16 Circuit DC Input/Output Blocks, from the Genius I/O Discrete and Analog Blocks User's Manual
Manual23 pagesPDF 1.3 MB
GE Fanuc Genius I/O manual section for the 16-circuit 24 VDC and 24/48 VDC source and sink I/O blocks, incl. IC660EBD021.
Names · 3 models
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
A section of the GE Fanuc Genius I/O Discrete and Analog Blocks User's Manual covering the four 16 Circuit DC Input/Output blocks: 24 VDC and 24/48 VDC source blocks and 24 VDC and 24/48 VDC sink blocks, each sold also as terminal assembly or electronics assembly (IC660EBD020, IC660EBD021). Each circuit can be an input, tristate input or output. It gives specifications, block operation, input and output data formats, diagnostics, field wiring, and the block configuration features and worksheet.
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Chapter 8 of the GE Fanuc Genius I/O Discrete and Analog Blocks User's Manual (GEK-90486D-2, September 1993), on the 16 circuit DC input/output blocks: sink blocks IC660BBD021 (24/48 VDC) and IC660BBD023 (24 VDC), and source blocks IC660BBD020 and IC660BBD022. It gives specifications, field wiring, diagnostics and the Hand-held Monitor configuration steps. It names the sink-block electronics assembly as IC660EBD021, without the C suffix, and does not name the IC660EBD025C.
- Device
- Genius 16 circuit DC I/O block; each circuit can be an input, tristate input or output p. 2
- IC660EBD021
- IC660EBD021: electronics assembly only, listed for sink blocks IC660BBD021 and IC660BBD023 p. 3
- Sink blocks
- IC660BBD021: 24/48 VDC sink block for 3-wire sensors; IC660BBD023: 24 VDC sink block for 2-wire and 3-wire sensors p. 2
- Block power
- No separate block power supply; control power comes from the I/O device voltage p. 2
- Operating voltage
- 18-30 VDC (24 V blocks); 18-56 VDC (24/48 V blocks) p. 3
- Output current
- 2 amps per circuit p. 3
- Compatibility
- Any Genius bus controller, PCIM or QBIM module; all Genius Hand-held Monitors p. 2
- Sink input levels
- Sink blocks, 24 VDC supply: input ON 0-8 VDC, OFF 17-24 VDC p. 3
- Tristate resistor
- 24/48 VDC blocks: 5.1K ohm, 1/2 Watt or larger, across the dry contacts p. 9
- Size and weight
- 8.83 x 3.50 x 3.94 in (22.44 x 8.89 x 10.00 cm), height x width x depth; 4 lbs. (1.8 kg) p. 3
- Operating temperature
- 0 to +60C (32 to +140F) p. 3
- Output diagnostics
- Short circuit, overload, no load, failed switch, overtemperature p. 3
- Bus baud rate
- 153.6 Kbd standard (default), 153.6 extended, 76.8 or 38.4 Kbd p. 11
- Overload shutdown
- Optional per output; trips when a load exceeds 2.8 amps DC p. 8
What this manual walks you through
- Wiring inputs and outputs to a DC sink block p. 9
- Field wiring: terminal sizes and DC power connections p. 9
- Wiring power disconnects so block and input power are removed together p. 10
- Wiring a Bus Switching Module p. 10
- Understanding the overtemperature, short circuit, failed switch, open wire, no load and overload diagnostics p. 6, 7, 8
- Configuring the block with a Hand-held Monitor p. 11
- Pulse testing outputs p. 13, 14
- Choosing the input filter time p. 15
- Setting hold last state and output defaults for loss of CPU communications p. 18, 19
- Setting CPU redundancy and configuration protection p. 22, 23
Good to know
- Turn off the No Load diagnostic for outputs whose very small loads (small relays, transformers, indicating lamps) draw less than 50 mA. p. 8
- If circuit power is not removed at the same time as block power, the block may power up when several inputs are activated. p. 10
- The Short Circuit diagnostic detects shorts across the load only. p. 6
- Photo-sensors, high-speed counters, instrumentation and fiber optic sensors cannot be monitored for Open Wire and should be standard inputs. p. 7
- With Overload Shutdown off for loads above 2 amps, the manual limits load current to 5 amps DC, ON time to 1 minute and all outputs together to under 16 amps. p. 8
Questions this manual answers
What is the IC660EBD021?
The electronics assembly alone, listed for the Genius 16 circuit DC sink I/O blocks IC660BBD021 (24/48 VDC) and IC660BBD023 (24 VDC). p. 2, 3
What resistor do tristate inputs need on a 24/48 VDC block?
A 5.1K ohm resistor, 1/2 Watt or larger, across the dry contacts of the input device; it is needed for the Open Wire diagnostic. p. 9
How much current can each output of a Genius 16 circuit DC block switch?
2 amps per circuit. With Overload Shutdown turned off, a load may draw up to 5 amps DC within the manual's duty cycle and ON time limits. p. 3, 8
What does the NO LOAD message mean on a Genius DC block?
The load on the output did not continuously draw 50mA. The manual says to disable this diagnostic for very small loads under 50 mA. p. 8
How do I protect the block configuration from changes?
Configuration Protection is selected only from the Hand-held Monitor, and the manual says to protect the configuration before the block is used in the system. p. 23
The whole text · 3 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file