Page 131
Surface Mount W
D
W6
D1 H8
H2
D2
D7
H9
W1 W3
W5
W4
D3 D5
D6
Holes for mtg. bolts D4
H1
4-ØC
460V Series NEMA 1 Hp 400 450 500 600
W 26.8 (680) 34.6 (880)
W1 22.8 (580) 30.7 (780)
W4 – 10.2 (260)
DIMENSIONS inches (mm) W5 W6 H1 H2 24.0 21.9 53.9 52.4 (610) (555) (1370) (1330) 31.9 29.7 (810) (755)
DIMENSIONS inches (mm)
Hp 400 450 500 600
W3 11.4 (290) 10.2 (260)
D2 0.3 (6)
D3 2.0 (50)
D4 3.9 (100)
D5 1.4 (35)
D6 4.5 (115)
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
D7 8.7 (220)
Mtg. Bolts M12
Wt. Lb (kg) 562 (255) 804 (365)
11-7
H4 52.6 (1335)
H8 3.3 (084)
H9 57.1 (1450)
D 17.7 (450)
D1 11.2 (285)
Page 132
11.3.2 Outline Dimensions Open Type Surface Mount
Through Panel Mount
H1
230V Series Hp 230V 40 50
W 13.4 (340) 14.8 (375)
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
20.9 (530) 26.8 (680)
16.9 (430) 22.8 (580)
20.1 (510) 26 (660)
W 13.4 (340) 14.8 (375)
W1 9.4 (240) 10.8 (275)
W2 12.8 (326) 14.2 (361)
W3
60
H 21.7 (550) 24.2 (615) 29.1 (740)
H1 20.9 (530) 23.4 (595) 28.3 (720)
DIMENSION Inch (mm) H2 H3 H4 19.7 20.2 0.5 (500) (512) (12) 22.2 22.7 (565) (577) 27.2 27.6 (690) (702)
H5 1 (25)
H6 0.4 (9)
D 10 (255) 10.6 (270)
1.3 (33)
0.5 (13)
11.2 (285) 14.2 (360)
D1 5.7 (145)
D2 0.2 (4)
C 0.4 (10)
Mtg. Bolts M8
75 100 125 460V Series Hp 460V 40 50
W3
60
29.5 (750) 34.6 (880)
27 (685) 32.1 (815)
27.4 (695) 32.5 (825)
33.5 (850)
H 21.7 (550)
H1 20.9 (530)
26.6 (675)
25.8 (655)
24.6 (625)
25.1 (637)
29.1 (740)
28.3 (720) 28 (710) 38.2 (970)
27.2 (690) 26.6 (675) 36.8 (935)
27.6 (702) 27 (682) 37.2 (945)
0.6 (16)
DIMENSION Inch (mm) H2 H3 H4 19.7 20.2 0.5 (500) (512) (12)
0.6 (15)
M12
8.7 (220)
H5 1 (25)
H6 0.4 (9)
D 10 (255) 10.6 (270)
D1 5.7 (145)
1.3 (33)
0.5 (13)
12.4 (315) 14.2 (360)
6.9 (175) 8.7 (220)
D2 0.2 (4)
C 0.4 (10)
Mtg. Bolts M8
75 100 125 150 200 250 300 350
20.9 (530)
16.9 (430)
20.1 (510) 39.4 (1000)
26.8 (680)
22.8 (580)
26 (660)
11.4 (290)
11-8
0.6 (16)
0.6 (15)
M12
Weight Lb (kg) 64 (29) 79 (36) 97 (44) 101 (46) 154 (70) 253 (115) Weight Lb (kg) 64 (29) 75 (34) 86 (39) 88 (40) 106 (48) 154 (70) 220 (100) 308 (140)
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 133
Surface Mount
Through Panel Mount
D
D1
W 3 or 4 dia. C
W1 W3
W4
H6
D1
D1 D2
D2
W2
W2
D2
H6
H2 H1
Alternative Through Panel Mount (bottom bracket support by customer supply.
H
C
W1
W1 W3
W5
W4
W3
W4
W H7 W4
H7
Holes for mtg. bolts H4
H4
W3 D5
4-dia.1.4 (35) Lifting bolts
D3
D6
Holes for mtg. bolts
Holes for mtg. bolts
D4
H3 H1
H1 4-ØC
460V Series Open Type Hp 400 450 500 600
W 26.8 (680) 34.6 (880)
Hp 400 450 500 600
W1 22.8 (580) 30.7 (780)
W2 26.0 (660) 33.8 (860)
W3 11.4 (290) 10.2 (260)
W4
10.2 (260)
W5 24.0 (610) 31.9 (810)
D6 4.5 (115)
C 0.6 (015)
–
DIMENSIONS inches (mm) D2 0.3 (6)
D3 2 (50)
D4 3.9 (100)
D5 1.4 (35)
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
DIMENSIONS inches (mm) H H1 H2 H3 H4 H5 55.1 53.9 52.4 52.8 52.6 0.6 (1400) (1370) (1330) (1340) (1335) (016)
Mtg. Bolts M12
Wt. Lb (kg) 551 (250) 793 (360)
11-9
H6 1.4 (035)
H7 0.6 (015)
D 17.7 (450)
D1 11.2 (285)
Page 134
11.3.3 Outline Dimensions Open Type with NEMA 12 Heatsink
11-10
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 135
AF-300 G11 230 VAC Series HP W 40 15.04 (382)
W4
W5
W6
W7 W8 W9
W2
W3
14.41 (366)
13.39 (340)
12.83 9.45 (326) (240)
4.72 (120)
21.65 20.87 (550) (530)
19.69 (500)
20.16 (512)
16.42
15.79
14.76
14.21 10.83
5.41
24.21 23.43 (615) (595)
22.24 (565)
22.72 (577)
(417)
(401)
(375)
(361)
29.13 (740) 28.35
27.17 (690)
27.64 (702)
50 60
DIMENSIONS Inch(mm) H1 H2 H3 H4
W1
(275)
-
(137.5)
-
-
-
H
75
H5
H6
H7
H8
3.74 (95) 0.47 (12)
0.98 (25)
22.28 (566)
20.87 (530)
20.08 16.93 (510) (430)
8.46 (215)
125 29.13 (740)
28.19 (716)
26.77 (680)
25.98 22.83 11.42 (660) (580) (290)
0.35 1.67 6.69 (9) (42.5) (170) 4.13 (105)
32.09 (815)
32.48 (15.5) (32.5) (12.5) 4.02 8.46 (825) (102) (215)
W6
W7 W8 W9
H
D
D1
Fixing Wt. Fig Bolts Lb(kg)
23.43 0.43 (595) (11)
66 (30)
0.4 5.71 (10) 10.63 (145)
M6 and
81 (37)
(270)
M8
99 (45)
-
(720) 27.36 (695)
34.65 33.46 (880) (850)
C
8.86 (225)
-
26.97 (685)
2.95 (75)
H12
28.35
29.53 (750)
-
H10 H11
20.87 (530)
(720)
100 23.23 (590)
H9
0.61
1.28
1.75 8.27 0.49 (44.5) (210)
1
2
104 (47) 0.51
33.46 (850)
(13)
H9
H10 H11
11.22 5.71 0.6 (285) (145)
M6 and
161 (73)
(15) 14.17 8.66 (360) (220)
M12
260 (118)
4
AF-300 G11 460 VAC Series HP W 40 15.04 (382)
W1
W2
W3
W4
14.41 (366)
13.39 (340)
12.83 9.45 (326) (240)
W5
4.72 (120)
50 60
16.42 (417)
15.79 (401)
14.76 (375)
14.21 10.83 (361) (275)
75
5.41 (137.5) -
-
-
100
DIMENSIONS Inch(mm) H1 H2 H3 H4
23.23 200 (590) 250 300 29.13 350 (740)
22.28 (566)
20.87 (530)
20.08 16.93 (510) (430)
28.19 (716)
26.77 (680)
25.98 22.83 11.42 (660) (580) (290)
-
400 29.13 450 (740)
28.19 (716)
26.77 (680)
25.98 22.83 11.42 (660) (580) (290)
2.95 4.55 2.60 (75) (115.5) (66)
500 37.01
36.06
34.65
33.86 30.71 10.24
4.72
600 (940)
(916)
(880)
(860)
(120)
(780)
H7
H8
19.69
20.16
3.74
20.87
(550)
(530)
(500)
(512)
(95)
(530)
26.57 25.79 (675) (655)
24.61 (625)
25.08 (637)
0.47
0.98
0.35
6.69
(12)
(25)
(9)
2.85 (170) (72.5)
25.79 (655)
H12
C
D
D1
Fixing Wt Fig Bolts Lb(kg)
8.86 (225)
66 (30)
0.43
0.4
(11)
(10) 10.63 (145) (270)
5.71
M6 and
77 (35)
M8
88 (40)
-
90 (41) 28.35 (720) 27.95 (710)
27.17 (690) 26.57 (675)
27.64 (702) 26.97 (685)
8.46 (215)
(260)
H6
21.65 20.87
29.13 (740) 29.13 (740)
125 150
H5
4.13 (105) 1.56 8.27 (39.5) (210)
28.35 (720) 27.95 (710)
0.61 1.28 0.49 (15.5) (32.5) (12.5)
-
0.6 (15)
2
108 (49) 161 (73)
12.4 6.89 (315) (175)
0.51 (13)
1
M6 and M12
229 (104) 317 (144)
5
M8
551
6
55.12 53.94 52.36 52.76 0.61 1.38 0.57 0.18 6.99 8.46 5.71 54.37 0.81 0.59 17.72 11.22 and 2.76 2.56 4.33 (1400) (1370) (1330) (1340) (15.5) (35) (14.5) (4.5) (177.5) (215) (145) (1381) (20.5) (15) (450) (285) M12 (70) (65) (110)
(250)
2.95 (75)
39.37 38.19 (1000) (970)
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
36.81 (935)
37.20 (945)
11-11
2.15 8.46 (54.5) (215)
38.19 (970)
14.17 8.66 (360) (220)
793 (360)
3
7
Page 136
Keypad Mounting Hole (Panel Cutting) Dimensions in inches (mm)
dia. 0.11 M3
2.68 (68)
0.81 (20.5)
4.53 (115)
1.69 (42)
dia. 1.38 (35)
11-12
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 137
12. RS485 Modbus RTU Serial Communications The serial interface supports operation, configuration and monitoring of drive functions through an EIA/RS485 connection. The serial interface is based on Modbus RTU protocol. This protocol allows the drive to function as an RTU slave on an industrial network.
12.1 Transmission Specification Item Physical level
Specification EIA/RS485
Transmission distance Number of nodes
500 m max. 32 total
Transmission speed Transmission mode
19200, 9600, 4800, 2400 [bits/s] Half duplex
Transmission protocol Character code
Modbus RTU Binary
Character length Error check
8 bits CRC
12.2 Connection Connection method Use shielded wire and connect to the control terminals (DX-, DX+ and SD). A termination resistor should be added between the data lines on the each end of the network. The value of the termination resistor depends on the characteristic impedance of the cable. A common value for termination resistors is 120 ohms.
Control terminals Terminal marking
Terminal name
Function description
DX+ DX-
RS485 communication data (+) RS485 communication data (–)
Input/output terminals for RS485 communication.
SD
Cable shield
Electrically floating
12.3 Serial Interface Configuration Drive function codes H30 to H39 are used to configure the serial interface parameters, such as device address, baud rate and error response.
12.4 Modbus RTU Functions The following RTU functions are supported. The maximum number of consecutive parameters for function 03 and 16 messages is 16. Code 03
Description Read Holding Registers (16 registers maximum)
06 16
Preset Single Register Preset Multiple Registers (16 registers maximum)
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
12-1
Page 138
12.5 Drive Function Code Access All of the drive function codes are accessible through the RS485 serial interface. Drive function codes are mapped to RTU holding registers. A drive function code RTU address is 2 bytes in length. The high byte corresponds to a code that represents the drive parameter sort (F–M). The low byte corresponds to the drive parameter number within the sort (0 99). Code
Sort
Name
Code
Sort
Name
0 1
F E
Basic function Terminal function
5 6
A o
Motor 2 function Option function
2 3
C P
Control function Motor 1 function
7 8
S M
Command/function data Monitor data
4
H
High level function
For example, drive function code M11, output current, is addressed as RTU parameter number 080B hexadecimal or 2059 decimal. high byte low byte drive parameter sort code drive parameter number 12.6 Command and Monitor Data Registers The command and monitor function codes are used to control the operation of the drive and monitor the status variables through the serial interface. The command and monitor function codes are not accessible from the drive keypad interface. Drive parameter H30 and digital input signal LE must be enabled to operate the drive from the Modbus interface. If LE is not assigned to a digital input (X1-X9), the signal will default to ON. Frequency Setting Registers Address Code 1793 S01
Name Frequency command
Unit -
1797
Frequency command
Hz
S05
Variable Range -20000–20000 (max. frequency at ± 20000) 0.00–400.00
Min. unit
Read/ Write
Data Format
1 0.01
R/W R/W
2 5
Note: 1) If both S01 and S05 are set, the drive will ignore the setting of S05. 2) A data setting that exceeds the setting range is possible, but the actual action will be limited by the drive configuration. Operation command data Registers Address Code
Name
1798 1799 1804
Operation command Universal Do Universal Ao
S06 S07 S12
Unit
Variable Range
-
Min. unit
Refer to the data format [14] Refer to the data format [15] -20000–20000 (100% output at ± 20000 )
1
Read/ Write R/W R/W R/W
Data Format 14 15 2
Note: 1) Since X1–X9 are configurable input commands, it is necessary to set the functions by E01–E09. 2) The alarm reset is executed, when RST signal changes from ON to OFF even if there are no alarms. 3) Universal Do is a function that utilizes the drive’s digital outputs via communication. Function data Registers Address Code
Name
Unit
Variable range
1800 1801 1802
S08 S09 S10 s s %
0.1–3600.0 0.1–3600.0 -20.00 –200.00, 999
1803
S11
Acceleration time F07 Deceleration time F08 Torque limit level 1 (driving) F40 Torque limit level 2 (braking) F41
%
0.00, 20.00–200.00, 999
Note: 1) 2)
Min. unit 0.1 0.1 1
Read/ Write R/W R/W R/W
Data Format 3 3 5
1
R/W
5
The writing of data out of range is treated as out of range error. Use a value of 7FFFH to enter 999 for torque limit functions.
12-2
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
Page 139
Monitoring parameter registers Address Code
Description
2049
M01
2053
M05
2054
M06
Frequency command (final command) Frequency command (final command) Actual frequency
2055 2056 2057 2058
M07 M08 M09 M10
2059
M11
2060 2061
M12 M13
2062 2063
M14 M15
2064 2065 2066 2067 2068
M16 M17 M18 M19 M20
2069 2071 2072 2073 2074
M21 M23 M24 M25 M26
2075
M27
2079
M31
2080
Unit Hz -
Range
Min. unit
- 20000–20000 (max. frequency at ± 20000) 0–400.00 - 20000–20000 (max. frequency at ± 20000) - 200.00–200.00 - 200.00–200.00 0.00–400.00 0.00–200.00
1
Read / Write R
Data Format 2
0.01
R
5
1
R
2
0.01 0.01 0.01 0.01
R R R R
6 6 5 5
0.01
R
5
1 -
R R
3 14
Actual torque value Torque current Output frequency Motor output (input electric power) Output current r. m. s.
% % Hz %
Output voltage r. m. s. Operation command (final command) Operating state Universal output terminal data Fault memory 0 Fault memory 1 Fault memory 2 Fault memory 3 Integrated operating time
V -
0.00–200.00 (inverter rating at 100.00) 0.0–600.0 Refer to data format [14]
-
Refer to data format [16] Refer to data format [15]
-
R R
16 15 h
Refer to data format [10]
-
R
0–65535
1
R
10 10 10 10 1
V -
0–1000 Refer to data format [17] Refer to data format [11] 0–64999 Refer to data format [20]
1 1 -
R R R R R
1 17 11 1 20
-
1
R
2
Hz
- 20000–20000 (max. frequency at ±20000 ) 0–400.00
0.01
R
5
M32
DC link voltage Type code Drive capacity code ROM version Transmission error processing code Frequency command at alarm (final command) Frequency command at alarm (final command) Actual frequency at alarm
-
- 20000–20000
1
R
2
2081 2082 2083
M33 M34 M35
Actual torque at alarm Torque current at alarm Output frequency at alarm
% % Hz
(max. frequency a t ± 20000) - 200.00 – 200.00 - 200.00 – 200.00 0.00 – 400.
0.01 0.01 0.01
R R R
6 6 5
2084
M36
%
0.00–200.00
0.01
R
5
2085
M37
%
R
5
M38
V
0.00 – 200.00 (inverter rating at 100.00) 0.0 – 600.0
0.01
2086
1
R
3
2087
M39
-
Refer to data format [14]
-
R
14
2088
M40
Motor output at alarm (input power) Output current r.m.s. at alarm Output voltage effective value at alarm Operation command at alarm Operating state at alarm
-
Refer to data format [16]
-
R
16
2089
M41
-
Refer to data format [15]
-
R
15
2090
M42 h
0–65535
1
R
1
2091
M43
Universal output terminal data at alarm Integrated operation time at alarm DC link voltage at alarm
V
0–1000
1
R
1
2092
M44
°C
0–120
1
R
1
2093
M45
Inverter internal air temp. at alarm Cooling fin temp. at alarm
°C
0–120
1
R
1
2094
M46
%
0.0–100.0
0.1
R
3
2095
M47 h
0–65535
1
R
1
2096
M48
Life of main circuit capacitor. Life of printed circuit board capacitor. Life of cooling fan.
h
0–65535
1
R
1
%
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA
12-3
Page 140
12.7 Data Format Specification All data in the data field of communication frame shall be represented by a 16 bit length word. 15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
16 bits binary data
Data format [1] Unsigned Integer data (Positive): Min. unit 1 Example If F15 (Frequency limit, upper)= 60Hz 60 = 003CH Data format [2] ] Example data = -20 -20 = FFECH
Integer data (Positive, negative): Min. unit 1
Data format [3] Unsigned Decimal data (Positive): Min. unit 0.1 Example: If F17 (frequency gain setting signal) = 100.0% 100.0 X 10 = 1000 = 03E8H Data format [4] Decimal data (Positive, negative): Min. unit 0.1 Example If: C31 (Analog input offset adjust, terminal12) = - 5.0% - 5.0 X 10= - 50 = FFCEH Data format [5] Unsigned Decimal data (Positive): Min. unit 0.01 Example: If C05 (multi-step frequency 1) = 50.25Hz 50.25 X 100 = 5025 = 13A1H Data format [6] Decimal data (Positive, negative): Min. unit 0.01 Example: If M07 (actual torque value)= - 85.38% - 85.38 X 100= - 8538=DEA6H Data format [7] Unsigned Decimal data (Positive): Min. unit 0.001 Example: If o05 (follow - up side ASR 1 constant) = 0.105s 0.105 X 1000 = 105 = 0069H Data format [8] Decimal data (Positive, negative): Min. unit 0.001 Example: Data = -1.234 - 1.234 X 1000 = - 1234 = FB2EH Data format [9] Unsigned Integer data (Positive): Min. unit 2 Example If P01 (Motor 1 number of poles) =2pole 2 = 0002H Data format [10]
Alarm Code
12-4
Data subject to change without notice 9/00. © 2000 GE Fuji Drives USA