, max. 500 ohm Terminal CS-: Current output common (Terminal CS- is isloated from terminal 21, 31 and AO-) Related function code o23 MCCB or ELCB L1/R L2/S L3/T

U V W

(R0) *

30A 30B 30C

(T0) *

M

13 12 11 AF-3 0 0G 11 C1

RUN command input

Y5A Y5C Y4 Y3 Y2 Y1 CM E PLC FW REV D CM X1 X2

32 31

X3 X4 X5 X6 X7 X8 X9 CM

VR (1k ohm)

22

VR

21

(1k ohm)

C2

(+)

Voltage input (Both polarity)

Voltage input (Single polarity)

Current input

(-) AO+ AOCS+

FM A FM P DX B DX A SD

CS-

Analog voltmeter

Anammeter

E(G)

* Te rm i na ls [ R0 ] an d [ T0] ar e no t prov id ed f or 1.0 HP or s m aller.

Remarks

13-6

Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA