Page 225

I/O Specifications and Wiring

6-63

GE&90842

Table 6-14. Analog Input Module Specifications Number of cJhanmls Input Ranges

4 (Independent)

Resolution Digital outputs I/O Points Required

LEVI Display (16 LEDs)

Operating Temperature Relative Humidity @Jut Types Input Impedance

Conversion Method Conversion Time Linearity Error AmY Accuracy vs. Temperature External Power Source 9 V dc Power Consumption

+l to +5 v dc or 4 to 20 mA (jumper selectable for each channel) &bit binary (1 in 256) 8 bits, binary data output 4 bits, cbannel status 16 consecutive (per slot assignments for 16 points, 0 to 7 and 100 to 117, etc.) 8 bits: Data being read into the selected channel 4 bits: Channel selected for Data Display 4 bits: Channels being scanned 0 to 60’ C (32 to 140’ I?) 5% to 95% (non-condensing) Differential > 1 MSZ (Voltage put) 250 Sz (Current put) Voltage Input, 0 to +lO V dc Current Input, 0 to 30 mA Successive Approximation Method 2 msec, maximum fo.8%, maximum 21% at 25’ C, maximum i50 ppm (parts per million) per l°C +25 V dc, 65 mA (maximum) 55 mA (Supplied by rack power supply)

I/O Reference Definitions The Analog Input module uses 16 consecutiveI/O points, beginning with the first I/O reference assigned to the I/O slot selected for the module. In the table, it is assumed that the Analog Input module is placed in slot 3 of a properly configured 5 or lO-slot CPU rack (references 10 to 17 and 110 to 117). These references are used for the example only, other valid references for I/O slots that allow 16 references can be used. The following table defines the use of each of the I/O points.

Table 6-15. I/O Point Definition I/O POINT

DEFINITION

WEIGHT

I/O TYPE

10 11 12 13 14 15 16 17 110

Data Bit - Binary Data Bit - Binary Data Bit - Binary Data Bit - Binary Data Bit - Binary Data Bit - Binary Data Bit - Binary Data Bit - Binary Channel 1 ‘Ibis bit is used in ladder logic to sense whenthedatarezeivedattheinputsisforthis channel. Channel 2 sense bit -1 3 Sense bit

1 2 4 8 16 32 64 128

Input Input Input Input Input Input Input Input Input

111 112

Input Wut

Page 226

I/O Specifkations and Wiring

644

GEK-90842

Table 645. I/O Point Definition - Continued I/O POINT

DEFINITION

WEIGHT

113 114 115

Channel 4 Sense bit This output combined with the following output can be set to selectively scan only 1 channel, instead of all 4. These outputs are ignored if the scan selection output is on. The desired channel is selected by settingthesetwooutputsinthel~logictothe state, as shown below, for that channel.

OUTPUT 114 0

OUTPUT 115 0

1

0

0 1

1 1

116 117

Not used Scan selection output. This bit must be set for the module to n5ad data input, unless the selected channel scan outputs anz used. This output is set in the ladder logic program

I/O TYPE Input output -put

1

2 3 4 output

Sample Ladder Logic Sample ladder diagrams are provided below using the same I/O referencing as is used in defking the I/O points in Table 6.15 on the previous page. These are examples of programming the Series One Plus.

Example 1. If all channels are to be scanned, output 117 must be on.

I

117

SW1

+ -m-- 1 I ~~-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

( s )--+

117 E~~~~~~~~~~~~~~~~~~~~~

(

R

)

--&

I

SW1 and SW2 are switches user

Page 227

I/O Specifications and Wiring

6-65

GEK-90842

Example 2. This example of ladder logic allows you to select the channel to be scanned. 1 CH

2 SELECT

114

&___]

I

CH 4 SELECT + ---1 1 ----I)--

CH 3 SELECT + ---1

+

111-w

+ w--w

115

CH 4 SELECT 1 1 -----1-

SW2

+ ----

I

[ ~~--~~~~~~-~~

I

1~-~~~~---~~~~~~~-~~~[

+ ----[

F51 R# 1

]-------+

F60 R# 500]-------+

Retrieve data and convert to BCD

Store channel 1 data in registers 500 and 501

111 + w---

+

--I)-

+

-m-w

I

[ ~~~~---------~~~~~~~[

112 -~~~~~~~---~-~~~~~~~[ I [ g-60

R#

5()2]---_---

Store channel 2 data in registers 502 and 503

F60 R# 5041.-0-0-0 +

Store channel 3 data in registers 504 and 505

~'60 R# 50610-0---9+

Store channel 4 data in registers 506 and 507

113

I

[ ~~--~~----~---~~~-~~[

The Function codes used in the above example are as follows: F51 = D STRl (Data Store l), F86 = BIN to BCD, F60 = D OUT (Data Out)

Page 228

I/O Specifications and Wiring

6-66

GEK-90842

Analog Input Module Features Figure 6.58 is an illustration of the faceplate for the Analog Input module, showing its features and user wiring CoMections.

a41 896

CHANNELS BEINGSCANNEDALL DIM, IF ALLSCANNED

1

DATABEINGREAD IN ON SELECTED CHANNEL

CHANNELSELECTED FOR DATADISPLAY BY DEPRESSING PUSHBUTTON

1

31 31 I4164

FOR -DATADISPLAY &

+

CHANNEL I INPUT

+24V ov

EXTERNAL SUPPLY

Figure 648. Analog Input Module Faceplate Sekction Of Operating Mode The mode of operation, either 1 to 5 V or 4 to 20 IYA is determined by the absence or presence of jumper plugs on pins that are located on the side of the bottom circuit board. There are four sets of pins (2 pins in each set), with one set for each channel. The first set of pins is labeled CHl and the last set of pins is labeled CH4. The factory default setting is for 1 to 5 V operation, which is no jumper present. TO select the 4 to 20 mA mode of operation for any channel, place a jumper on the two pins for the channel or channels and push the jumper fkmly onto the pins.

Page 229

I/O Specifications and Wiring

6-67

GEL90842

Analog Output IC610MDL166 Introduction The Analog Output module provides two independent output channels, each capable of converting 8 bits of binary data to an analog output. ‘This module can be used with any of the Series One family of programmable controllers. The Series One Plus, in addition to the basic functions, provides data operations (including math functions), which allows other types of operations to be performed when using the analog output module. Each Analog Output module requires 16 YO references for addressing. Although this module can be used with the Series One and Series One Junior, in addition to the Series One Plus, certain programmin g techniques will make better use of the capabilities of the Analog Output module with these PCs. An APPLICATION NOTE will be issued explaining those techniques in detail.

Hardware Features Each channel can provide either a voltage output (0 to +lO V dc) or current output (4 to 20 r&4 source). Voltage or current selection for each channel is user selected by how the field wiring is connected on the scow terminals on the faceplate. Resolution is 8 bits, which allows a maximum digital value of 255 to be converted. Eight LEDs for each channel on the faceplate provide an 8-bit binary display of the data output for each channel. User field wiring is made to a removable terminal board on the module’s faceplate. A hinged plastic terminal cover on the terminal board protects the terminals. The terminal cover has a removable label that can be used to record circuit information. The maximum conversion time is 10 microseconds channels are converted with each scan.

and does not add to the scan time of the CPU. Both

Power Requirements This module requires an external 24 V dc power supply. The 24 V dc supply in Series One racks can be used, however the current provided by the rack is 100 mA, which is sufficient current for one Analog Output channel, since the module requires up to 85 mA for operation. The maximum load for both channels is 170 m4.

General and Electrical Specifications Specifications for this module are provided in the following table.

Page 230

6-68

II0 Specifications and Wiring GEL90842

Table 6-16. Analog Output Module Number of Channels Analog Output Ranges Resolution Digital Input Data I/O Points Required

. .

LED Display (16 LEDs) 8 LEDs for each channel Operating Temperature Relative Humidity Output Impedance Output Current External Resistor Conversion Start Conversion Time Accuracy Accuracy vs. Temperature External Power Source 9 V dc Power Consumption

I/O Reference

Specifications

2 (Independent) . 0 to +lO V dc or 4 to 20 mA (selectable for each channel on faceplate terminals) &bit binary (1 in 256) 8 bits, binary from the CPU 16 consecutive (per slot assignments for 16 points, 0 to 7 and 100 to 117, etc.) 8-bit binary data display of output data for each channel

0 to 60’ C (32 to 140’ F’) 5% to 95% (non-condensing) < 0.5L (Voltage Output) 10 mA, maximum (Voltage Output) 55OL, maximum (Current Output) At start of CPU’s scan 10 msec, maximum 0.2% at 25OC 30 ppm (parts per million) per l°C +24 V dc, 85 mA (maximum) 55 mA (Supplied by rack power supply)

Definitions

The Analog Output module uses 16 consecutive I/O points, beginning with the first I/O reference assigned to the I/O slot selected for the module. In the table, it is assumed that the Analog Output module is placed in slot 2 of a properly configured 5 or lO-slot CPU rack (references 0 to 10 and 100 to 110). These references are used for the example only, other valid references for II0 slots Jhatallow 16 references can be used.The following table defines the use of each of the I/O points. Table 6-17. I/O Point Definition I/O POINT CHANNEL 0

1 2 3 4 5 6 7 100 101 102 , 103 104 105 106 107

DEFINITION DATA

Channel 1 - Data Bit 1 Channel 1 - Data Bit 2 Channel 1 - Data Bit 3 Channel l- Data Bit 4 Channel 1 - Data Bit 5 Channel 1- Data Bit 6 Channel 1- Data Bit 7 Channel 1 - Data Bit 8 Channel 2- Data Bit 1 Channel 2 - Data Bit 2 Channel 2 - Data Bit 3 Channel 2- Data Bit 4 Channel 2- Data Bit 5 Channel 2- Data Bit 6 Channel 2 - Data Bit 7 Channel 2- Data Bit 8

L/O TYPE WEIGHT

1 2 4 8 16 32 64 128 1 2 4 8 16 32 64 128 output output output output output output output output output output output output output output output output

Page 231

6-69

I/O Specifications and Wiring GE&90842

Sample Ladder Logic A sample ladder diagram is provided below showing a method of how to move output data to Channels 1 and 2. This is an example of programming the Series One Plus for using the Analog Output module.

Example.

Move output data to Channels 1 and 2, using the same I/O references as are used in previous table; i.e., 0 to 7 for Channel 1 and 100 to 107 for Channel 2.

SW1 SW2 + --w-1 [----I/[-w---w

SW1 + m--w IO ---I,

----a-[

F50 R# 500]-------+

1 -------

------

1 F85

-----[

F61

----111[

~50 R# 502]-------+

R#

0

+

]-------+

SW2

1 111-----

-----[

F61

R#

10

I-------

The Function codes used in the above example are as follows: F50 = D STR (Data Store) F85 = BCD to BIN F61 = D OUT1 (Data Out 1)

Move data from registers 500/501 to the accumulator then Convert data from BDC to Binary and Send the data to Channel 1

Move data from registers 502/503 to the accumulator then Convert data from BCD to Binary and Send the data to Channel 2

-

Page 232

6-70

I/O Specifications and Wiring GEK-90842

Analog Output Module Features Figure 6.59 is an illustration user wiring connections.

of the faceplate for the Analog Output module, a41 897

CHANNEL I DISPLAY OF DATAOUTPUT

CHANNEL I 4T0 20MA OUTPUT

OR

CHANNEL I 0 TO +lOV OUTPUT

CONNECTIONSON MODULE,ONLY ONEREQUIRED

SUPPLY

Figure 6-59. Analog Output Module Faceplate showing its features and

Page 233

I/O Specifications and Wiring

6-71

GE&90842

UL Listed Products The Series One products that have obtained UL approval or are UL pending are described in the following pages. These products are listed below. As with all products that have obtained UL approval, each listed item has an attached UL label. l

IC61OCPUlOl Series One CPU. Version C of the CPU is UL Listed. The functionality has not changed, all specifications are the same as the previous version.

l

IC61OCHSlll

Series One S-slot rack.

l

IC61OMDL135

Series One 115 V ac Input module,

IC61OMDLl81 l IC61OMDLl85 l of the CPU

115 V ac source of input power required. 6 circuits.

Series One Relay Output module, 5 circuits. Series One 115 V ac Output module, 6 circuits.

The following pages contain the technical specifications the Series One UL listed products.

and wiring information required to implement

Page 234

II0 Specifications and Wiring

6-72

GEK-90842

5-Slot Rack, UL Listed IC610CHSlll The 5-slot UL Listed rack is similar to the existing 5-slot rack, IC610CHS110, in that it has a power supply to the right and slots to contain up to 5 modules. The power supply for this UL rack requires an input power source of 115 V ac. This rack does not accept 230 V ac input. As with existing S-slot rack, a terminal board is provided for field wiring connections, refer to the following figure. The two top terminals a for the 115 V ac HOT (H) and NEUTRAL (N) connections. The next two terminals are for connecting an external device to the RUN relay, the next two contacts (+ and -) provide a 24 V dc output voltage at 100 mA for connection to an external sensor, and the bottom terminal is the common (C) connection to an expansion rack. When used as the first rack in an installation, it must contain the CPU which is placed in the slot next to the power supply. The rack can also be used as the second or third rack in a system if more I/O is required than can be contained in the first rack. A two-position switch on the inside, left of the rack, must be set detetied by location of the rack in the system. For a UL approved installation, do not mix UL approved and non UL racks or modules. Specifications for this rack are as follows: AC power Requeucy:

Required:

Maximum Load: output current:

115vac, 15% 47 to 63 Hz 0.8 A, max. 1.4 A, at 5 V dc 0.8 A, at 9 V dc 0.5 A, at 24 V dc b41930

Figure 6-60, UL Listed SISlot Rack