Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 24 of 35

Series One Programmable Controllers, Series One/One Plus User's Manual: Chapter 6 I/O Specifications and Wiring, pages 215 to 224

Pages 215 to 224 of 300, from Series One Programmable Controllers, Series One/One Plus User's Manual

The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the GE Fanuc IC610CPU105A, GE Fanuc IC610CPU105C, Fanuc IC610CPU105A, GE IC610CPU105A, Fanuc IC610CPU105C and GE IC610CPU105C

Page 215

I/O Specifications and Wiring

643

GEK-90842

Ouptut Logic Each of the two HSC outputs operate in either the manual or counter mode. The operating mode of each output is determined by the state of its mode select function (refer to output function section). The logic of each mode will be covered separately. If Mode Select Function

Disabled (0): Manual Mode, Enabled (1): Counter Mode.

Manual Mode The state of an output in the manual mode corresponds to the status of its associated Function as shown below in the manual mode output truth table.

Output State

Table 6-6. Manual Mode Output Logic Truth Table

I

OUTPUT MODE SELECT

I

0 0

OUTPUT STATE

I

0 1

OUTPUT

I

0 1 l

Counter Mode In the counter mode of operation outputs can react immediately when the current count reaches specific preset values. In this mode each output is controlled by a combination of three ‘factors. 1. Initial relationship between preset and current count.

2. Real time relationship between preset and current count.

3. Status of Output State function. When the HSC receives a preset value from user logic (via preset counter function), it is initially compared to the current value of the counter. If the preset is-greater than the current count in this initial comparison the real time comparison *2between the preset and current count is “true” when the current count is greater than or equal to the preset. In other words when the current count reaches the preset moving in the POSITIVE direction the real time comparison becomes “true”. This concept is shown below in table 6.7.

Table 6-7. Real Time Comparison Table for Preset Initially > Current Count

/ REAL TIME COMPARISON STATUS

CURRENT COUNT < PRESET

CURRENT COUNT -> PRESET

FALSE

TRUE

*Real Time compariston = continuous comparison between preset value and cummt value of cutmter.

1

Page 216

6-54

I/O Specifkations and Wiring GEK-90842

Conversely, if the preset is kGtially less than the current count, the real time comparison is “true” when the current count is less than or equal to the preset. In other words, when the current count reaches the preset moving in the negative direction the real time comparison becomes “true”. This concept is shown below in table 6.8.

Table 6-8. Real Time Comparison Table for Preset Initially c Current Count

I REAL TIME COMPARISON STATUS

I

CURRENTCOUNT > PRESET

I

CURRENT COUNT < PRESET

I

I

FALSE

I

TRUE

I

Once the status of the real time comparison between the preset and current count has been determined, the status of the output is easily obtained. If the outputs associated output state function is disabled its status corresponds directly to the real time comparison status. If the output state function is enabled the output’s status is the inverse of the real time comparison status. This concept is shown in table 6.9.

Table 6.9. Output State vs Real Time Comparison Status in Counter Mode OUTPUT STATE FUNCTION

I I

DISABLED ENABLED

1: OUTPUT ENABLED 0: OUTPUT DISABLED

Table 6.10 summarizes

I

I I

REAL TIME COMPARISON IS FALSE 0 1

REAL TIME COMPARISON ISTRUE

I

1 0

-

I the logic associated with an output in the counter mode of operation.

I

I I

Page 217

Ii0 Specifications and Wiring

6-55

GEK-90842

Table 640. Output Logic in Counter Mode INITMLLY PRESET > CURREW OUTPUT STATE FUNCTION

0 1

COUNT cuRRENTcOuNT < PRESET

0

CURRENT COUNT > PRESET 1

1

0

INITMLLY PRESET < CURRENT COUNT OUTFWT STATE FUNCTION 0 1 cuRRENTcOuNT > PRESET 0 1

CURRENT COUNT < PRESET 1 0

Filter Selection In some electrical noisy environments it may be necessary to filter out noise through filters available on the module. The HSC provides this capability on the incremental count, decremental count, and reset/inarker inputs. The location of these switches on the module is shown in figure 6.53. Sense of switch: OPEN - Filter Disabled (< 10 Khz) CLOSED - Filter Enabled (C 500 Hz)

Figure 643. Filter Selection with Dip Switch

Page 218

II0 Specifications and Wiring

646

GEK-90842

Fast Response I/O IC610MDL115 The Fast Response I/o module allows a Series One or Series One Plus PC to respond quickly to an input and/or monitor very short input pulses. The module’s four 24 V dc inputs and two relay outputs use 8 I/O references to interface with user logic. Each of the 2 outputs can operate in a manual or fast response mode. An output in manual mode is controlled from user logic similar to any other discrete output. An output in the fast response mode can be controlled independent of CPU scan time by its 2 associated inputs, with one input enabling it, and the other disabhg it. Up to 14 Fast Response I/O modules can be included in a Series One or Series One Plus PC system, thereby providing 28 fast response outputs and 56 inputs total. Following are specifications for each of the input and output circuits.

r

DC INPUT CIRCUITS Number of Circuits Maximum Voltage (Open Circuit) Input current ON Level OFF Level OFF to ON Response ON to OFF Response Maximum OFF Cment Minimum ON Current Input Pulse Width Chait Indicator

4

36 V dc 16 mA (maximum) 0-3Vdc 18 - 36 V dc 0.3 to 1 ms 50 to 150 ms 3mA 7mA 1 ms (minimum) Field Side

NOTE

Input Switching Voltage Provided by Module r

RELAY OUTPUT CIRCUITS Number of Circub Operating Voltage

2 S-265 V ac/dc

AC F’reqwncy

47-63 Hz 4 amp (esistive) 0.5 amp (inductive) 1mA 10 mA

Range lkhuimum C-t* Maximum Leakage Current Smahst Recommended Load Maximum Inrush OFF To ON Response ON To OFF Response Ciralit Indicator Ciralit Indicator Fbse (In Output Common Line) Wernal Power Consumption

5ms 5 ms (hum) 5 to 10 ms Field Side Field Side 3 mP 5OmA+53mA/OutputONChuitat9Vdc, lS~ut@24Vdc Units of Load: 16 (9 V dc) 6 (2A V dc)

Since non-solid state relays are used as the power switching devices, the limitations as shown in table below must be observed for reliable operation.

Page 219

I/O Specifications and Wiring

647

Table 641, Maximum Current vs. Load Type for Relay Outputs OPERATING VOLTAGE

MAXIMUM

I

RESISTIVE

22ovac 22ovac 1lOVac 11ovac 24 V dc 50 V de 1OOVdc 250 V dc

4bP 4bP 5bP 1hP

0.5 Amp 0.3 Amp

CURRENT FOR LOAD TYPE LAMP

0.5 Amp 0.05 Amp

0.5 Amp 0.1 Amp 0.5 Amp 0.1 Amp 0.05 Amp 0.03 Amp

1

TYPICAL

LIFE

SOLENOID

(OPERATIONS)

0.5 Amp 0.05 Amp OJ Amp 0.1 Amp 0.5 Amp 0.1 Amp 0.05 Amp 0.03 Amp

100,ooo 800,000 150400 650,000 100,ooo

100,000 100,ooo 100,ooo

NOTE Lamp loads are defined as a X10 inrush with a power factor (PF) of 1.00 and when tumed OFF represent a PF of 1.00. Solenoids are defined with a X10 inrush, a PF of 0.65, and when turned OFF represent a PF of 0.35. b40556

Figure 6-54.

Module Reference NUMBER/LOGIC Symbol Definition

Page 220

6-58

I/O Specifications and Wiring GEK-90842

Mode Selection The Operating Mode Selection of outputs X4 and X6 is determined references SS and S7 as shown in table 6.12.

by the status of their mode select

Table 6-12. Operating Mode Selection

I

MODE SELECT

OUTPUT

I

(SS and S7) Disabled (0) Enabled (1)

I w=dx6) Manual Mode Fast Response Mode

Output Logic - Manual Mode An output operating in the manual mode is controlled through user logic similar to any other discrete output. Its associated inputs on the fast response module do not affect it any way.

Output Logic - Fast Response Mode In the fast response output.

mode of operation, a combination of three factors determines

State of Associated

Enable Input (Reference number 0 or 2)

State of Associated l User Logic

Disable Input (Reference number 1 or 3)

l l

The truth table (following) and disable inputs.

shows how the output can be controlled the status of the from user logic or with its enable

Table 643. Truth Table for Output in Fast Response Mode (S5 or S7 Have Been Enabled) ENABLE INPUT No. 0 or 2

DISABLE INPUT No. 1 or 3

USER LOGIC X4 or X6

OUTPUT

1 0 1 1 1 0 0

0 0 0 1 1 1 0

0 1 1 1 0 0 0

1 1 1 0 0 0 0

0: Disabled

1: Enabled

It can be seen from the first three rows in the truth table that the output can be enabled from its enable input or from user logic. The last four rows of this truth table show the various conditions that disable the outputs.

The logic diagram shown below in figure 6.55 summarizes the operation of this module.

Page 221

I/O Specifications and Wiring GEK-90842 a40547

CPU s&e (UserLogic)

Fast Response Moduk fidd Side

Input No. 0 4

1 LnQutNo.0 hputNo.1

)

( hputNo.1 b Output No. 4 Output No. 4 o(4) c wect Output No. 4 IS51 ’ hput No. 2 (I-

3 input No. 2

Input No. 3 (3-

3 Input No. 3 _

> OutputNo. Output No. 6 DC61 SeIect Output No. 6 @‘I)

Figure 645. Fast Response Module Logic Diagram

Page 222

6-60

I/O Specifications and Wiring G=-90842

USER WIRING INPUTS

USER MODULE

WIRING

OUTPUTS c4

USER

WIRING

DIAGRAM

24 VDC

COMMON r ___________~____+~’

I I I I I I I I I L - ,d:P=

5 255 VAC DC

A

6

=

$

*

TO OTHER m THREE CIRCUITS

INTERNAL POWER SUPPLY

INPUT H(-he w -

A

A v w

LOAD

.> 5-265

I

RELAY

SAMPLE OUTPUT

3A

CIRCUIT

Figure 6-56. Wiring for Fast Response I/O Module

VAC’DC

Page 223

6-61

II0 Specifications and Wiring GEL90842

I/O Simulator IC6lOMDL124 The I/O simulator module has 8 two-position

(ON or OFF) switches, each having an associated LED, that is, if switch 1 is turned ON, LED 1 will light. An I/O simulator module uses one I/O slot and the 8 I/O references assigned to that slot. Each of the switches can be programmed as a discrete input device. This module requires no field connections since its function is controlled by programming. An I/O simulator module is a valuable tool in program development and troubleshooting. An I/O simulator could also be programmed to be used as conditional input contacts for control of output devices. Specifications for this module are as follows: 4 to 15 ms 4 to 15 ms lOmA@ 9Vdc 14mA/CircuitON@24Vdc lunit@9Vdc llunits@24Vdc 3.2 oz (90 g)

ON to OFF Response OFF to ON Response Interndl Power Consumption unitsof Load Weight a40215 1

I

,

I ,

I/O SIMULATOR

Figure 647. I/O Simulator Module Faceplate

Page 224

I/O Specifications and Wiring

6-62

GEK-90842 -.

Analog Input IC610MDLll6

Introduction The Analog Input module provides four independent input channels capable of converting an analog input signal to a digital signal for processing by the programmable controller. This module can be used with Series One and Series One Plus programmable controllers. However, the input can only be provided in binary form with a Series One PC. ‘Ihe Series One Plus, in addition to the basic functions, provides data operations (including math functions), which allows other types of operations to be performed when using the analog input module. Each Analog Input module requires 16 I/O references for addressing.

Hardware Features The user can select, by jumper placement, to use either voltage inputs (1 to 5 V dc) or current inputs (4 to 20 mA>. The factory setting is for voltage input operation. Resolution is 8 bits, which allows a maximum digital value of 255 to be converted. Eight LEDs on the faceplate provide an 8-bit binary display of the input. The channel to be displayed is selected by depressing a pushbutton on the faceplate. Each time the pushbutton is depressed, the next channel in sequence is selected, i.e., channel 1, 2, 3, 4, 1, etc. User field wiring is made to a removable terminal board on the module’s faceplate. A hinged plastic temG.nal cover on the terminal board protects the terminals. The terminal cover has a removable label that can be used to record circuit information. The maximum conversion time is 2 milliseconds and does not add to the scan time of the CPU. The four channels are converted one at a time, with one channel being converted each scan. Each successive scan converts the next channel in turn.

Power Requirements This module requires an external 24 V dc power supply. The 24 V dc supply in Series One racks can be used, however the current provided by the rack is limited to 100 mA, which is sufficient current for one Analog Input module, sin& the module requires up to 65 m4 for operation.

General and Electrical Specifications SpecifGzations for this module are provided in the following table.