Series One Programmable Controllers, Series One/One Plus User's Manual: Chapter 4 PC Operation, pages 67 to 74
Pages 67 to 74 of 300, from Series One Programmable Controllers, Series One/One Plus User's Manual
The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE Fanuc IC610CPU105A, GE Fanuc IC610CPU105C, Fanuc IC610CPU105A, GE IC610CPU105A, Fanuc IC610CPU105C and GE IC610CPU105C
Page 67
49I
PC Operation GE&90842 with other keys. The programmer is an excellent tool for program entering, editing and monitoring. Table 4-2 lists the various operations, the keystrokes required to enter those operations, and the mode or modes in which the operation can be performed. Each of the modes is indicated by a letter, R (RUN), P (PROGRAM), or L (LOAD).
Table 4-2. PC Operation Sequences MODE Keystrokes or Operation Sequence
OpWt.i0n bsert or Remove Key
R
P
X
Clear all user memory
CLR SHF 3 4 8 DEL N-XI’
Display present address
CLR
Display present function
X X
X
X
X
X
Next function
NXT(After previous keystroke)
X
X previous function
PRV
X
X
Go to address 0000 in progxam memory
SHF Nxr
X
X
Go to specific address
SHF (&dress)
X
X
Go to next address
After previous entry NXI’ x x
* x
X
X
X x x
NXT clear displayed function Search for a specific function
(Function)
Search for a specific reference number
SHF (Ref. No.) SCH NXT
Insert function before the displayed function (or address)
(Function)
cancel insert
CLRSHF INS
X
Delete a function
(address) DEL PRV
X
Check program for errors. If no error detected, the next available address is displayed.
CLR SCH
X
Turn Timer/Counter ON Turn Timer/Counter OFF
TMR or CNT SHF 6XX SET TMR or CNT SHF 6xX RST x .
Change preset value of a Timer or Counter SHF (p-t
SHF (Ref. No.) SCH NXT
X
SHF (Ref. No.) INS NXT value) ENT
X
Monitor ON/OFF mtus of a ~~QIQof 16 ‘SHF (Beginning Ref. No.) MON consecutive Iefen33ces (VO, intemal coils, Shift Register coils
X
Monitor Timer or Counter accumulated value
SHF (T/C No.) MON To monitor the previous or next T/C enter, PRV or NXT
X
Monitor ON/OFF state of any coil or contact
TheONOFFr-EDtumsONorOFFtoindicatetbestate of the displayed Rfmnce.
X
SET SHF (Ref. No.) ENT Refizrence can be Input, Output$hift Register, Timer or Counter
X by user logic)
v Force a mfezence ON (will be ovetiti
L
X
Page 68
4-10
PC Operation GEK-90842
Table 4-2.PC Operation Sequences - Continued
Keystrokes or Operation Sequence
OptXation
Force a reference OFF (will be overridden RST SHF (Ref. No.) ENT by user logic) I Enter a fhnction into program memory I (Function) SHF (Ref. No.) ElNT
I
1x1
Editaprogram
I Same as above. Select address and enter change
I
1x1
Transfer data to tape
( tionalpqram lop
ID) SHF WRITE
(OptionalpIogram
ID) SHF CHECK *
Load program memory from tape Verify data on tape or in PROM writer RAM against program memory
~~
( tionalprogram ID) SHF READ lop I
I
I
Ix
1 1 -12
I I I
SERIES ONE PLUS ONiY Monitor contents of Data Registers (1) Monitor text register Monitor previous register Enter or change the contents of displayed register. A 4 digit BCD value can be entered (Wbits). Enter or change a password (2) (3) Log in sequence (3) Log out sequence (3)
IR (Register Ref) SHF
MON l=T IN=
IxxxxE?NTNxr ICLR SHF
9876
DEL
SHF 5678 DEL (Password) ENT NXT
SHF
SHF
T CLR SHF 1234 DEL NXT x
1
I
1x1 1x1
SHF XxXx ENT When the data contents are displayed, this sequence will overwrite the current contents of the register CLR
1x1
X
I I x xI xI I I I
I
X
X lxlxl
1. When the MON key is selected, the ADDRESS DATA display shows the address of the specified register. To display the data contents of the register, depress the MON key again. 2. 9876 is a f&d sequence. The password (XXXX) can be any numerical value between 0001 and 9999. The value 0000 is equivalent to no password. All programmer functions are operable when the password is 0000.
3. Password information also applies to the Series One Model E PC. The above table provides a convenient reference to the programmer keystrokes required for the various PC operations. A more detailed description of each operation is provided on the following pages or in Chapter 5, Programming. Monitor CPU Logic - This sequence of operation provides the steps required in order to observe the contents of user memory. You can either step forward or backward in user memory. With the Programmer installed and the mode switch in the Run or PRG (Program) position, observe or perform the following actions: 1. The programmer will display address zero indicated by four zero digits in the display with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Depress the NXI’ key, the logic content of memory location zero will be shown (beginning of memory or scan).
Page 69
PC Operation
4-11
GEK-90842
3 . Successive depressions of the NXT key will cause the programmer to step through the stored program in the order that the program is scanned, from address O.O.O.O.to the last address in the program. At any time, the CLR key can be depressed to display the address of the logic then being viewed. 4 . An additional depression of the NX’ key will restore the display to the logic content. 5 . At any time, depressing PRV will cause the logic of the previous (closer to zero) memory location to be displayed. 6 . Successive depressions of PRV will cause the programmer to step backwards through the stored program in reverse of the order that the program is scanned. At location O.O.O.O.,PRV has no effect. 7 . If by successive depressions of NXT, the end of the actual program is passed, the display will show End. With each successive selection (with the NXI’ or PRV keys) of an unprogrammed or empty memory word, the address of the new location will flash in the display for l/4 to l/3 of a second prior to going to End.
Search CPU Logic - In the event that you wish to quickly fkd a particular logic element (programming step) in user memory, this sequence of operation allows you to do so. After installing the programmer, with the mode switch in the RUN or PRG position, observe or perform the following actions: 1 . The programmer will display address zero indicated by four zero digits in the display, decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Enter the logic function whose location is to be searched for. For example, select AND, SHF, 1, 0, 5 (AND 105). Do not select ENT key. 3 . Select the SCH key to begin the search. If the logic function is not found, error code E99 will be displayed. 4 . If a match is found, the display will indicate the first memory address containing the desired function. Depressing NXT will cause the logic at that address to be displayed. 5 . Successive depression of SCH, while the memory address is being displayed, will cause additional searches to occur from the current location. 6 . As long as one match is found, the search will not stop at the end of memory, but will continue with memory address zero until a match (possibly the same location) is again detected. 7 . To find the first empty memory word, depress CLR to obtain an address location. Then select SCH (search for zero content) to begin the search for the first available location.
Alter One Logic Element - This sequence of operation allows you to change the contents of a particular bcation in user memory. After installing the programmer, Observe or perform the following actions:
place the mode switch in the PRG position.
1. The programmer will display address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Move the display to the element to be altered using the NXT or PRV key or Search function. 3 . Enter the new logic element, for example: OR, SHF, 2, and 5 (OR 25). 4 . Select the Enter (ENT) key to cause the change to occur. The new logic element you have entered will take the place of the previous logic at that memory location. The next address will be automatically displayed. 5 . If the new element is not to be entered or an error has been made in its constiction, depressing the Clear (CLR) key will cancel the new logic and return the display to the address of the examined element.
Page 70
4-12
PC Operation GEK-90842
Delete One Logic Element - This sequence of operation allows you to remove one logic element from the program position. A in user memory.
After installing the programmer, place the mode switch in the PRG
Observe or perform the following actions:
1. The programmer will display address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Move the display to the element to be deleted using the NXT or PRV key or the Search function. 3 . Select the DEL key. Notice that the Address/Data display has a small “d” in the left digit of the display. 4 . To confirm that the Delete operation is to be executed, select the PRV key. The next address will be displayed after the Delete is performed. The remaining user logic will automatically move back one address location (nearer to 0.0.0.0.) to fill the empty memory. 5 . To cancel the Delete operation, select the CLR key (before selecting DEL). The display will revert to the element being considered for deletion.
Clear All Memory - This programmin g sequence should only be used when the entire contents of logic memory m to be cleared. After installing the programmer, place the mode switch in the PRG position. Observe or perform the following actions:
1. The programmer will display address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Select the key sequence CLR, SHF, 3,4, 8. 3 . Select the DEL key; the display will change to. 4 . To execute the clear function and cause all logic elements to be removed from user memory, depress the NXT key. 5 . To cancel the clear function, the CLR key can be depressed before depressing NX?. ‘1 insert One Logic Element - This sequence of operation allows you to insert one logic element between two existing program steps in the use program. After installing the programmer, place the mode switch in the Program position. Observe or perform the following actions:
1. The programmer will display address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Move the display to the element that will be after the location at which the new element is to be entered. This can be done by using the NXT or PRV key or the Search function. 3 . Enter the new logic element, for example; AND, SHF, 1, 0, and 4 (AND 104). 4 . Select the Insert (INS) key to cause the change to occur. Notice that the address display has a small “i” in the left digit of the display. 5 . A con-g keystroke is required to ensure that the insert action by the operator is valid. To co&m the insert, select the NXT key. After the insert is performed, the display will show the address of the next logic element.
Monitor r/O Status - This operation sequence allows you to monitor the status (ON or OFF) of references. A total of 16 I/O references can be monitored at any one time, beginning with the lowest address in the group with the reference selected by the operator. Each reference is within a group of 8 references. The I/O status of the group containing the selected reference, plus the next higher group of 8, is displayed. After installing the programmer, place the mode switch in the RUN position. Observe or perform the following actions: 1. The programmer will display the address zero indicated by four zero digits in the display, with decimal poims iu the right of each digit (O.O.O.O.),and the ADR LED lit. 2. Enter any reference to be .monitored. For example, to monitor the real time status of references 020~027, or any one reference within that group, the following keys can be selected: SHF, 2 and 0.
Page 71
PC Operation
4-13
GEK-90842
3. Select the Monitor function (MON). Note that the shift is still in effect (selected in previous step)
causing the RST key to select the monitor function. 4. The display will revert to 1-3 followed by the lowest reference (e.g. 020) in that group. The I/O references can be for a 4,8, or 16 point module. If the module is a 4-point module, the status of the first 4 I/O points are real world outputs and their operating s-s will be displayed. The 4 higher references cannot be used as real world outputs, but can be assigned to internal coils. The 4 monitor LEDs normally assigned to the 4 higher references in this group will always be OFF. The status of an 8 point module (for example, 030 to 037) is indicated by the first 8 LED’s (AND, OR, STR, .. .. SR) and the next module’s status, if an 8 point (for example, 040-047) will be indicated by the last 8 LEDs (MCS, MCR, SHF....7). In the case of a 16,point module, the status of all 16 points will be consecutively displayed. 5. Depressing the NXI’ or PRV keys will cause the address display to increment or decrement to the next or previous group of 8 statuses or module, if in an expansion rack. All discrete references can be examined. The display returns to zero after the highest reference has been examined.
Monitor Timer or Counter Status - This operation sequence allows an operator to monitor the current accumulated value of a timer or counter. After installing the programmer, place the mode switch in the RUN position. Observe or perform the following actions: 1. The programmer will display the address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2. Enter the timer or counter reference to be monitored. For example, to monitor the operating status of timer 601, enter SHF, 6,0, 1. If a counter had been assigned reference 601, you would then be monitoring the status of counter 601. The valid references for timers or counters are 600 to 677. References 674,675,676, and 677 are reserved for use with the Thumbwheel Interface unit (Series One or One Plus) or the Timer/Counter Setpoint Unit (only for Series One Plus). Remember, each valid reference can be assigned to only 1 timer or 1 counter. 3. Select the Monitor function (MON). Note that the shift selected in the previous step is still in effect causing the RST key to select the monitor function. If the selected reference is not used in the program, error code EOl will be displayed. 4. The display will contain the current content (accumulated value) of the selected timer or counter. Timer values will be displayed in tenths from 000.1 up to 999.9 and counter values will be 0001 to 9999. The Logic Display will also show the two least significant digits of the timer or counter reference (for example, 01 for timer or counter 601). 5. The NXT and PRV keys move the display to adjacent timer or counters. Any timer or counter not actually used in the logic cannot be displayed.
Display a Specific Address - This operation sequence allows you to select and display a specific memory address (location) and the logic content of that address. After installing the programmer, place the mode switch in the RUN or PRG position. Observe or perform the following actions: 1. The programmer will display the address zero indicated by four zero digiti in the display, with decimal points to the right of each digit (O.O.O.O.), and the ADR LED lit. 2. Enter the memory address to be observed. For example, if the logic contained in address 36 is to be observed, SHF, 3 and 6 would be selected. 3. The NXT key is then selected and the display will contain the selected ad@s$. To display the content of this memory address, the NXT key is dep=ssed a second time. 4. At any time, selecting SHF then NXT will cause the display to go to address 0.0.0.0.
Page 72
4-14
PC Operation GEK90842
Monitor Data Register Contents (Series One Plus only) - This operation sequence allows an operator to monitor the current contents of any data register. After installing the programmer, place the mode switch in the RUN position and perform the following actions: 1 . The programmer will display the address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2 . Enter the reference for the data register to be monitored. Valid data register references are 400 through 577 and 600 through 673. For example, to monitor the contents of data register 452, enter the key sequence R 4 5 2 MON. 3 . The display will contain the address of the selected data register. 4 . To display the contents of the selected data register, depress the MON key a second time. The display will now contain the current contents (4digit BCD value) of the selected register. 5 . The NXT and PRV keys move the display to adjacent data registers.
Change Contents of a Data Register (Series One Plus only) - This opemtion sequence allows an operator to change the current contents of any data register. After installing the programmer, place the mode switch in the RUN position and perform the following actions: 1. The programmer will display the address zero indicated by four zero digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit 2 . Enter the reference for the data register to be monitored, following the steps in the previous operation. 3 . After depressing the MON key a second time and the current contents of the data register are displayed, the contents may be changed if desired. 4 . To change the cwTent contents of the displayed data register, enter the sequence SHF m ENT, where m is a 4digit BCD value having a valid range from 0000 to 9999. ‘The new value entered will write over &place) the value originally displayed.
Enter or Change a Password (Series One iMode E and Series One Plus) - This operation sequence allows an operator to enter a password or change a previously entered password. When a password is This prevents entered, all programmer tictions are disabled, except for the monitor f&nctions. unauthorized access to the program in a Series One Plus PC. After installing the programmer, place the mode switch in the RUN or PRG position and perform the following actions: 1. To enter a new password or change a previously CLR
SHF
9876
DEL
SHF
W entered password, use the following key sequence: ENT
NXI’
2. 9876 is a required sequence. Your password (XXXX) can be any numerical value from 0001 through 9999. The value 0000 is equivalent to no password, all programmer functions are operable when the password is 0000. If you do not have a requirement for password security, use 0000. To have access to all programmer functions when a password is in effect, a LOG IN sequence must be entered by the operator. After performing any necessary operations with the programmer, the operator must then enter a LOG OUT sequence to prevent any unauthorized access to the program. The LOG IN and LOG OUT sequences are shown below.
Access to Programmer Functions with Password in Effect(Series One M&l E and Series One Plus) After installing the programmer on a Series One Plus PC having a password in effect, place the mode switch in the RUN or PRG position and perform the following actions:
1. To LOG IN, enter the key sequence: CLR SHF 5678 DEL
SHF
=
2. The numerical value, 5678 is a required entry. selected by the operator.
ENT
NXT
XXXX is the password that had been previously
Page 73
PC Operation
4.15
GEK-90842
3. The operator can now monitor or change the program as required. When not using the programmer, the operator should then LOG OUT to return the programmer to password security. 4. To LOG OUT, enter the following key sequence. CLR SHF 1234 DEL
5. verify that the programmer functions
NXI have been disabled. NOTE
If the user should for any reason forget the password entered into the PC, use of most programmer functions would not be possible. If this should happen, contact the GE FanucAutomation service center in Charlottesville, Virginia for assistance.
Forcing References - The operation sequences described in this paragraph allow you to force an Input, Output, Shift Register, Timer, or Counter reference either on or off. Forcing the state of I/O references provides a convenient method of testing the operation of field devices and debugging the logic in the user program. If an input or output is forced on or off, it will remain in the forced state for 1 scan of the CPU. The programmer must be in the RUN mode to force any reference. After installing the programmer, place the mode switch in the RUN position. Use the following steps to force references. 1. The programmer will display address zero indicated by four digits in the display, with decimal points to the right of each digit (O.O.O.O.),and the ADR LED lit. 2. Enter one of the following sequences to force a reference either on or off as required: l To force a specific reference ON, enter the sequence: SET, SHF, m (Reference), ENT l To force a specific reference OFF, enter the sequence: RST, SHF, m (Reference), ENT 3. Repeat the above operation for other references to be forced.
When forcing input points with the set or rst sequence, the actual state of the input may be overridden. If the forced set or rst occurs in the user logic program before the input is checked in the same i/o scan, the set or rst state will take precedence and could cause an output to be turned on or off at the wrong time.
Operation With Peripheral Devices Several peripheral devices are available for use with a Series One or Series One Plus PC. The Programmer is required for operation with the tape recorder, when recording user programs. The tape recorder connects to the Programmer through the Programmer’s tape port. The tape port is located to the right of the mode switch and is labeled TAPE. The rest of this chapter describes the operation of these peripherals, which are listed below: Audio Tape Recorder Printer Interface Unit PROM Writer Unit
Various models Catalog Number IC61OPER151 Catalog Number IC61OPER154
Tape Recorder Operation Most audio tape recorders with auto-level control can be used with a Series One or Series One Plus PC. It is recommended that the recorder also be equipped with a counter to allow multiple programs to be record&Von tape. Units such as General Electric model 3-5148 have been tested and found fully compatible with the Series One family of PCs. This recorder is packaged with an interface module (not
Page 74
PC Operation
4-16 I
GEK-90842 required for the Series One or Series One Plus PCs) and can be ordered as Catalog Number 3-5156. The tape recorder allows three functions to be performed: (1) record a program onto tape, (2) load a CPU or peripheral from tape, and (3) verify the content of a tape. The operation of each of these functions is described below in a step-by-step manner. All logic memory is recorded on tape. Tapes created on Series One, Series One Model E or Series One Plus PCs can be loaded into any Series One, Series One Model E, Series One Plus or Series One Plus 3.7K PC Tapes created on the Series One Plus 3.7K PC can only be loaded into another Series One Plus 3.7K PC. A 2.5 foot (0.75 meter) audio cable (Catalog number IC6lOCBLl51), which is gray with a red tracer, is supplied with the programmer. This cable is used only with a tape recorder and connects it to the tape port on the programmer. Recording A Program 1 . Install the Programmer and apply AC power to the PC.
2 . Turn the mode switch on the Programmer to the LOAD position.
3 . Apply AC power to the tape recorder. Verify presence of the write protect t&b on a cassette and insert the cassette. If the write protect tab is not in place, data entered on the tape may be inadvertently erased. 4 . Adjust the tone control to its highest position. 5 . Connect the Programmer (TAPE port) to the tape recorder (MIC input) with the 2.5 ft. (0.75 m) audio cable (gray with red tracer). 6 . Rewind tape to the beginning or to the desired record position if multiple programs are to be placed on one tape. Programs require approximately 1.5 minutes (700 words), 4 minutes (1724 words) or 8 minutes (3.7K words), as applicable, of tape per program. 7 . For identification of a program, if desired, enter a four digit number (00009999) on the Programmer. When tape is accessed later to load the CPU, this number can be used to identify the comet program prior to altering CPU data. If a program number is not as expected, the operator can terminate the load operation and get the correct tape without loss of existing program nor delay incurred by loading a wrong program. However, this identification number is optional. 8 . Begin the tape recorder operation by depressing the RECORD button (and PLAY if required by the tape recorder). 9 . Depress the WRITE key on the Programmer. 10 . If after following with batteries.
all instructions,
The record operation will now begin.
reliable operation cannot be obtained, try operating the recorder
11 . When the record is complete, the Programmer will display End in the Address/Data display and the ON/OFF LED will be off. Stop the recorder and note the counter position so that the amount of tape used for that program can be determined. 12 . Depress the CLR (Clear) key on the Programmer to end the record operation.
13 . It is recommended that the tape be rewound to where the record began and that the Verify operation described below be performed to ensure data integrity.
Verif'yingAProgram 1. Install the Programmer and apply AC power to the PC. 2. Turn the mo& 3. Aply
I
’ .:.-=h on the Programmer to the LOAD position.
AC power to the tape recorder and insert the cassette containing the program to be verified.