Two-page GE Intelligent Platforms brochure from 2010 on Genius distributed I/O, covering the Genius LAN, CPU redundancy, block diagnostics, bus length and an ordering table of IC660 discrete and analog blocks with the diagnostics each supports. The BBD022 and BBD025 blocks appear only as rows of that table, and the IC660EBD020L, IC660EBD021C and IC660EBD025C are not named.
- Network
- Genius blocks talk to the system CPU over the Genius LAN instead of rack-mounted I/O p. 1
- Bus length
- 7500 feet with 16 devices at 38.4 Kbaud; 3500 feet with 32 devices at 153.6 Kbaud ext. p. 2
- Redundancy
- With two or more CPUs, blocks shift automatically to a backup CPU if the main controller stops communicating p. 1
- Diagnostics
- Field wiring, power conditions, loads, and the state of the network, blocks and circuits p. 1
- Discrete diagnostics
- Open wire, failed switch, over temp, loss of I/O power, no load, over load, short circuit, load state feedback, pulse test (varies by block) p. 2
- Discrete blocks listed
- IC660 BBD101, BBS102, BBS103, BBD110, BBD020, BBD022, BBD021, BBD023, BBD024, BBD025 p. 2
- BBD025 diagnostics
- BBD025: failed switch is an output diagnostic only; over current is reported as failed switch; load state feedback shows the output switch, not the load p. 2
- Analog blocks
- BBA020, BBA024, BBA025, BBA026, BBA021, BBA023: 24/48 VDC; BBA100: 115 VAC; BBA104, BBA105, BBA126, BBA101, BBA103: 115 VAC/125 VDC p. 2
- Family
- 20 different I/O blocks, PLC interface modules and third-party interfaces p. 2
- Mixed I/O
- Genius I/O blocks, VersaMax and Field Control can share one Genius LAN p. 1
- Hosts shown
- System diagram shows PACSystems RX3i and RX7i, Series 90-30 and Series 90-70 PLCs, 90-70 Remote Drop and VersaMax I/O Station p. 2
- Brochure
- GE Intelligent Platforms, 2010, GFA-155I p. 2
What this sheet walks you through
- How Genius blocks handle CPU, bus interface or cable failure in a redundant setup p. 1
- What the built-in block diagnostics report p. 1
- Ordering table of discrete, relay, counter and analog blocks with their diagnostics p. 2
- Maximum bus length by device count and baud rate p. 2
Good to know
- On the BBD025, load state feedback reports the output switch state only, not the load itself. p. 2
- On the BBS103, failed switch diagnostics caused by certain field wiring conditions are deliberately suppressed. p. 2
Questions this sheet answers
How long can a GE Genius bus be?
7500 feet with 16 devices at 38.4 Kbaud, or 3500 feet with 32 devices at 153.6 Kbaud ext. p. 2
What happens to Genius I/O blocks if the main PLC fails?
In a redundant setup with two or more CPUs, the blocks shift automatically to a backup CPU when the main controller fails to communicate. p. 1
What diagnostics do Genius I/O blocks give?
Information on field wiring, power conditions and loads, plus the state of the network, blocks and circuits. p. 1
Does the IC660BBD025 load state feedback show the load?
No. On the BBD025 it indicates the state of the output switch only, not the load. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
GE Intelligent Platforms
Genius* Distributed I/O By providing distributed control on the factory floor, GE Intelligent Platforms’ Genius* I/O systems offer fewer terminations to document, dramatically shorter wiring runs, and simpler, more effective troubleshooting. In a host of industries, from steel to food processing to automotive, more than half a million Genius blocks are helping companies meet the challenge of an increasingly competitive marketplace.
Genius Technology Provides the Cornerstone for Redundancy.
Genius is a Simple and Efficient Communication Network.
Genius blocks provide predictable system operation in the event of a CPU, bus interface, or network cable failure. When connected in a redundant configuration with two or more CPUs running simultaneously, the Genius blocks will shift automatically to a backup CPU if the main controller fails to communicate.
As opposed to traditional rack-mounted I/O, Genius blocks communicate with the system CPU over a network – the Genius LAN. The Genius LAN greatly simplifies system installation, and network tools such as the hand-held monitor makes troubleshooting easy.
Genius Advanced Diagnostics Reduce Costs. Genius I/O blocks automatically provide diagnostic information on field wiring, power conditions, and loads, as well as the state of the communication network, blocks, and circuits. Genius diagnostics sharply reduce the time needed for initial control and debugging.
Genius Performs Equally Well with High- or Low-Density I/O. Many different GE I/O products may be integrated into a single Genius LAN including Genius I/O blocks, VersaMax* and Field Control*. This flexibility allows users to deploy the most efficient combination of high-density and low-density distributed I/O for their application.
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Genius* Distributed I/O Product Features
CPU
Genius Open Architecture simplifies system integration. The Genius family includes 20 different I/O blocks, a variety of PLC interface modules, and a growing number of thirdparty interfaces.
Bus Controller
Power Supply PACSystems RX3i
Series 90-30 PLC Series 90-70 PLC
I/O ScannerPACSystems* RX7i90-70 Remote DropVersaMax I/O Station
Maximum Bus Length 7500 feet with 16 devices at 38.4 Kbaud 3500 feet with 32 devices at 153.6 Kbaud ext.
Genius I/O
Field Control I/O
Ordering Information Block Type
AC Discrete BlocksDC Discrete BlocksCatalog Number IC660
Input Input and Output Open Wire Failed Switch Over Temp Loss of I/O Power No Load Over Load
Output Short CircuitLoad State FeedbackPulse TestBBD101xxxxxxxxBBS102xxxxxxxxxBBS103x4xxxxxxxBBD110xxBBD020xxxxxxxxBBD022xxxxxxxxBBD021xxxxxxxxBBD023xxxxxxxxBBD024xxxxxBBD0251x23xRelay BlocksBBR100High Speed CounterBBD120
BBR101 (1) Failed switch is output diagnostic only. (2) Over current condition is reported as failed switch. (3) Load state feedback indicates state of output switch only, not the load. (4) Failed switch diagnostics resulting from certain field wiring conditions are intentionally suppressed. Block Type
Analog Signal Blocks
Catalog Number Input Power IC660
Open Wire
High Alarm
Input Only Low Alarm Int. Fault
Wiring Error
Input Short
Input and Output Under Range Over Range
Output Only Feedback Error
BBA02024/48 VDCxxxxxBBA100115 VACxxxxxBBA02424/48 VDCxxxxxxBBA104115 VAC/125 VDCxxxxxxBBA02524/48 VDCxxxBBA105115 VAC/125 VDCxxxxxBBA02624/48 VDCxxxBBA126115 VAC/125 VDCxxxBBA02124/48 VDCxxxBBA101115 VAC/125 VDCxxBBA02324/48 VDCxxBBA103115 VAC/125 VDCxxxxxxxxxxxxxxxxxxxxxxx
GE Intelligent Platforms Contact Information Americas: 1 800 433 2682 or 1 434 978 5100 Global regional phone numbers are listed by location on our web site at www.ge-ip.com/contact
www.ge-ip.com ©2010 GE Intelligent Platforms, Inc. All rights reserved. All other brands or names are property of their respective holders. Specifications are subject to change without notice.