Page 51
Installation GEK-90842 a40282
Figure 3-9. Proper Module Insertion 19. Tilt the module approximately 10’ as shown in figure 3-9. Insert bottom of the large printed circuit board into the bottom card slot.
20. When the bottom slot is engaged, rotate the module to engage top slot. Slide module into base unit until it is firmly seated and snap locks engage.
II0 21. Other modules are installed into racks at slot locations as determined by installation plans.
Follow steps 19 and 20 above for each I/O module.
22. To remove a module, squeeze the snap locks top and bottom (see figure 3-10) towards the center and pull the module straight out. Squeeze force should be approxbately 10 pounds (5 Kg) and pull force 8-12 pounds (4-5 Kg). a40283
Figure 3-10. Proper Module Removal
Page 52
3-10
Installation GEK-90842
Power
Co~ections
23 . AC or DC power connections are made to the terminal strip on the far right of each unit. See table 3-l for power requirements. The minim um recommended wire size for power connections is AWG No. 18 (lmm). 24 .
Strip 0.4 2 0.1 inches (10 & 2mm) of insulation from each wire (hot, neutral, and ground or + and -) or place a No. 6 insulated lug (ringed or forked) onto each wire.
25 . Remove plastic cover over terminal strip and retain. Connect the hot wire to the top terminal. The neutral is connected to either the next (second) terminal for 115 V ac operation or the third terminal for 230 V ac operation as marked on the base unit. For 24 V dc racks, connect the + and - terminals to the DC power source.
Do not use the top screw for power connections; it secures the terminal block connections before applying power.
Verify
26 . Connect an earth ground wire to the rack mounting bracket as shown in figure 3-2. (Typically this ground wire is the green wire from the ac power source.)
Ensure that aI1 exposed wiring is either under the screw-down plate of the terminals or insulated by shrink tubing or sleeves. 27 . The terminals labeled +24 V dc and -24 V dc provide 24 V dc @ 100 mA for connection external sensor (not on IC61OCHSlOl).
to an
28 . The two remaining terminals are used with the RUN indicator.
Use of this standard feature on all racks is optional. It can be used to drive an external indication of the functional state of this rack. The Run relay is closed when the CPU is scanning (not on IC61OCHSlOl).
29 . If the Run indication is desired, it can be wired separately to an external indicator (light, bell, whistle, etc.) or in series with other racks. Follow steps 24-25 above for guidance on connecting these wires. Then replace the plastic cover.
If0 Field Wiring 30 . Recommended wire size for connection to the I/O modules is stranded AWG No. 12 (0.65~2mm) wire. Two wires per terminal are possible with AWG No. 14 (0.65.1.6mm) wire. 31 . Strip 0.3 i 0.05 inches (8 * 1.5mm) from each wire to be connected to the I/O modules or install a No. 6 insulated lug (ringed or forked). Bare wire co~ections are recommended for multiple wire co~ections to one terminal. 32 . Carefully remove plastic covers over I/0 terminal sliding it to right or left.
co~ections by lifting top or bottom leg and
33 . starting with the lower terminals, connect the field wires to all UO terminals. Power connections such as those to commons (C) should be made last. No co~ections are required to unused circuits; however, screws on unused terminals should be tightened.
Page 53
Instdlation
3-11
GEK-90842
34. For 16 point I/O modules that connect to I/O through a connector on the faceplate, connector on the I/O Interface cable to the connector on the module.
secure the
Ensure that wires to the top set of terminals do not extend beyond the screw-down plate. Any wire exposed before the terminal plate must be covered by shrink tubing or sleeves. 35. Wires should be laced together to leave a service loop adequate for removal of I/O modules without discoMecting wires. See figure 3-11. After testing of I/O wiring, replace plastic covers.
a4001 7
Figure 3-11. Typical Routing of I/O Wiring Programmer 36 . The hand-held programmer (catalog no. IC61OPRGlOO or IC61OPRG105) can be placed over the CPU and power supply for permanent or temporary mounting. Its connector fits into the receptacle on the CPU and it snap locks onto the power supply. 37 . If an extender cable is used with the programmer, it should be installed next or when required. One end of the cable has a push tab (see figure 3-12). This end is connected to the programmer (see figure 3-13). The other end is connected to the 26.pin coMector on the CPU. Both ends m keyed for proper instaIlation. The red edge of the ribbon cable is installed up at both ends.
Page 54
Installation
342
GEK-90842 a40163
Figure 342. Pull Tab on Programmer Cable NOTE For proper noise immunity, it is recommended that the extender cable be used on a temporary basis and not permanently installed with the programmer.
38. TO installthe programmer directly onto the CPU, align the programmer on the outside dimensions of the power supply and gently push down to engage snap locks.
To ensure proper. CPU operation, it is recommended that the programmer not be connected nor disconnected with ac power applied.
83-pc-35m m-4-3-3 1a
Figure 3-13. Installation of Programmer Cable
Page 55
Installation
3-13
39. The Programmer Mount Assembly (catalog no. IC610PRG190) can be used when installing the hand-held programmer on the outside of a panel or console, or can be used as a table top stand for the programmer. Figure 3-14 shows how to install the mounting assembly. The CPU/Programmer cable must be ordered separately. a40148
*cABLEwsTBE OmEREDsEPARAELY
Figure 3114. Programmer Mount Assembly
Power Supply Limitations for Racks If the power supply in either a CPU or expansion rack should become overloaded, unpredictable system operation may occur. To ensure that this does not happen, the total current capabilities of the modules placed in the rack must not exceed the current carrying capabilities of the rack power supply.
Units of Load The power used by each module is expressed in (units of load), where 1 unit equals 10 mA. Calculations are based on the worst case condition with all inputs and outputs on. Table 3-4 list the units of load supplied by each rack, and table 3-5 is a list of units of load used by each module. When configuring a rack, note the units of load supplied, then add the total units of load used by the modules you have selected. The total units of load for the modules must not exceed the total units of load supplied by the rack. If they do, the system should be redesigned.
Page 56
3-14
Installation GEK-90842
Table 3-4. Units of Load Supplied by Rack CATALOG NUMBER
POWER SUPPLIED IN UNITS OF LOAD RACK DESCRIPTION
+s v
+9 v
+24v
+24VExtemaI
*If an external sensor is connected to the 24 V + and - terminals on the power supply, the current used by the sensor (up to the maximum of 100 mA), should be deducted from the available listed units of load.
Table 3-S. Units of Load Used by Modules
CATALOG NUMBER
IC6lOCPUlOl IC61OCPU104 IC61OCPU105 IC61OCPU106 IC610PRGlOO IC61OPRG105 IC61OMDLlOl IC61OMDL103 IC61OMDL104 IC61OMDL105 IC61OMDL106 IC61OMDL107 IC61OMDLllO IC61OMDLlll IC61OMDLll2 IC6lOMDLll5 IC61OMDL124 IC61OMDL125 IC6lOMDL126 IC61OMDL127 IC61OMDL135 IC6lOMDL151 IC61OMDL153 IC61OMDLl54 IC61OMDL155 IC61OMDLI ,-“: IC61OMDL157
L MODULE DESCRIPTION CPU CPU25 CPU CPU Programmer Programmer 24 V dc Sir& Input (8) 24 V dc In/Out (4/4) 24 v dc In/Relay out (4/4) Thumbwheel Interhce 24 V dc Sink In wm (16) 24 V dc Sink Load In (16) High Speed Counter 24 V dc ac/dc Input (8) 24 V ac/dc Source In (16) Fmt Resgonse UO (4/2) m Simllatm (8) Inputs 115 V ac Input (8) 115vacIsolatedIIpt(4) 230 V ac Input (8) UL, 115 V ac Input (6) 24 V dc Sink Output (8) 24V&2ASinkOut(4) 24 v dc sink/Soum! out (4) 34 V dc Source Output (8) ’ G. -J dc Sink Out W/WEDS(16) I 24VdcShkOutw/LEDs(16)
POWER USED IN UNITS OF LOAD +s v
+9v
25
- m
25 25 6 6
_
+24V
I)
5 5 1 2 20 1 3 3 7 1 13 8 1 1 1 1 1 2
10
7 6 9 24 23 m
6 11 1
0 10
Page 57
Installation
345
GEL90842
Table 36. Units of Load Used by Modules - Continued CATALOG NUMBER
IC61OMDL158 IC61OMDLl75 IC61OMDL176 Ic61oMDL18o IC61OMDL181 IC61OMDL1.82 IC61OMDL185 IC61OCCM105 IC61OCCMllO IC61OCCMlll IC6lOPERlSl IC61OPER154 IC609CTUlOO
MODULE DESCRIPTION
POWER
USEDINUNITSOF
LOAD
+s v
+P v
+24 V
24 V dc Source Out w/LEDs (16) 115/230 V ac Output (8) 115/230 v ac Isolated OUT (4) Relay Output (8) UL, Relay Output (5) Relay Output (16) UL, 115 V ac Output (6) Data Communications Unit I/Ok&Local I/O Ihk Remote Printer Interface Unit PROM Writer Unit Timer/Counter Setpoint Unit
1 unit of load = 10 m4.
Calculations are based on the worst case, that is, all inputs and outputs on.
Safety Considerations When planning the layout of a system, safety should be a prime consideration. System planning should include procedures and methods to ensure the physical safety of personnel, the Series One or One Plus Those personnel who are involved in the system and the equipment or process being controlled. planning and installation of a system should be familiar with all local and national electrical codes as well as installation instructions in this manual. All practices should be followed that are specified by the IEEE (Institute of Electrical Engineers) Standard 510 which includes tray and conduit spacing and wiring procedures. standard can be obtained by writing:
and Electronic A copy of this
Institute of Electrical and Electronic Engineers 345 East 47th Street New York, NY 10017
Recommended Field Wiring Procedures The following Drocedures are recommended _ _ when runnine. field wiring: Low-level $nal wires should be separated fkom other yfield wiring.”
AC power wiring should be separated from DC field wiring. . Wiring should not be routed near devices causing electrical interference. If severe noise problems are present, additional power supply filtering or an isolation transformer may be required. Contact your GE Fanuc Automation sales representative if assistance is required. Proper grounding should be provided to minim& hazards to personnel. Label all I/O wires. Circuit numbers or other identification can also be marked on the cover over the wire terminals on each ?!O module. I/O wires should be no larger than No. 12 AWG.