Page 59

Chapter

4

PC Operation

4-l GEK-90842

Introduction to PC Operation After completing the installation procedures described in the previous chapter, your Series One or Series One Plus PC is ready for operation. This chapter describes the operation sequences for those PCs. A description of the features and functions of the programmer are the basis for the information in this chapter. The last portion of this chapter describes the operation of peripheral devices that can be used with the Series One or Series One Plus. The information in this chapter will allow you to become familiar with the programmer keys and the keystroke sequences required for the various programmer operations.

Programmer The hand-held programmer (figure 4-l), when connected to a PC by one of the three methods described in the previous chapter, can be used for entering a new program, examining a previously entered program, editing (changing) a previously entered program if required, monitoring the status of input or output points, displaying the contents of registers, and displaying timer or counter accumulated values. In addition, with the Series One Plus, a password can be entered with the programmer to protect the contents of your program from unauthorized or inadvertent entry or changing. Its features and functions are described in the following paragraphs. For detailed descriptions of the programming functions, refer to programming, Chapter 5.

a41 927

ADDRESS/

’

-AlmESSDAlAON OFF

STATUS DISPLAY

I

LOGIC DISPLAY

(r Le-a

RUN

II I

@++ pM4

;R

7ZR

“8

Sk

Sk

CL

S:T

OlpTAIII

I

Nib iii

R:l

R:G

1

BAT1

“”

( I(

LOGIC KEYS

DATA OP ERATION KEYS RUN f’f?G LOMJ

SHIFTED FUNCTION KEYS

T#‘E

MODE SWITCH

PERIPHERAL

NXT cl

JACK 6

Figure 4-l.

b6 EDITING

Programmer

Features

KEYS

Page 60

42I

PC Operation GEK-90842

Programmer Features The programmer features shown in the illustration on the previous page are described in this section. The descriptions of the features are keyed to the numbers (1 to 8) next to each feature in the illustration.

1 . Mode Switch This is a three-position keyswitch used for selecting the operating mode of the PC. This switch can be repositioned at any time as necessary without disrupting AC power. The left position (RUN) allows program execution with outputs enabled. The CPU scans its stored logic and allows timer/counter and relay contacts to be displayed. However, in the Run mode, changes to the logic are not allowed. In the center (PRG or Program) position, new programs can be entered and previously entered logic can be altered; however, no solving of the logic is performed. The right (LOAD) position connects the programmer to an external device such as a tape recorder through the adjacent tape port. Logic is not solved while in the LOAD position.

If a version A or B (IC610CPUlOlA OR IC61OCPUlOlB) CPU IS installed, the Series One programmable controller will always power up in the run (operating) mode unless a programmer is connected and the programmer is in the program or load mode. 2 . Address Data Display This is a four digit display used to indicate either the address, in decimal format, of where the display is in the user program stored in the PC’s memory or reference data used as a part of the logic. To indicate that addresses are being displayed, periods appear near the bottom and to the right of each digit (for example, 0.1.2.3.). The LED to the top right behind ADR will also be lit. 3 . Status Display These five LEDs are energized to indicate the following functions or status of the Series One:

ON/OFF When in the Run mode, this LED indicates the status of discrete Eferences (I/O, internal coils, and shift register stages). It is ON when a refance is energizd and OFF when de-energized.. RUN ON when in the RUN mode and CPU is solving logic. BATT ON when the voltage of tbe intemal lithium battery, which is used for maintaining the program stored in CMOS memory during no-power conditions, is at a low level and should be r~+placedwithin 10 days - see Chapter 7. This LED is OFF when battery voltage is OK, or battery is disconnected. PWR ON when the internal power supply is producing DC power. If OFF the rack power supply should be check4 - see Chapter 7. CPU ON when internal error checking has detected a fault in internal hardware - see Chapter 7.

The above four LEDs (RUN, BATT, PWR and CPU) duplicate the operation of the indicators on the CPU when tie programmer is installed. 4 . Logic Display These sixteen LEDs are used to indicate the type of logic entered into memory. While being programmed, they reflect the logic selected by the user prior to actual entry into CPU memory. For definition of the f!irst 12 LEDs fknctions, see key definitions under 5 below. The 4 LED’s to the right have special functions as follows: ADR

ON when display is indicating an adchss value. Tbe address is displayed in decimal notation, beginning at 0000 and ending at the last anntess in the user program or a maximum 6f I723 (maximum number of M-bit words in memory is 1724).

Page 61

43m

PC Operation GE&90842

SHF DA’IX REG

ON when operator has selected the Shift key and is an indication that future key selections will be based upon the upper key labels. Sbifi function will remain in effect until either the Enter or C&xr key is selected_ (Series One Plus only) On when monitoring the contents of a rqister and the AddxW/Data display contains the data @digit BCD value) in that register. The contents of 2 consecutive Ilegimers will be displayed. (Series One Plus only) On when monitoring the contents of a register and the ackkss of the selected register is displayed. The display can be alternated between REG and DATA by depressing MON.

These sixteen LEDs can also indicate the status of 16 consecutive I/O states when used with the monitor function discussed later in this chapter. The numerals above the alphabetical characters are used during this function. 5 . Logic Keys These twelve keys are used to select the required function and enter logic when in the Program mode. The upper labels are used to enter numerical values when preceded by the Shift key. Numerical values, when entered, are viewed in the Address Data display. The decimal point is used only for the entry of timer preset values in tenths of a second. The Monitor function will be discussed below as part of the Upper Case keys. The f&nction of the lower or normal case labels on these keys is described in the following key discussion. Places logic such as two contacts or two groups of contacts in series (see figure 4-2). Power flow must be possible through both elements before it will be passed to the next element. Places logic such as two contacts or two groups of contacts in parallel (see figure 4-3). Power flow can be possible through either (or both) elements before it will be passed to the next element.

OR

A-,..,,,,,,,J

L rr--rrr----a

Figure 4-2. Series Logic (AND)

NOT

OUT

Figure 4-3. Parallel Logic (OR)

Begins (Stats) a new group of logic and stores current logic results into a Last h Krst Out (UFO) pushdown stack. hverts the state of the refenzxed status to create a normally closed contact. NOT AND results in a normally closed series e NOT OR rest& in a norrually ched parallel contact. Specifiestbe end of a stzing of logic by entering a coil. With a valid reference, such as OUT 19, this coil will reflect the output of the rung of relay logic by turning ON or OFF as dictated by the pow- flow. Outputscan be paralleled by enteringadditionalOUT fbnctio~ at the end of a rung of lc-‘_ ;.

Page 62

44D

PC Operation GEK-90842

TMR

Specifies a timer function to end a rung of logic. The timer requires a unique 6XX reference for storage. Two types can be programmed (seconds and tenths of seconds) depending upon the numerical preset (with or without decimal point) entered after the 6XX reference. For example, 0.9 or 9.0 seconds can be programmed, depending on the ciecimal point.

CNT

Specifies a counter fhction to end two logic rungs. The two logic rungs requirtd by this function are count and reset. Count, being the tap rung of conditional logic. When all programmed conditions permit power flow, the counter will begin counting. The bottom rung is the reset rung and is programmed with the conditional logic required for resetting the counter. The counter also requires a unique 6xX reference for storage. Transition detection is a stand& built-in function.

SR

Specises a Shift Register function to end three logic rungs (input, clock, and reset). The reference used with SR (for example, SR 410) is the first stage of this shift register. The last stage must be entered immediately after the SR and its reference. A shift register can contain a total of 128 steps or several shift registers can be programmed, each with a di&rent number of steps, as long as the total of 128 steps is not exceeded

MCS

The MCS (Master Control Start) key specifies the beginning of a Master Control relay function. This provides an efficient method of programming for controlling large quantities of coils if a specific permissive condition is not satisfied_

MCR

The MCR (Master Control Reset) key sped& the end of a Master Control relay function. A similar number of MCRs must be entered to terminate, one at a time, the Master Control Start functions entered. One MCR terminates only one p~vious MCS function.

SET

Used with latches, shift registers, and coils. It specifies where latches are to be turned ON (set), shift register stages set to the ON state, or coils to be turned ON and not affected by internal reference 376 (disable all outputs).

RST

Performs functions similar to the SET key for latches, shift registers, and coils, except it specifies when these references will be turned OFF (reset).

6 Editing Keys These eight keys select the action required to modify either the stored logic within the CPU or the logic address being displayed. Those keys that can modify previously entered logic (that is, Delete and Insert) require a confirming key operation to ensure that the operation is to be executed. Thus, if they are accidentally depressed, the error can be corrected by depressing the CLR (Clear) key without actually affecting any entered logic. A description of each editing key is as follows: DEL

When logic is being displayed, tbis key (Delete) when included as the fhst keystroke of a two key sequence, will cause that single function to be moved (deleted) fium the CPU memory. To be effective, after depressing Delete, the PRV (Previous) key must be depressed, which executes the delete operation.

INS

This key (Insert) flows logic functions to be inserted between existing logic functions. The function or its ~sthatisafterthelocationatwhichtbeoewfunctionistobeplacedisnisplayed. Thenthenewlogicis built followed by the Insert key (not the Enter key) and the conhnhg NXT (Next) key. ‘Ihe new logic that is inserted by this key sequence will be placed in memory immediately before the displayed function or addZ&

ENT

The ENT (Enter) key is used to complete the entry of logic when initially building the CPU program or to replace an e&e single woTdfunction Logic functions are entered typically at the end of the existing logic.

Page 63

45(I

PC Operation GEL90842

CLR

The CLR (Clear) key, when select& clears the programmer of previously enuzd commands. If error codes are displayed, this key will aclmowledge the error and return the programmer to its normal (cleared) function. When monitoring a program, depressing Clear will cause the display to indicate the memary address in lieu of logic functions. When the key sequence CLR, SHF, 3,4,8, DEL, MCI’ is erasred, tbe enth contents of memory will be cleared.

NOTE This key sequence should be used with caution, be sure that you want to clear the entire program. Remember, if single functions or groups of functions are to be cleared, the DEL key, followed by PRV should be selected for each function to be cleared.

SHF

This key (Shift) locks all other keys to their shifted (upper label) functions and causes the SHF LED to be lit in the display area. The shift opemtion is ended by selecting the keys Clear or Enter. The SHF key must precede a numerical key or a group of numerals before selecting the numerical keys. For example to enter an open contact with input reference 12 as the first contact in a rung of logic, the key sequence would be SIR, SHF, 1,2, ENT.

SCH

This key (Search) allows the entire program to be searched for specific logic functions. The logic function is defined by the logic keys (without Enter), then Search is selected. The memory will be searched from the current location until either a match is found or all memory is searched. Successive depressions of this key will cause repeated searches with memory wrap-around. An unsuccessful search results in error code E99 being displayed.

PRV

When displaying logic or monitoring I/O state, selecting the PRV (Previous)B key causes the previous logic function or I/O status to be displayed. Additional depressions of this key cause the display to decrement until memory address zero is reached.

NXT

When displaying logic or monitoring I/O state, selecting the NXT (Next) key causes the next logic function or I/O status to be displayed. Additional depressions of this key cause the display to increment until the end of memory is reachezL

7. Shifted Functions The Shift key, when selected, causes most keys to change their function to those marked on the face of the programmer directly above the correspbnding keys. Normal unshifted functions are as placed Most of the shifted functions are used when entering numerical values on the keys themselves. (digits O-9 plus the decimal point). When entering a program, the unshifted functions must be selected first (AND, OR, NOT, OUT, TMR, etc.), then the SHF is selected to enter the numerical portion of the program. The use of the other four shifted tictions are as follows: MON

When in the Run mode, this fhction allows the user to monitor the m of I/O ndhxxes in two successive groups of 8. The specified I/O reference is used to select the fust 8 referezxxs d the next group in numerical sequence is also shown to provide a total of 16 real time m. The specified xlefiexenceshould be the first refhwe in a group of 8, for example, specify 10 to mcmitor the I/O group 10 to 17. If a reference otherthan~first~inagroupisspecifiedmonitaringoftbeI/Owill&~ttotbefirst~~renceinthe group. After the refemace (for example 043) is entered and displayed (for example 040) as ristn. the status of the 8 references in that group (for example 040447) are displayed by the first 8 T’s (AND, OR, STR, etc.) in tbe logic display. W ~lext 8 references (e.g. 050) are also displayed and their status is indicated by tbe last 8 LED’s (MCS, MCR, SET, etc.). These 16 LED’s will be ON or OFF as the I/O assigned to these dzences is energized or de-eoergized As the x/o changes, the state of the LEDs changes.

Page 64

m 46

PC Operation GE&90842

To display another group of I/O refenxxes, the PRV or NXI’ key can be selected to decrement (40,30,20, etc.) or increment (50,60,70, etc.) the group number and its associated refe=nces. Ref&ences up to 577 can be displayed; there is automatic wrap-around from 570 to 000 (NXT) or 000 to 570 (PRV). The cumznt values of timers and countem can also be monitored by entering TMR or CNT, SHF, 6n (timer or counter reference) followed by MON (the Monitor Key). WRITE

This function operates with an audio tape cassette recorder or certain other peripherals to effect a transfer of the CPU’s logic to the peripheral. Connect the device to the tape port with the audio cable supplied with each programmer or peripheral. Set the mode switch to LOAD and turn the device ON. To begin the transfer, select the WRITE key. This starts the writing of the CPU logic onto the cassette or other peripheral. For more detailed information on transferring data to peripheral devices, refer to the discussion of each peripheral .

READ

This function operates with the audio tape cassette recorder or other peripheral to load a CPU’s memory from the cassette or other storage device. Connect the device to the tape port with the audio cable supplied with each programmer or peripheral. Set the mode switch to LOAD and select the READ key. To begin the CPU loading, turn the device ON. This starts the reading of the tape and the loading of the stored program into the CPU memory. CHECK

8

This function operates with the audio tape recorder or other peripheral to verify proper program transfer. After a transfer is made, it should be & back similar to the READ above; however, the CHECK key must be selected instead of READ. The Check operation does not alter either the CPU logic nor the data in the peripheral. A data compare is made between the two sow of information to ensure that there has been no error in the nzording process. 1*

WP

Data Operanon Keys These two keys are used during entering the data operations when programming the Series One Plus PC. These keys have no effect when this programmer (Catalog no. IC610PRGi05) is used to program a Series One PC. The function of each of these keys is described below. F

This key must be depressed before a 2digit value corresponding to the data operation or Function to be performed (for example, F50, F62, F74, F82, etc.). A complete list of the data operations and their Function number can be found in Chapter 5, Programming. The shift key does not need to be depressed immediately before the fWction numbers as must be done when selecting other numerical values when programming a Series One or Series One Plus PC.

R

‘Ibis key serves a dual function, in that it is used to select either a data register or a Timer/Counter accumulated value qister, or a group reference number when programming data operations. A register is operated on as a word (16 bits) in the Series One Plus PC. When a 3digit data nsgister reference (400 to 577) is specified, two cmsecutive 8-bit registers are actually selected to write data to or read data from. For example, if R followed by the reference 410 is entered, registers 410 and 411 are selected for that data operation. If R 6 10 were entered, the accumulated value register for the timer or counter assigned to that ref&rencewouldbespec&dinadataoperaticm. UnusedT/Cre~~~,600-673canbeusedasdata II?giWrs. A register can be qxified to contain a Timer or Counter preset value. In this case the register reference (R xxx) is specified immediately following the Timer or Counter reference wkn programming a Timer or Counter. A group reference is a 1, or 2 digit r&zence corqxmding to the first 1 or 2 digits of a group of 8 consecutive dismete references. These references can be ti I/D points, intemal coils, or shift rq&ters. For example, if the R key followed by 37 is enmwi, the reference is to dixrete points 370 thmgh 377. If R 5 is entez=& the refemce is to I/O paints 050 tlumgh 067 (W-057 and 060-067).

Page 65

47m

PC Operation GEK-90842

9. Peripheral Jack This is a serial port which allows connection of an audio cassette tape recorder to record (save) the user memory, verify the contents of a tape against the contents of user memory, and load a program stored on tape into user memory. It is recommended that programs entered into user memory be saved on tape, once they have been verified as being correct. Note that when recording a Series One Plus program on tape, the contents of the data registers are not saved.

prOgram

Stored in

Program Checking and Error Codes When entering ladder logic programs with the programmer, the CPU automatically performs many checks on the data and operations selected by the programmer. Functions entered are checked for proper key sequence, proper range of references entered, etc. Errors detected during these checks ax indicated in the data display by the letter E followed by a two digit code (01-99). The CPU also performs a partial program error check any time that the PC is switched to the RUN mode. After entering a program a manual error check should be performed, which checks the entire program. Table 4-1 summarizes the meaning of each error code, its cause, and possible methods of clearing the error. The use of the programmer to enter logic is documented in Chapter 5 as part of programming. However, there are many other valuable functions it provides which are shown in the following table:

Table 4-l. Error

Code Definitions

Applicable Mode Code Run Prog Load X

SigllifiCaIlCe

Cause

Corrective Action

El

X

E2

X

Fault inPmgmm Strut- CPU has detected ezror in pro- Go to Program mode. Depress ture. Series One. gram when placed into RUN CLR. Address of faulty logic will mode. Example: Input module be shown. Depress NXT to display contexx reference used as coil

E2

X

Fault in Program Strut- CPU has detected error in pro- Go to Program mode. Depress Address of ture. Series One Plus. gram when placed into RUN CLR-SCH-CLR. mode. Example: Input module faulty logic will be shown. DeIleference used as coil. press NXT to display content.

E3

X

Stack Capacity Exceed- More than eight status levels at- Go to Program mode. Depress ed tempted to be stored in pushdown CLR. Programmer will display location of first 9th STR error. stack Examine logic and reprogram as ==ssary*

E5

X

Duplicate ence x

Incomct opemtion

Operator attempted to perform il- Examine operation. Depress legal operation such as changing CLR. Reinitiate proper function. program in RUN mode.

Coil Refer- Coil (output, intemd, timer, or GO to Program mobe. Depress c0unter) used as an OUT more CLR. Programmer will display location of SecOnd coil of pair usthan once. ing same r&%nce. Enter another coil retice. I

Page 66

48I

PC Operation GEK-90842

Table 4-l. Error Code Definitions - Continued Applicable Mode Code Run Prog Load

SigXliiiClD~

Corrective Action

Cause

E6

X

Incomplete Control

E7

X

Irmmplete Counter or Ail control lines not provided to Go to Program mode.

Master More MCR references than MCS Go to Program mode. Depress CIR. Programmer will display in program. first unmatched MCR. Correct program by deleting MCR or adding MCS.

Shift Register.

X

E8

E9

E21

Incorrect Operation.

Operator attempted to write in- Depress CIR. struction on second word of a 2-word instruction.

Incomplete Logic.

Relay ladder line not connected to Go to Program Mode. Depress coil; relay contact(s) left incorn- CLR. Programmer wiIl display first unfinished logic element. plete or hanging. Add logic to tie this element into stored logic, or delete element(s) to remove incomplete logic.

X

Memory Full.

Operator attempting to add logic Depress CLR. Restrucm program so that lo@ limits will not to CPU already at limit. be exceeded.

x

Parity Failure.

CPU has detected a fault in the Go to Load Mode. Depress CLR. parity structure of its internal Reload memory from previously recorded tape or clear entire memmemory. ory and reload manually. If BAIT light not ON and fault cannot be cleared, replace CPU module .

X

El1 x

Depress one or more Counters and/or Shift CLR. Programmer will display Registers. errant function. Add required reset, clock or clear lines.

E25

X

Faulty Comparison.

External device such as tape cas- Depr~s CIR. Verify cornxt prosette has content that does not gram number or tape. If corr~%, either re-record tape or reload agree with CPU memory. CPU.

E28 x

We& R#zo!rd SignaL

Playback Signal level, such as Adjust volume level on tape refrom tape recorder, is below ac+ corder or other peripheral device. If ON steady for extended period ceptable level. of time, restart function to obtain reIiable operation.

unsuccessflll search,

Search function has reviewed all Depress CIR. To cause an addimemory 8nd has not located re- tional search, re-enter fun&or andquirea

.

E99

X

X

Operation Sequences An understanding of the basic PC operation sequences is necessary in order to effectively and efficiently enter ladder diagram programs. You should be familiar with the use of each key, alone and in sequence